PROGRAMMABLE FUNCTIONS (Cont’d)

UPDATE TIME

The Rate Minimum and Maximum Update Times range from 0.1 to 99.9 

seconds. This provides averaging capability for non-consistent pulse spacing.

Note: The maximum update time must be larger than the minimum update time.

COUNTING MODES

Count with Direction
Count with Direction (X2)
Quadrature
Quadrature (X2)
Quadrature (X4)
2-Input Anti-coincidence Add/Subtract
2-Input Anti-coincidence Add/Add
A separate Inhibit input is available for all count modes.

RESET MODES

Manual Reset
Automatic Reset at Preset
Reset at Beginning Of Output 1
Reset at End Of Timed Output 1
Reset at Beginning Of Output 2
Reset at End Of Timed Output 2
Reset at Beginning Of Output 1 or Output 2
Reset at End Of Timed Output 1 or Output 2

MODEL LGPB ONLY

Reset at Beginning Of Output 3
Reset at End Of Timed Output 3
Reset at Beginning Of Output 4
Reset at End Of Timed Output 4
Reset at Beginning Of Output 3 or Output 4
Reset at End Of Timed Output 3 or Output 4

RESET ACTION

Reset to Zero:

 Count display value returns to zero when reset. Output activates, 

if programmed, when the count equals the preset value.

Reset to Preset:

 Count display value returns to preset value when reset. Output 

assigned to the specified preset activates, if programmed, when the count 
equals zero.

Reset to Counter Load:

 Count display value returns to counter load value when 

reset. Output activates, if programmed, when count equals the preset value.

USER INPUTS

There are four external user inputs and two front panel Function keys that are 

programmable. When activated, each user input can be programmed to perform 
one of the following functions:

Maintained Reset or Momentary Reset:

 

Can reset Rate, Peak, Valley, Process*, Batch*, Total*, or Count* display 
values and/or any output associated with that display.

*

 On Models with these available display options.

Reset Output(s):

Places the output(s) in their inactive state. 

(Momentary action)

Set Output(s):

Places the output(s) in their active state. 

(Momentary action)

View Display 1-4:

Causes the selected indication display 

(1, 2, 3, or 4)

 to be displayed and held 

from anywhere in the main display loop. The current display value is frozen 

(not updated)

 while the display is held.

Change Display:

Causes the indication display to toggle to the next indication display.

Request Message:

Requests a specific programmed message to activate.

Clear Message:

Causes the displayed message to be canceled. 

(Maintained action)

Skip Preset:

Keeps the output from activating and automatic reset from occurring, if 
programmed, when the count value equals the preset value.

Counter Load:

Places the counter load value into the count display and operates from that 
value. 

(Maintained action)

Print Request:

Transmits the values specified in the Program Print Options module over the 
serial port. 

(Maintained action)

Program Disable:

Can be used alone, or in conjunction with the program disable DIP switch, to 
provide a variety of program security modes. 

(External User Input only)

Inhibit Count:

Prevents pulses from being counted on Inputs A and B. 

(User Input 4 only)

The rate input is not affected by the inhibit setting and continues to display the 
rate of the signal at Input A.

OUTPUT(S)

Output Assignment:

The LGPB can have outputs 1 through 4 assigned to the process or the rate. 

Outputs 3 and 4 can also be assigned to the batch or total.

The LGPM can have outputs 1 through 6 assigned to either count or rate.

Phase:

Each output can have its active logic state set for positive phase (normally 
off) or negative phase (normally on).

Output Activation Mode:

Latched
Boundary
Timed - 0.01 to 99.99 seconds

Hi/Lo Acting:

This mode is used in conjunction with all Rate modes and the Boundary 
count modes. A Lo acting output would perform the Output action when the 
count/rate is lower than the preset. A Hi acting output would perform the 
Output action when the count/rate is higher than or equal to the preset.

Rate Output On/Off Delay:

Used to prevent output chatter. Output condition must be satisfied for a 
period of time longer than delay period for output state to change.

On Delay:

 Prevents activation of output(s) for the amount of time 

programmed.

Off Delay:

 Prevents deactivation of output(s) for the amount of time 

programmed.

On & Off Delay:

 This mode prevents output state change for specified delay 

period when turning on or off.

Output Reset Mode:

Outputs 1 & 2 Only:

End Output 1 @ Output 2 Start
End Output 1 @ Timed Output 2 End
End Output 2 @ Output 1 Start
End Output 2 @ Timed Output 1 End

Output(s) Power Up or Power Down State:

The Output’s state can be set to be Off (Inactive) @ power up.

OR

The Output’s state can be saved @ power down and restored at power-up.

OR

The Output’s state can be set to be ON (Active) @ power up.

Note: Power down state for Latched Mode Only

.

Reset Output when Count is Reset:

This feature can be enabled or disabled.

Request Message:

Each output can be programmed to request a specific message when the 
output conditions are satisfied.

INDICATION DISPLAYS

Each of the four indication displays is programmed individually. Each line of 

each indication display can be programmed to show a value mnemonic, a 
numeric value, the output status, a preset value, the counter load value, or a 
custom display line. The mnemonics are factory set to; RATE, PEAK, VALLEY, 
COUNT*, PROCESS*, BATCH*, TOTAL*, and OVERFLOW. Each mnemonic 
can be individually changed to a mnemonic tailored to a specific application. 
The first character of the full mnemonic is displayed to the left of the appropriate 
numeric value if the other line is not programmed to display the full mnemonic. 
Each of the 4 indication displays can be programmed to be green or red on dual 
color models.

On Models with these available display options.

Scroll Speed:

None
2.5 Seconds
5.0 Seconds

Display Intensity:

The brightness of the display can be adjusted from 1 to 5, with 5 as the 
brightest. There is a separate adjustment for each color.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание Legend Plus Series

Страница 1: ...or suffix This capability allows displays such as 1000 RPM 99999 Ft PRC 9999 etc The Legend Plus also features messaging capabilities that can inform the user of output actions or other events that o...

Страница 2: ...ch can control NPN open collector outputs 01 SNK to 06 SNK respectively Presets 1 through 6 can be assigned to either the rate or count display SPECIFICATIONS 1 DISPLAY 2x8 0 3 7 mm high characters ne...

Страница 3: ...us unit Also shown above right are four different views of the indication displays PROGRAMMABLE FUNCTIONS PRESET S Ranges from 99999 to 999999 Counter Load ranges from 99999 to 999999 SCALE FACTORS RA...

Страница 4: ...disable DIP switch to provide a variety of program security modes External User Input only Inhibit Count Prevents pulses from being counted on Inputs A and B User Input 4 only The rate input is not af...

Страница 5: ...c For total only the first character is transmitted A transmit and reset count capability allows the selected count values to automatically reset after the value is printed transmitted OPERATOR ACCESS...

Страница 6: ...CK LABEL GLUE PRIORITY 6 TYPE 1L SCROL BLINKING MULTIPLEX CANCEL TIMED TIME SEC 1 COLOR GREEN MSG 6 6 TEXT CHECK TOP SUPPLY PRIORITY 6 TYPE 1L SCROL BLINKING MULTIPLEX CANCEL TIMED TIME SEC 1 COLOR GR...

Страница 7: ...expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters wh...

Отзывы: