INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not
exceed the maximum operating temperature and provides
good air circulation. Placing the unit near devices that
generate excessive heat should be avoided. The bezel should
be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils,
etc.) to operate the keypad of the unit.
Installation
The CUB4 Volt and Current meters meet
NEMA 4X/IP65 requirements for indoor use, when properly
installed. The units are intended to be mounted into an enclosed panel. A
sponge rubber gasket, mounting clip, two screws, and nut fasteners are
provided to install and seal the unit in the panel cutout.
The following procedure assures proper installation:
1.Cut panel opening to specified dimensions. Remove burrs and clean panel
opening.
2. Carefully remove center section of the panel gasket and discard. Slide
gasket over rear of the unit to the back of the bezel.
3. Slide nut fastener into slot on mounting clip and then insert mounting screw
through nut on both sides of mounting clip. Tip of mounting screw should
NOT
project through hole on clip.
4. Install CUB4 unit through panel cutout.
5. Slide mounting clip over rear of unit until clip is against back of panel. The
mounting clip and CUB4 housing have a latching feature to hold the unit in
place until tightened.
Note: Hold the CUB4 front bezel in place when sliding the mounting clip into
position.
6. Alternately tighten each mounting screw to ensure uniform gasket pressure.
Visually inspect the gasket for proper seal. The gasket should be
compressed approximately 75 to 80% of its original thickness.
(Recommended torque is 28 to 36 in-oz.)
7. If the gasket is not adequately compressed and the mounting screws cannot
be tightened any further, loosen mounting screws and insure that the clip is
latched as close as possible to the panel.
8. Repeat step #6 for tightening the mounting screws.
10.
INPUT IMPEDANCE:
Voltmeter
: 1 M
Ω
Current Meter
:
199.9 µA - 1 K
Ω
1.999 mA - 100
Ω
19.99 mA - 10
Ω
199.9 mA - 1
Ω
11.
CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File # E179259, UL3101-1, CSA C22.2 No. 1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate # UL2356A-179259/USA,
CB Scheme Test Report # 98ME60090-000098
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m.
Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth
ground.
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms.
Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Install power line filter RLC#LFIL0000 or equivalent at the unit.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
12.
ENVIRONMENTAL CONDITIONS:
Operating Temperature
: 0° to 60°C
(above 50
°
C, derate backlight
operating voltage to 26 VDC maximum)
.
Storage Temperature
: -40° to 80°C
Operating and Storage Humidity
: 85% max relative humidity (non-
condensing) from 0 to 60°C.
Vibration According to IEC 68-2-6:
5 to 500 Hz, in X, Y, Z direction for
1.5 hours, 5g’s.
Shock According to IEC 68-2-27:
Operational 30 g, 11 msec in 3 directions.
Temperature Coefficient
: 100 PPM/°C
Altitude
: Up to 2000 meters.
13.
CONSTRUCTION:
High impact plastic case with clear viewing window.
(Panel gasket and mounting clip included.) This unit is rated for NEMA
4X/IP65 indoor use. Installation Category II, Pollution Degree 2
14.
WEIGHT:
3.3 oz. (93.5 g)
Power mains class A
Enclosure class A
EN 55011
RF interference
Emissions to EN 50081-2
Level 4; 30 A/m
150 KHz - 80 MHz
EN 61000-4-8
Level 3; 10 V/rms
2
EN 61000-4-6
RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/O
EN 61000-4-4
Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
1
EN 61000-4-3
Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contact
EN 61000-4-2
Electrostatic discharge
200 Hz, 50% duty cycle
900 MHz
±
5 MHz
Immunity to EN 50082-2
Level 3; 10 V/m
ENV 50204
Simulation of cordless telephone
Power frequency magnetic fields