Redlion IRMA Скачать руководство пользователя страница 3

WIRING CONNECTIONS

All conductors should meet 

voltage and current ratings for 
each terminal. Also, cabling 
should conform to appropriate 
standards of good installation, 
local codes and regulations. It 
is recommended that power 
supplied to the unit be 
protected by a fuse or circuit 
breaker. When wiring the unit, 
use the numbers on the label to 
identify the position number 
with the proper function. Strip 
the wire, leaving approximately 
1/4" (6 mm) of bare wire 
exposed (stranded wire should 
be tinned with solder). Insert 
the wire into the terminal, and 
tighten the screw until the wire 
is clamped tightly.

INPUT AND POWER/OUTPUT CONNECTIONS

INPUT

When connecting the RTD or resistance device, be certain that the 

connections are clean and tight. Attach the device to terminals #2 and #3. Install 
a copper sense lead of the same gauge as those used to connect the device. 
Attach one end of the wire at the probe where the lead connected to terminal #2 
is attached and the other end to terminal #1. This configuration will provide 
complete lead wire compensation. If a sense wire is not utilized, then Terminal 
#1 should be shorted to terminal #2. To avoid errors due to lead wire resistance, 
field calibration should be performed with a series resistance equal to the 
total lead resistance in the system. Always refer to the probe manufacturer’s 
recommendations for mounting, temperature range, shielding, etc. 

POWER/OUTPUT

The unit has the power and current output sharing the same two wires (loop-

powered). Connect DC power to terminals #4 and #5, observing the correct 
polarity, with a current meter/indicator connected in between so that the output 
current can be monitored.  Be certain that the DC power is relatively “clean” 
and within the 12 to 42 VDC range at  the terminals. The current meter voltage 
drop must be included in the power supply considerations.

DIP SWITCH SETTING DESCRIPTIONS

Range switch settings (ON = 1  OFF = 0)

FACTORY SETTINGS

The unit is shipped from the factory calibrated for a 4 to 20 mA output using 

a type 385 RTD in range 0. The IRMA should be calibrated by the operator for 
the application environment it will be used in. If the unit is not recalibrated by 
the operator, the following table lists the temperature ranges for each RTD type.

SWITCH

DESCRIPTION

1

OUTPUT CAL

Output Calibration

2

FIELD CAL

Field Calibration

3

BASIC CAL

Basic Calibration

4

385/392

Select RTD alpha - 0.00392 (ON) / 
0.00385 (OFF)

5

OPEN SEN DN/UP

Open Sensor Detection - 
Upscale (ON) / Downscale (OFF)

6

RTD/OHMS

Select Input Type - 
Ohms (ON) / RTD (OFF)

7

8

RANGE

Sensor Range - 2 switch 
combination setting

DIP SWITCH

RANGE

7

8

0

0

0

1

0

1

2

1

0

3

1

1

2

1

3

RTD

S

-

+

-

RTD

+

1

S

2

3

RTD

1

S

2

+

3

-

3-WIRE RTD

4-WIRE RTD

N.C.

2-WIRE RTD

150

C to 595

C

0

392

150

C to 606

C

0

385

TEMPERATURE RANGE

RANGE

TYPE

Current Display

Indicator or

Power Supply

12 to 42 VDC

4 to 20 mA

±

A

OUTPUT

POWER/

+

4

5

-

6

1

2

3

Monitoring

Instrument

RTD

S

+

-

M2160B

IRMA

3

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Содержание IRMA

Страница 1: ...NPUT OUTPUT POWER HIGH DENSITY PACKAGING 22 5 mm wide WIDE OPERATING TEMPERATURE RANGE DESCRIPTION The IRMA accepts a 2 3 or 4 wire RTD or resistance input and converts it into a 4 to 20 mA current output The 4 to 20 mA output is linearly proportional to the temperature or the resistance input This output is ideal for interfacing to indicators chart recorders controllers or other instrumentation e...

Страница 2: ... use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or equivalent are recommended Ferrite Suppression Cores for signal and control cables Fair Rite 0443167251 RLC FCOR0000 TDK ZCAT3035 1330A Steward 28B2...

Страница 3: ...has the power and current output sharing the same two wires loop powered Connect DC power to terminals 4 and 5 observing the correct polarity with a current meter indicator connected in between so that the output current can be monitored Be certain that the DC power is relatively clean and within the 12 to 42 VDC range at the terminals The current meter voltage drop must be included in the power s...

Страница 4: ...ndicator Adjustable 3 1 2 Resistance Source RTD S MC2160X IRMA TEST OUTPUT CAL FIELD CAL BASIC CAL 385 392 OPEN SEN DN UP RTD OHMS RANGE RANGE DIP SWITCH SETTINGS ON 1 OFF 0 M2161A 1 2 4 5 6 7 8 ON Test Pad RED LION CONTROLS MADE IN U S A MODEL IRMA YORK PA Field Calibration Wiring Allow a 30 minute warm up period before starting Field Calibration Field Calibration scales the 4 to 20 mA output to ...

Страница 5: ...nput terminals using a third sense wire Set the RANGE 7 8 TYPE 4 OUTPUT CAL 1 and FIELD CAL 2 switches OFF Set the BASIC CAL switch 3 ON 2 2 Apply power and allow a 30 minute warm up period Current goes to 3 5 mA nominal 2 3 Set the OUTPUT CAL switch 1 ON and then OFF 2 4 Set the resistance source to 40 ohms and wait 5 seconds 2 5 Set the OUTPUT CAL switch 1 ON and then OFF 2 6 Set the resistance ...

Страница 6: ...il Push the module toward the rail until it snaps into place To remove a module from the rail push up on the bottom of the module while pulling out away from the rail T Rail Installation To install the IRMA on a T style rail angle the module so that the top groove of the foot is located over the lip of the top rail Push the module toward the rail until it snaps into place To remove a module from t...

Страница 7: ...7 This Page Intentionally Left Blank AUDIN 8 avenue de la malle 51370 Saint Brice Courcelles Tel 03 26 04 20 21 Fax 03 26 04 28 20 Web http www audin fr Email info audin fr ...

Страница 8: ...able including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those expressly contained herein The Customer acknowledges the disclaimers a...

Отзывы: