MODULAR CONTROLLER SERIES 

  MODELS AVAILABLE TO ACCEPT ±10 V, 0/4-20 mA, 

THERMOCOUPLE AND RTD INPUTS

  ±10 V AND 0/4-20 mA INPUT VERSIONS FULLY SCALABLE

  ±10 V AND 0/4-20 mA INPUT VERSIONS AVAILABLE WITH 100 

POINT LINEARIZATION

  UNUSED INPUTS CAN BE DISABLED TO INCREASE OVERALL 

READING RATE

  IDEAL FOR DATA-ACQUISITION APPLICATIONS

  AUTO ADDRESSING MINIMIZES CONFIGURATION TIME

  CAN BE USED IN CONJUNCTION WITH ANY CS 

SERIES MODULES

GENERAL DESCRIPTION

The Model CSTC, CSRTD, CSINI, and CSINV are 16-bit analog input 

modules designed for use with the Modular Controller Series. These modules 
provide a means of high-density signal measurement for data-acquisition 
applications. The CSTC module accepts a wide range of thermocouple types, 
while the CSRTD accepts various RTD inputs. The CSINI and CSINV accept 
0/4-20 mA and ±10 V process signals, respectively. 

The modules connect and communicate via a backplane connection to the 

CSMSTR Modular Controller Series Master. The CSMSTR, equipped with serial 
ports as well as an Ethernet port, allows the system to share data with PCs, PLCs, 
and SCADA systems. The Master supports any combination of up to 16 CS series 
modules, allowing a total of 128 signals to be monitored via a single Master.

Internal power management circuits allow the modules to be replaced while 

power is applied, which reduces downtime. All configuration information is 
stored locally within the module, as well as in the Master, so replacement 
modules do not need to be configured.

The Modular Controller Series’ high density packaging and DIN rail 

mounting saves time and panel space. The backplane connection provides power 
and communication to the module and snaps easily onto standard top hat (T) 
profile DIN rail.

CONFIGURATION

The Modular Controller Series is configured with Windows

®

 compatible 

Crimson

®

 software. The software is an easy to use, graphical interface which 

provides a means of configuration and commissioning of new systems, as well 
as routine module re-calibration.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 
prevent damage to either the instrument or equipment connected to it. If 
equipment is used in a manner not specified by the manufacturer, the protection 
provided by the equipment may be impaired.

Do not use the module to directly command motors, valves, or other actuators 

not equipped with safeguards. To do so can be potentially harmful to persons or 
equipment in the event of a fault to the module. An independent and redundant 
temperature limit indicator with alarm outputs is strongly recommended.

GENERAL SPECIFICATIONS

1. 

POWER

: Derived from system backplane. (75 mA load on power input of 

MASTER). Module may be hot-swapped (replaced while powered up).

2. 

LEDs

:

STS

 - Status LED shows module condition.

ALM

 - Alarm LED is lit during any internal alarm condition.

3. 

MEMORY

: Non-volatile memory retains all programmable parameters. 

MASTER also stores the parameters in order to reprogram modules that are 
replaced.

4. 

ISOLATION LEVEL

: 500 Vrms @ 50/60 Hz for 1 minute between the 

Signal Inputs and the CS Master Power Supply Input.

5. 

COMMUNICATIONS

: Provided by the CS Master

MODELS CSTC, CSRTD, CSINI, CSINV - 
MODULAR CONTROLLER SERIES ANALOG INPUT MODULES

Bulletin No.  CS8- H
Drawing No.  LP0556
Released  01/10

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

1

7

13

1.24

(126.5)

4.17 (105.9)

4.98

(31.5)

DIMENSIONS  In inches (mm)

CC

US LISTED

US LISTED

UL

R

IND. CONT. EQ.

34AD

Содержание CSTC

Страница 1: ...p hat T profile DIN rail CONFIGURATION The Modular Controller Series is configured with Windows compatible Crimson software The software is an easy to use graphical interface which provides a means of configuration and commissioning of new systems as well as routine module re calibration SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equi...

Страница 2: ...0 60 Hz Normal Mode Rejection 90 dB 50 60 Hz Temperature Coefficient 0 01 C Step Response Time One scan time to within 99 of final value Types T E J K R S B N C Slope Offset Provides sensor error correction Input Impedance 20 M Lead Resistance Effect 0 25 μV Cold Junction Compensation Less than 1 C typical 1 5 C max over 0 to 50 C ambient temperature Resolution 0 1 13 TEMPERATURE INDICATION ACCURA...

Страница 3: ...M Max Continuous Overload 50 V 22 ACCURACY 0 1 of span 23 INPUT FAULT RESPONSE Upscale Drive Input Fault Alarm bit set high ALM LED illuminates below 10 4 VDC and above 10 4 VDC CSINI8 SPECIFICATIONS 18 INPUTS Channels 8 single ended Ranges 0 20 mA or 4 20 mA Effective Resolution Full 16 bit Programmable Scaling 30 000 Linearizer 100 Points CSINI8L0 only Sample Time 50 msec 400 msec depending on n...

Страница 4: ...should be run through metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy c...

Страница 5: ...ult condition When one or more Input Fault Alarm bits is high the LED turns on The alarms may be disabled for unused inputs CONFIGURATION Programming is done via Crimson software a Windows compatible configuration interface Please see the Crimson manual for more information Rapidly Flashing Red Module is currently running the boot loader and or being flash upgraded by Crimson This occurs for four ...

Страница 6: ... Point Linearizer 6 Channel RTD Module CSINV8L0 CSRTD600 8 Channel 10 V Input Module 8 Channel 0 4 20 mA Input Module 100 Point Linearizer 8 Channel 0 4 20 mA Input Module 8 Channel Thermocouple Module CSINV800 CSINI8L0 CSINI800 CSTC8000 CSINI CSTC1 CSINV CSRTD Input Modules Modular Controller Master Multi Comms ports and Ethernet CSMSTR Master Module CSMSTRGT CSMSTRSX CSMSTRV2 DESCRIPTION MODEL N...

Страница 7: ...7 This page intentionally left blank ...

Страница 8: ...uyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those ex...

Отзывы: