background image

 

Inside US: +1 (877) 432-9908

Bulletin No. GMDIO-J

Outside US: +1 (717) 767-6511

Drawing No. LP0921

www.redlion.net

Released  2018-10-31 

-1-

Model

 

GMDIO

 ‐ 

Graphite®

 

Digital

 

Module

C

US

UL

R

LISTED

IND.CONT. EQ.

FOR USE IN HAZARDOUS LOCATIONS:
    Class I, Division 2, Groups A, B, C, and D
    T4

E317425

ADDS I/O CAPABILITY TO THE GRAPHITE PRODUCTS

EIGHT INPUT, SIX OUTPUT DIGITAL MODULE

INPUTS ISOLATED FROM OUTPUTS

INPUTS INDEPENDENTLY SWITCH SELECTABLE FOR SINK OR 
SOURCE SIGNALS

INPUTS INDEPENDENTLY CONFIGURABLE FOR HIGH OR LOW 
ACTIVE STATE

INPUTS INDEPENDENTLY SWITCH SELECTABLE FOR HIGH OR 
LOW FREQUENCY SIGNALS

RELAY OR NFET OUTPUT MODELS AVAILABLE

C

US LISTED

UL

R

IND. CONT. EQ.

II 3 G Ex nA IIC T4 Gc
-40°C 

 T

AMB

 

 75°C

DEMKO 14 ATEX 1387X
IECEx UL 15.0035X

GENERAL

 

DESCRIPTION

The Model GMDIO14 module is a digital I/O module designed for use

with the Graphite products. This module offers eight inputs and six
outputs that can be used to monitor contact or sensor inputs and actuate
relays, solenoids, PLC inputs, etc.

The inputs accept standard DC inputs or contact closures, and are

configured for Sink/Source signals via external switches. Additionally,
each input has a switch selectable input filter that can be used to prevent
contact bounce. Each input may also be software configured as a high-
active or low-active input.

The module is available with relay or NFET outputs that are capable of

switching up to one amp each (NFET DC only). For applications
requiring large loads to be controlled, several DIN rail mount relays are
available.

The modules connect and communicate via proprietary USB

connection to the various Graphite host devices. The Graphite host
devices, equipped with serial ports as well as an Ethernet port(s), allows
the system to share data with PCs, PLCs, and SCADA systems. The
maximum number of modules varies for each Graphite host device, see
specific models for details. 

Once programmed, the module will continue to operate/control

independent of the Graphite host device as long as power is applied.
Remove power from the host device before installing or replacing any
modules.

CONFIGURATION

The Graphite is configured with Windows

®

 compatible Crimson

®

software. The software is an easy to use, graphical interface which
provides a means of configuration and commissioning of new systems,
as well as routine module re-calibration.

SAFETY

 

SUMMARY

All safety related regulations, local codes and instructions that appear

in this literature or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired. 

Do not use this unit to directly command motors, valves, or other

actuators not equipped with safeguards. To do so can be potentially
harmful to persons or equipment in the event of a fault to the unit.

WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU

CAUTION: Risk of Danger.

Read complete instructions prior to installation 
and operation of the unit.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 2.

DIMENSIONS

 

In

 

inches

 

(mm)

4.65

(118)

1.25 (32)

2.97 (76)

DIMENSIONS

 

In

 

inches

 

(mm)

For

 

Model

 

No.

 

GMDIOS00

 

Only

For

 

Model

 

No.

 

GMDIOS00

 

Only

E302106

Содержание Graphite GMDIOS00

Страница 1: ...hernet port s allows the system to share data with PCs PLCs and SCADA systems The maximum number of modules varies for each Graphite host device see specific models for details Once programmed the mod...

Страница 2: ...ng 1 ADC max VDS ON 0 2 V 1 A VDS MAX 30 VDC Offstate Leakage Current 0 5 mA max 6 ISOLATION LEVEL 500 Vrms 50 60 Hz for 1 minute between the following Inputs Outputs Graphite Host Power Supply Input...

Страница 3: ...following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 Red Lion Controls FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Controls...

Страница 4: ...e environment to which it is being installed When wiring the module use the numbers on the label to identify the position number with the proper function Strip the wire leaving approximately 1 4 6 mm...

Страница 5: ...erface Please see the Crimson manual for more information GRAPHITE TROUBLESHOOTING If for any reason you have trouble operating connecting or simply have questions concerning your new Graphite unit co...

Страница 6: ...6 Bulletin No GMDIO J Released 2018 10 31 Drawing No LP0921 This page intentionally left blank...

Страница 7: ...7 Released 2018 10 31 Bulletin No GMDIO J Drawing No LP0921 This page intentionally left blank...

Страница 8: ...mer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a...

Отзывы: