1. 

POWER REQUIREMENTS

:

Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.

Supply Voltage: 

+24 VDC ±20%

Typical Power

1

: 27 

W

Maximum Power

2

: 67 

W

Notes: 

1. Typical power with +24 VDC, RS232/485 communications, Ethernet 

communications, CompactFlash card installed, and display at full brightness.

2. Maximum power indicates the most power that can be drawn from the 

G315C. Refer to “Power Supply Requirements” under “Installing and 
Powering the G315C.”

3. The G315C’s circuit common is not connected to the enclosure of the 

unit. See “Connecting to Earth Ground” in the section “Installing and 
Powering the G315C.”

4. Read “Power Supply Requirements” in the section “Installing and 

Powering the G315C” for additional power supply information.

2. 

BATTERY

: Lithium coin cell. Typical lifetime of 10 years.

3. 

LCD DISPLAY

:

*Lifetime at room temperature. Refer to “Display” in “Software/Unit Operation”
4. 

10-KEY KEYPAD

: for on-screen menus.

5. 

TOUCHSCREEN

: Resistive analog

6. 

MEMORY

:

On Board User Memory

: 32 Mbyte of non-volatile Flash memory.

Memory Card

: CompactFlash Type II slot for Type I and Type II 

CompactFlash cards.

7. 

COMMUNICATIONS

:

USB Device Port

: Adheres to USB 2.0 Specification supporting high speed 

and full speed via Type B connection.

Serial Ports

: Format and Baud Rates for each port are individually software 

programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, V

OH

 = 15 VDC, 

V

OL

 = 0.5 V @ 25 mA max.

Note: For additional information on the communications or signal 

common and connections to earth ground please see the “Connecting to 
Earth Ground” in the section “Installing and Powering the G315C.”

Port to port isolation: 500 Vrms for 1 minutes signal isolation : 50V

Ethernet Port

: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to G3 operator interface: 1500 Vrms

8. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range

: 0 to 50 °C

Storage Temperature Range

: -20 to 70 °C

Operating and Storage Humidity

: 80% maximum relative humidity (non-

condensing) from 0 to 50°C.

Vibration according to IEC 68-2-6

: Operational 5 to 150 Hz, in X, Y, Z 

direction for 1.5 hours, 2 g’s.

Shock according to IEC 68-2-27

: Operational 35 g’s, 9 msec in 3 directions.

Altitude

: Up to 2000 meters.

9. 

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No.61010-1

Recognized to U.S. and Canadian requirements under the Component 
Recognition Program of Underwriters Laboratories, Inc.

UL Listed, File #E211967, UL61010-1, ANSI/ISA 12.12.01-2007, CSA 22.2 

No. 61010.1, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/12460C/UL,

CB Scheme Test Report #E179259-A1-CB-1

Issued by Underwriters Laboratories Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment 

for measurement, control, and laboratory use, Part 1.

IP66 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, 

Control and Laboratory use.

Note: 

1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self 
recovers.

10. 

CONNECTIONS

: Compression cage-clamp terminal block.

Wire Gage: 12-22 AWG copper wire
Torque: 5-7 inch-pounds (56-79 N-cm)

11. 

CONSTRUCTION

: Steel rear metal enclosure with NEMA 4X/IP66 

aluminum front plate for indoor use only when correctly fitted with the gasket 
provided. Installation Category II, Pollution Degree 2.

12. 

MOUNTING REQUIREMENTS

: Maximum panel thickness is 0.25" (6.3 

mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of 
0.125" (3.17 mm) is recommended.

Maximum Mounting Stud Torque

: 17 inch-pounds (1.92 N-m)

13. 

WEIGHT

: 11.41 lbs (5.17 Kg)

16.00 (406.4)

13.00

(330.2)

14.59 (370.6)

11.59

(294.4)

.28 

(7.1)

PROTECTIVE EARTH GROUND

2.8 

(71.5)

DIMENSIONS  In inches (mm)

S

PECIFICATIONS

15-inch

TFT

32K

1024 X 768

600 cd/m

2

50,000 HR TYP.

Class A

EN 55011

Emissions

Emissions:

3 V/rms

Criterion B

EN 61000-4-6

RF conducted interference

2 kV L&N-E power

2 kV power

Criterion B

EN 61000-4-4

Fast transients (burst)

Criterion A

EN 61000-4-5

Surge

1 kV L-L,

10 V/m

Criterion B

EN 61000-4-3

Electromagnetic RF fields

1 kV signal

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

WARNING - DO NOT CONNECT OR DISCONNECT CABLES WHILE 

POWER IS APPLIED UNLESS AREA IS KNOWN TO BE NON-

HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND 
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT 

CONNECTION.

SIZE

TYPE

COLORS

 PIXELS

 BRIGHTNESS

 BACKLIGHT

*

Содержание G315C

Страница 1: ...N0000 G3DN DeviceNet option card for G3 operator interfaces with isolated high speed communications ports G3DN0000 G3PBDP Profibus DP Optional Communication Card G3PBDP00 SFCRM2 Crimson 2 0 2 SFCRM200...

Страница 2: ...to IEC 68 2 27 Operational 35 g s 9 msec in 3 directions Altitude Up to 2000 meters 9 CERTIFICATIONS AND COMPLIANCES SAFETY UL Recognized Component File E179259 UL61010 1 CSA 22 2 No 61010 1 Recognize...

Страница 3: ...ny case it is very important that the power supply is mounted correctly if the unit is to operate reliably Please take care to observe the following points The power supply must be mounted close to th...

Страница 4: ...mpactFlash instructions in the Crimson 2 user manual CABLES AND DRIVERS Red Lion has a wide range of cables and drivers for use with many different communication types A list of these drivers and cabl...

Страница 5: ...1 COM 3 COM 6 TxEN 2 TxEN 5 Name RLC RJ11 Name G3 RJ45 Connections G3 to Modular Controller CBLRLC05 TxA 8 TxA 8 TxB 7 TxB 7 COM 6 COM 6 TxEN 5 TxEN 5 RxA TxA 3 2 2 3 RxA TxA 3 2 2 3 RxB 4 1 RxB 4 1 T...

Страница 6: ...Ds Shown below is the default status of the LEDs 1 The operator interface is shipped without a configuration After downloading a configuration if the light remains in the flashing state continuously t...

Страница 7: ...inimum of 4Mbytes with the G315C s CompactFlash socket Cards are available at most computer and office supply retailers CompactFlash can be used for configuration transfers larger configurations data...

Страница 8: ...yer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any pers...

Отзывы: