Power cords and terminal strips
The main factors that affect the selection of wires are the supply voltage, current, room
temperature and cable installation conditions.
The power supply cables of the system must be selected in accordance with the applicable
regulations at the site and comply with the following description:
The input power cords of the power supply must match the maximum input current and
maximum charging current shown in the table below, including the power rating of the
power supply and the AC input voltage.
Output and bypass cables must be matched to the rated output currents given in the
table, including the power rating of the power supply and the AC output voltage.
Battery cables must be matched to the discharge current of the battery at the voltage at
the end of discharge indicated in the table, taking into account the power rating of the
power supply.
The terminal block is equipped with screw connections. Select the appropriate cable
clamp and use the appropriate tightening torque given in the table below.
Table 2-1 Table of power supply currents for 400Vac and 40 batteries
Power UPS
Rectifier
Bypass/
Output
Battery
Type of
conenction
Tightening
torque
HS 105/100kVA
152A
145A
208A
M6, M8
4,9Nm, 13 Nm
HS 205/150kVA
227A
216A
313A
M10
15Nm
HS 205/200kVA
303A
289A
417A
M10
15Nm
HS 305/250kVA
380A
362A
521A
M12
28Nm
HS 305/300kVA
455A
433A
626A
M12
28Nm
HS 505/350kVA
533A
507A
729A
M16
96Nm
HS 505/400kVA
607A
578A
833A
M16
96Nm
HS 505/450kVA
685A
652A
938A
M16
96Nm
HS 505/500kVA
759A
723A
1042A
M16
96Nm
Warning
The power supply needs to be connected to the PE protective conductor. Incorrect
connection of the protective conductor may cause malfunction of EMI filters and result in
electric shock or fire.
The terminal strip for connecting power / receiving cables is located on the front for the
HS 205 housing and on the back of the power supply unit for HS 305 and HS 505.