BOX STACKING CONTROL

A typical application requires the control of a conveyor belt which feeds a

mechanical stacker. The stacker can stack 12, 24, 32, or 48 cartons of ceiling
tile onto each pallet 

(depending on pallet size)

. When the required number of

cartons  have  been  stacked,  the  conveyor  is  stopped  until  the  loaded  pallet  is
removed and an empty pallet is placed onto the loading area. Also, it is required
that only the foreman be allowed to change the number of cartons per pallet.

A single preset Libra counter is used to satisfy all the above requirements.

Terminal 3 and terminal 4 of a Model RR Photo-electric sensor 

(which feeds a

count pulse to the Libra after each carton passes by)

are respectively connected

to the 

“+12 VDC”

and 

“CNT. IN”

terminals of the Libra counter. The normally

closed  contact  of  relay  1  is  connected  to  the  conveyor  belt  drive  control.  A
remote  reset  button  is  connected  to  the 

“REM.  RST.”

terminal  of  the  Libra

counter, which allows the operator to reset the system from the forklift, after an
empty pallet is placed onto the loading area. Also, a key switch is connected to
the 

“PGM. DIS.”

terminal, which allows only the foreman to change the preset

value. The DIP switches are set as follows: DIP switch 1 is set to 

“SRC.”

so the

count will increment after the box has passed by the sensor 

(count on dark to

light transition)

. DIP switch 2 is set to 

“LO. FRQ.”

and DIP switch 3 is set to

“HI  BIAS”

,  both  of  which  provide  extra  noise  immunity  on  the  input.  DIP

switch 4 is set to 

“DIS. RST.”

position, which prevents resetting the unit from

the front panel. The unit is set for Mode 0 operation, switches 5 through 8 are
in the 

“UP”

position 

(Latch Output at Preset, Manual Reset to Zero)

.

The system operation is as follows: as the trailing edge of the box passes the

photo-electric, a count is registered on the Libra display. When the preset value
is  reached,  the  conveyor  belt  will  turn  off.  The  forklift  operator  removes  the
loaded pallet. After the empty pallet is in position, the forklift operator presses
the remote reset switch, which then starts the whole cycle over again.

APPLICATION FOR SINGLE PRESET LIBRA COUNTER

APPLICATION FOR DUAL LEVEL PRESET LIBRA COUNTER

THE CONTROL OF A PAPER ROLL 
MANUFACTURING PROCESS

In a paper production process, the requirement exists to control a solenoid which places

a red ink marking at the end of a roll of printing paper 

(this marking is used to indicate

when  the  end  of  the  roll  is  near)

.  The  unit  must  also  stop  the  system  when  the  proper

amount of paper is wound onto the roll. Then, the cutting knife is manually  actuated which
shears off the paper. The full roll is taken off the spool and a new roll is loaded on. The
system is then started up again. The Libra two preset counter satisfies these requirements.

The Libra set-up is as follows: Preset 1 is set to 30 

(30 ft. {9 M} is desired length of

red marking at the end of the roll)

. When the system is started, the ink marker solenoid

is  activated  which  starts  marking  the  paper 

(this  is  connected  to  the  normally  closed

contact  of  relay  1)

.  When  30  is  reached,  output  1  fires  which  de-energizes  the  ink

solenoid. Preset 2 is set to 3400 feet. 

(3400 ft. {1036 M} is the total desired length of

paper wound onto the roll)

. When the unit reaches 3400 feet, preset 2 fires which de-

energizes  the  entire  system 

(the  system  control  is  connected  to  the  normally  closed

contact of output 2)

. The operator then activates the knife, which shears off the paper

and at the same time, the Libra counter is reset and is ready for the next cycle.

An LSC 

(length sensor)

with a 1 pulse/foot wheel is connected to the Libra counter.

The red 

(+12 V)

, black 

(COMM.) 

and white 

(COUNT)

of the LSC are connected to the

Libra 

“+12  VDC”

“COMM.”

,  and 

“CNT.  IN”

terminals  respectively.  The 

“PGM.

DIS.”

terminal is left unconnected so preset values can be changed 

(a key switch can be

used if desired)

“RESET”

is connected to the knife actuator so when the knife shears

off the paper, the Libra counter is reset. DIP switch 1 is set to current sinking to match
the LSC output. DIP switch 2 is set to 

“LO FRQ.”

because the count speed cannot be

greater  than  100  Hz.  DIP  switch  3  is  set  to 

“HI  BIAS”

.  The  front  panel  reset  enable

switch 

(DIP switch 4)

is set to 

“DIS.”

. All the mode switches are set 

“UP”

, which is

mode  0 

(Latch  Outputs  at  Presets  and  Manual  Reset  to  Zero)

.  The  relay  contacts  are

connected as previously discussed.

ORDERING INFORMATION

LIBC2E00

LIBC2E10

Dual Preset LED Libra Counter

LIBC2E

For more information on Pricing, Enclosures & Panel Mount Kits refer to the RLC Catalog or contact your local RLC distributor.

LIBC1E00

LIBC1E10

Single Preset LED Libra Counter

LIBC1E

LIBC2000

LIBC2010

Dual Preset LCD Libra Counter

LIBC2

LIBC1000

LIBC1010

Single Preset LCD Libra Counter

LIBC1

115 VAC

230 VAC

DESCRIPTION

MODEL NO.

PART NUMBERS FOR

AVAILABLE SUPPLY VOLTAGES

LIBC-j.QXD  10/26/04 10:52 AM  Page B8

Содержание LIBC Series

Страница 1: ...unit s timed output is set at the factory to be 0 1 sec The Libra counters have an internal non volatile memory device which eliminates the need for battery back up When input power is removed this de...

Страница 2: ...contacts max rating 5 amps 120 240 VAC 28 VDC resistive load 1 8 H P 120 VAC inductive load The operate time is 5 msec nominal and the release time is 3 msec nominal Relay Life Expectancy 100 000 cyc...

Страница 3: ...t will automatically Reset to Preset and start the cycle over During automatic reset no counts will be lost as long as the count rate does not exceed 2 500 cps Manual reset will turn off the output if...

Страница 4: ...OUTPUT 1 TURN OFF AT ZERO TIMED OUTPUT 2 AT ZERO MANUAL RESET TO PRESET In this mode as the unit counts from preset 2 output 1 will turn on when preset 1 is reached When zero is reached output 2 will...

Страница 5: ...t that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radi...

Страница 6: ...ressing and holding the button will continuously scroll the digit from 0 through 9 then back to 0 again When the desired value for that digit is reached release the button Do this for all the digits t...

Страница 7: ...nters meet NEMA 4 IP65 requirements for indoor use when properly installed The units are intended to be mounted into an enclosed panel with a gasket to provide a water tight seal Two mounting clips an...

Страница 8: ...requirement exists to control a solenoid which places a red ink marking at the end of a roll of printing paper this marking is used to indicate when the end of the roll is near The unit must also sto...

Отзывы: