CONFIGURING A G09

The G09 is configured using Crimson

®

 software. Crimson is available as a 

free download from Red Lion’s website. Updates to Crimson for new features 
and drivers are posted on the website as they become available. By configuring 
the G09 using the latest version of Crimson, you are assured that your unit has 
the most up to date feature set. Crimson

®

 software can configure the G09 

through the RS232 PGM port, USB port, or SD.

The USB port is connected using a standard USB cable with a Type B 

connector. The driver needed to use the USB port will be installed with Crimson.

The RS232 PGM port uses a programming cable made by Red Lion to 

connect to the DB9 COM port of your computer. If you choose to make your own 
cable, use the “G09 Port Pin Out Diagram” for wiring information.

The SD can be used to program a G09 by placing a configuration file and 

firmware on the SD card. The card is then inserted into the target G09 and 
powered. Refer to the Crimson literature for more information on the proper 
names and locations of the files.

USB, DATA TRANSFERS FROM THE SD CARD

In order to transfer data from the SD card via the USB port, a driver must be 

installed on your computer. This driver is installed with Crimson and is located 
in the folder C:\Program Files\Red Lion Controls\Crimson 3.0\Device\ after 
Crimson is installed. This may have already been accomplished if your G09 was 
configured using the USB port.

Once the driver is installed, connect the G09 to your PC with a USB cable, 

and follow “Mounting the SD” instructions in the Crimson 3 user manual.

INSERTION/REMOVAL OF THE SD CARD

Insert the SD card into the slot provided with the card oriented as shown. The 

card is inserted properly when the end of the card is flush with  the Graphite 
case. To remove the SD card, push in slightly on the card.

WARNING - DO NOT CONNECT OR DISCONNECT CABLES 
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE 
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND 
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT 
CONNECTION.

c

OmmunIcatIng

 W

Ith

 

the

 g09

I/O MODULE INSTALLATION

Modules must be installed beginning with slot 1 (left-most slot), with no 

empty slots between the modules, and the order must match the modules order 
in the Crimson database. Torque screws to 6.0 pound-force inch [96 ounce-
force inch] (0.68 N m). 

REMOVE RUBBER

MODULE PLUG

WARNING: Disconnect all power 
to the unit before installing or 
removing modules.

POWER SUPPLY REQUIREMENTS

The G09 requires a 24 VDC power supply. Your unit may draw considerably 

less than the maximum rated power depending upon the features being used. As 
additional features are used your unit will draw increasing amounts of power.  
Items that could cause increases in current are modules, additional on-board 
communications, SD card, and other features programmed through Crimson.

To ensure you do not exceed the capacity of your Graphite host power supply, 

calculate the total power consumption required for all of your planned modules. 
Each module’s maximum power consumption is listed in the Specifications of 
their Product Bulletin. The total power available for modules is listed in the 
specifications of the Graphite host. 

In any case, it is very important that the power supply is mounted correctly if 

the unit is to operate reliably. Please take care to observe the following points:

–  The power supply must be mounted close to the unit, with usually not more 

than 6 feet (1.8 m) of cable between the supply and the operator interface. 
Ideally, the shortest length possible should be used.

–  The wire used to connect the operator interface’s power supply should be

at least 22-gage wire suitably rated for the temperatures of the environment 
to which it is being installed. If a longer cable run is used, a heavier gage 
wire should be used. The routing of the cable should be kept away from 
large contactors, inverters, and other devices which may generate 
significant electrical noise.

–  A power supply with an NEC Class 2 or Limited Power Source (LPS) and

SELV rating is to be used. This type of power supply provides isolation to 
accessible circuits from hazardous voltage levels generated by a mains 
power supply due to single faults. SELV is an acronym for “safety extra-
low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe 
to touch both under normal operating conditions and after a single fault, 
such as a breakdown of a layer of basic insulation or after the failure of a 
single component has occurred. A suitable disconnect device shall be 
provided by the end user.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]