background image

1

DESCRIPTION

The ICM5 Serial Converter Module provides the capability of interfacing 

equipment with RS-485 serial communications to equipment with RS-232 

communications while providing three way isolation. Data format of the 

RS-232 and RS-485 equipment must be the same.

The unit can be configured for full duplex (RS-422), or half duplex (RS-485) 

operation. In half duplex mode, the RS-485 driver is automatically enabled 

using the leading edge of the first character that is received on the RS-232 side. 

After the last character is received, the converter waits one character time (at the 

selected baud rate) to disable the RS-485 driver.

An external DC power source (+9 to 26 VDC) is required to power the ICM5. 

The external power source and RS-485 communications connections are made 

via a 7-position removable terminal block located on the front of the module. A 

modular RS-485 connector is also provided for fast and efficient connection to 

other Red Lion devices that use a modular connector. The RS-232 connection is 

provided via a standard D-SUB 9-pin male connector. The ICM5 can be 

configured for DTE or DCE operation, allowing the use of modem or null-

modem cables.

There are 3 LEDs that can be viewed from the front of the converter module. 

A green power LED indicates power is on, a red RS-232 TXD LED flashes 

when the module is transmitting, and a green RS-232 RXD LED flashes when 

the module is receiving.

The unit is equipped with a universal mounting foot for attachment to 

standard DIN style mounting rails, including top hat profile rail according to EN 

50 022 - 35x7.5 and 35x15, and G profile rail according to EN 50 035 - G32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

SPECIFICATIONS

1. 

POWER

: +9 to 26 VDC @ 125 mA maximum. 85 mA typical

Power Supply must be Class 2 or SELV rated.

2. 

RS-232 VOLTAGES

Receive Data Pin

± 

30 VDC max.

Mark Condition

≤ 

0.8 VDC

Space Condition

≥ 

2.4 VDC

Transmit Data Pin

:

Mark Condition

: -8 VDC (typ.)

Space Condition

+

8 VDC (typ.)

3. 

RS-485 VOLTAGES

Differential Output Voltage

± 

5

 

VDC max. under no load

Differential Input Voltage

± 

5

 

VDC max.

Mark Condition

≤ 

-0.2 VDC

Space Condition

≥ +

0.2 VDC

RS-485 Drive Capability

: Up to 32 RS-485 receivers connected in parallel

RS-485 Drive Disable Time

: one character time (at the set baud rate)

4. 

MAXIMUM CABLE LENGTH

RS-232

: 50 feet (15.24 m)

RS-485

: 4000 feet (1219.2 m)

5. 

BAUD RATE

: 9600 min., 115200 max.

6. 

ISOLATION

: 1000 VDC

7. 

ENVIRONMENTAL CONDITIONS

Operating Temperature Range

: 0 to 50

°

C.

Storage Temperature

: -40 to + 75

°

Operating and Storage Humidity

: 85% max. relative humidity  

(non-condensing) from 0 to 50

°

C

MODEL ICM5 – THREE WAY ISOLATED SERIAL CONVERTER MODULE  

 (RS-232C/RS-485)

(85.1)

3.35

(89)

3.5

.39

(10)

(25)

.98

COMM

COMM

PWR

TXD

RS485

M2869

X

MADE IN U.S.A

.

RED LION CONTROLS

57600 BAU

D

115200 BAU

D

38400 BAU

D

OFF 4 WIRE/ ON 2 WIRE

OFF 422/ ON 485

120

 TERMINATION

OFF 4 WIRE/ ON 2 WIRE

OFF DCE/ ON DT

E

OFF DTE/ ON DCE

OFF DTE/ ON DC

E

OFF DCE/ ON DT

E

OFF 422/ ON 485

YORK, PA

.

MODEL ICM5

MUST BE SET IN GROUPS

SWITCHES

*

*

*

* *

@ 125mA MAX.

9-26VDC CLASS 

2

19200 BAU

D

9600 BAUD

PULL UP

PULL DOWN

RS232

10

6

2

1

3

5

4

7

9

8

NC

1

3

4

5

2

6

7

SPLY

PWR

ON

+ VDC

422

485/

LEDS

ON

RXA

RXB

TXB

TXA

2

1

4

3

5

6

7

 DIMENSIONS  In inches (mm)

CAUTION:  

Read complete instructions prior to 

installation and operation of the unit.

  

9 PIN D-SUB CONNECTOR FOR RS-232 CONNECTION

  

SWITCHABLE TERMINATION AND BIASING RESISTORS

  

MODULAR RJ JACK OR SCREW TERMINAL FOR RS-485 

CONNECTION

  

ALLOWS COMMUNICATIONS BETWEEN RS-232 CONTROL 

EQUIPMENT AND PRODUCTS WITH RS-422/RS-485 SERIAL 

COMMUNICATIONS

  

THREE WAY ISOLATION PROTECTS SERIAL EQUIPMENT FROM 

GROUND LOOPS (1000 VDC)

  

AUTOMATIC RS-485 DRIVER CONTROL

  

DIP SWITCH SELECTABLE BAUD RATES  9600, 19200, 38400, 

57600, 115200

  

WIDE DC INPUT POWER RANGE (+9 to 26 VDC)

  

HALF DUPLEX (RS-485) AND FULL DUPLEX (RS-422)

  

LED INDICATION FOR RXD, TXD, and POWER

  

UNIVERSAL MOUNTING FOOT FOR DIN RAIL INSTALLATION

  

SELECTABLE DTE & DCE OPERATION WORKS WITH ANY  

RS-232 CABLE

Bulletin No.  ICM5-E
Drawing No.  LP0529
Released  09/14

UL Recognized Component, 

File # E179259

Содержание ICM5

Страница 1: ...m 85 mA typical Power Supply must be Class 2 or SELV rated 2 RS 232 VOLTAGES Receive Data Pin 30 VDC max Mark Condition 0 8 VDC Space Condition 2 4 VDC Transmit Data Pin Mark Condition 8 VDC typ Space Condition 8 VDC typ 3 RS 485 VOLTAGES Differential Output Voltage 5 VDC max under no load Differential Input Voltage 5 VDC max Mark Condition 0 2 VDC Space Condition 0 2 VDC RS 485 Drive Capability U...

Страница 2: ...cation Listed below are the recommended methods of connecting the shield in order of their effectiveness a Connect the shield to earth ground protective earth at one end where the unit is mounted b Connect the shield to earth ground at both ends of the cable usually when the noise source frequency is over 1 MHz 3 Never run Signal or Control cables in the same conduit or raceway with AC power lines...

Страница 3: ...ed back This allows 2 wire half duplex operation without the use of handshake lines Both switches should be in the same position Switch 3 N C No Connection Switches 4 7 OFF DCE ON DTE These switches configure the RS 232 port to act as a DCE or DTE device With all of the switches in the DCE position pin 2 of the DB 9 connector is the RS 232 receiver and pin 3 is the RS 232 transmitter DTE configure...

Страница 4: ...dule until it releases from the rail TYPICAL RS 485 CONNECTIONS USING RJ 11 1 W RJ11 PRODUCT RED LION 4 7 10 115200 BAUD 57600 BAUD PULL DOWN 19200 BAUD 9600 BAUD 38400 BAUD OFF 4 WIRE ON 2 WIRE OFF 4 WIRE ON 2 WIRE 120Ω TERMINATION ON 2 1 3 10 8 9 6 4 5 7 PULL UP CABLE RS232 ICM5 OFF DTE ON DCE OFF DTE ON DCE OFF DCE ON DTE OFF DCE ON DTE OFF 422 ON 485 OFF 422 ON 485 7 6 4 3 NC 2 5 1 ON RJ 11 JU...