GENERAL SPECIFICATIONS (CONT’D)

6. 

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

UL Listed, File # E302106, UL508, CSA C22.2 No. 14-M05

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment 

for measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: 2006: Electrical Equipment for 
Measurement, Control and Laboratory use.

Notes:

1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-

recovers.

3. The module’s analog input and/or output signals may deviate during 

disturbance, but self-recover when disturbance is removed.

4. Power supplied from backplane via Master Module.

7. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: 0 to +50 °C
Storage Temperature Range: -40 to +85 °C
Operating and Storage Humidity: 85% max relative humidity, non-

condensing, from 0 to +50 °C

Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm 

amplitude in X, Y, Z direction 1 g.

Shock According to IEC 68-2-27: Operational 25 g's, 11 msec in 3 directions.
Altitude: Up to 2000 meters

8. 

CONSTRUCTION

: Case body is burgundy high impact plastic. For indoor 

use only. Installation Category II, Pollution Degree 2.

9. 

CONNECTIONS

: Removable wire clamp screw terminal blocks

Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)

10. 

MOUNTING

: Snaps on to standard DIN style top hat (T) profile mounting 

rails according to EN50022 -35 x 7.5 and -35 x 15.

11. 

WEIGHT

: 6 oz (170.1 g)

Class A

EN 55011

Emissions

Immunity to Industrial Locations:

3 V/rms

Criterion A

EN 61000-4-6

RF conducted interference

1 kV

signal

1 kV L-L, 2 kV L-G

power

Criterion B

EN 61000-4-5

Surge 

1 kV

signal

2 kV

power

Criterion B

EN 61000-4-4

Fast transients (burst)

Emissions:

10 V/m

Criterion B

3

EN 61000-4-3

Electromagnetic RF fields

8 kV air discharge

4 kV contact discharge

Criterion B

EN 61000-4-2

Electrostatic discharge

CSTC8 SPECIFICATIONS

12. 

INPUTS

:

Channels: 8 single-ended
Effective Resolution: Full 16-bit
Sample Time: 50 msec - 400 msec, depending on number of enabled inputs.

ENABLED 

INPUTS

SCAN TIME 

(READING RATE)

1

50 msec (20 Hz)

2

100 msec (10 Hz)

3

150 msec (6.7 Hz)

4

200 msec (5 Hz)

5

250 msec (4 Hz)

6

300 msec (3.3 Hz)

7

350 msec (2.9 Hz)

8

400 msec (2.5 Hz)

Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >90 dB, 50/60 Hz
Temperature Coefficient: 0.01%/°C
Step Response Time: One scan time (to within 99% of final value)
Types: T, E, J, K, R, S, B, N, C
Slope & Offset: Provides sensor error correction
Input Impedance: 20 M 

Lead Resistance Effect: 0.25 

μ

V/

Cold Junction Compensation: Less than ±1 °C typical (±1.5 °C max) over 0 

to 50 °C ambient temperature

Resolution: 0.1°

13. 

TEMPERATURE INDICATION ACCURACY

: ± (0.3% of span, +1 °C). 

Includes NIST conformity, cold junction effect, A/D conversion errors, 
temperature coefficient and linearization conformity at 23 °C after 20 minute 
warm up.

14. 

PROBE BREAK RESPONSE

: Upscale drive, Input Fault Alarm bit set high, 

ALM LED illuminates.

No Standard

No Standard

No Standard

No Standard

-10.00 to +56.00 mV

0 to +2315 °C

+32 to +4199 °F

Millivolt

C

W5/W6

(+) Orange

(-) Blue

(+) Orange

(-) Red

-200 to +1300 °C

-328 to +2372 °F

N

No Standard

No Standard

+149 to +1820 °C

+300 to +3308 °F

B

(+) White

(-) Blue

No Standard

0 to +1768 °C

+32 to +3214 °F

S

(+) White

(-) Blue

No Standard

0 to +1768 °C

+32 to +3214 °F

R

(+) Brown

(-) Blue

(+) Yellow

(-) Red

-200 to +1250 °C

-328 to +2282 °F

K

(+) Yellow

(-) Blue

(+) White

(-) Red

-200 to +760 °C

-328 to +1400 °F

J

(+) Brown

(-) Blue

(+) Violet

(-) Red

-200 to +730 °C

-328 to +1346 °F

E

(+) White

(-) Blue

(+) Blue

(-) Red

-200 to +400 °C

-328 to +752 °F

T

BS 1843

ANSI

WIRE COLOR

MEASUREMENT 

RANGE

TYPE

CSRTD6 SPECIFICATIONS

15. 

RTD INPUTS

:

Channels: 6 single-ended
Effective Resolution: Full 16-bit
Sample Time: 67 msec - 400 msec, depending on enabled inputs.

ENABLED 

INPUTS

SCAN TIME 

(READING RATE)

1

67 msec (14.9 Hz)

2

133 msec (7.5 Hz)

3

200 msec (5 Hz)

4

267 msec (3.8 Hz)

5

333 msec (3 Hz)

6

400 msec (2.5 Hz)

Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >90 dB, 50/60 Hz
Temperature Coefficient: 0.01%/°C
Step Response Time: One scan time (to within 99% of final value)
Type: 2 or 3 wire
Excitation: 150 

μ

A

Lead Resistance: 15 

 Max

Resolution: 0.1°
Slope & Offset: Provides sensor error correction

16. 

TEMPERATURE INDICATION ACCURACY

: Includes NIST conformity, 

A/D conversion errors, temperature coefficient and linearization conformity at 
23 °C after 20 minute warm up.

17. 

PROBE BREAK RESPONSE

: If channel is enabled: upscale drive, Input 

Fault Alarm bit set high, ALM LED illuminates.

TYPE

INPUT TYPE

RANGE

385

± (0.2% of span)

± (0.1% of span)

-200 to +600 °C

-328 to +1100 °F

392

± (0.2% of span)

± (0.1% of span)

-200 to +600 °C

-328 to +1100 °F

672

Ohms Linear resistance

± (0.2% of span)

± (0.1% of span)

-80 to +215 °C

-112 to +419 °F

± (0.2% of span)

± (0.1% of span)

 to 300 

428

50 

 copper,

Alpha = .00428

± (1.2% of span)

± (0.6% of span)

-50 to +200 °C

-58 to +392 °F

2

120 

 nickel,

Alpha = .00672

100 

 platinum,

Alpha = .003919

100 

 platinum,

Alpha = .00385

ACCURACY

0 TO 50°C

ACCURACY

18 TO 28°C

Содержание CSTC

Страница 1: ...p hat T profile DIN rail CONFIGURATION The Modular Controller Series is configured with Windows compatible Crimson software The software is an easy to use graphical interface which provides a means of configuration and commissioning of new systems as well as routine module re calibration SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equi...

Страница 2: ...0 60 Hz Normal Mode Rejection 90 dB 50 60 Hz Temperature Coefficient 0 01 C Step Response Time One scan time to within 99 of final value Types T E J K R S B N C Slope Offset Provides sensor error correction Input Impedance 20 M Lead Resistance Effect 0 25 μV Cold Junction Compensation Less than 1 C typical 1 5 C max over 0 to 50 C ambient temperature Resolution 0 1 13 TEMPERATURE INDICATION ACCURA...

Страница 3: ...M Max Continuous Overload 50 V 22 ACCURACY 0 1 of span 23 INPUT FAULT RESPONSE Upscale Drive Input Fault Alarm bit set high ALM LED illuminates below 10 4 VDC and above 10 4 VDC CSINI8 SPECIFICATIONS 18 INPUTS Channels 8 single ended Ranges 0 20 mA or 4 20 mA Effective Resolution Full 16 bit Programmable Scaling 30 000 Linearizer 100 Points CSINI8L0 only Sample Time 50 msec 400 msec depending on n...

Страница 4: ...should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy c...

Страница 5: ...ult condition When one or more Input Fault Alarm bits is high the LED turns on The alarms may be disabled for unused inputs CONFIGURATION Programming is done via Crimson software a Windows compatible configuration interface Please see the Crimson manual for more information Rapidly Flashing Red Module is currently running the boot loader and or being flash upgraded by Crimson This occurs for four ...

Страница 6: ... Point Linearizer 6 Channel RTD Module CSINV8L0 CSRTD600 8 Channel 10 V Input Module 8 Channel 0 4 20 mA Input Module 100 Point Linearizer 8 Channel 0 4 20 mA Input Module 8 Channel Thermocouple Module CSINV800 CSINI8L0 CSINI800 CSTC8000 CSINI CSTC1 CSINV CSRTD Input Modules Modular Controller Master Multi Comms ports and Ethernet CSMSTR Master Module CSMSTRGT CSMSTRSX CSMSTRV2 DESCRIPTION MODEL N...

Страница 7: ...7 This page intentionally left blank ...

Страница 8: ...uyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those ex...