background image

Etherbus Hardware Manual 

Page 22 of 23  

            Last Revised: 17-Sep-13 

Red Lion

 

Controls

 

 331 Ushers Road 

 Ballston Lake, NY 12019 

 USA 

 +1-518-877-5173 

 

[email protected]

 

 

Etherbus DC/DC Converter Performance Specifications

 

Model 

EB-PS-4824-13 

Output 

DC voltage 

24 VDC 

Rated current 

0.54 Amps  

Current range 

– 0.54 Amps 

Rated power 

13 Watts  

Ripple / noise (max.) 

200 mV p-p 

Voltage tolerance 

+/- 1% 

DC voltage range 

45 

– 56 VDC 

Efficiency (typ.) 

85 % 

Current (typ.) 

0.32 Amps @ 48 VDC 

Protection 

Over-load 

Current limiting with automatic recovery 

Over-voltage 

Transient: 15Kw peak; 
Surge: 5K watts (10x10 uS) 

Over-temperature 

140°C with auto. recovery 

Environmental 

Operation temp. 

-40 to + 75°C 

Operation humidity 

5 to 95% RH (non-cond.) 

Storage 

-40 to + 85°C 

Vibration, shock and freefall 

IEC68-2-6, -27 and -32 

Standards  

Safety 

 

UL508 / CSA C22.2/14 (CUL); EN61010-1

 

Hazardous locations  

ANSI / ISA12.12.01  / CSA C22.2/213 (CUL), Clas s 1, 
Division 2;  
ATEX / IEC60079-0, -15 (Zone 2) 

EMC emissions and immunity 

FCC Part 15 / ICES-003; EN55022 / IEC61326-1 

Withstand voltage 

Input to output: 1500 Vrms  

Miscellaneous  

MTBF (estimated) 

>1,000,000 hours 

Packaging 

Polycarbonate; IP30 

Mounting 

DIN rail or flat to panel 

Weight (approximate) 

0.17 Kg (0.25 lbs) 

Dims (w x h x d) (approximate) 

25 x 101 x 76 mm (1.0 x 4.0 x 3.0 inches) 

Содержание EB Series

Страница 1: ...unting Page 6 Section 4 Power Wiring Page 10 Section 5 Communication Wiring Page 15 Section 6 Technical Specifications Page 18 Section 7 Service Information Page 22 This manual applies to the following products EB 5ES PSE Industrial PoE 5 port unmanaged Ethernet switch EB PSE 48V 2 Industrial PoE power injector for 2 channels EB PSE 24V 1 Industrial PoE power injector with built in 24V to 48V conv...

Страница 2: ...y way increase the scope of this warranty This limited warranty is in lieu of all other warranties whether oral or written expressed or implied RED LION s liability shall not exceed the price of the individual units which are the basis of the claim In no event shall RED LION be liable for any loss of profits loss of use of facilities or equipment or other indirect incidental or consequential damag...

Страница 3: ...8 VDC 48V PoE 4 EB PSE 48V 2 Injector 48 VDC 48V PoE 2 EB PSE 24V 1 Injector 24 VDC 48V PoE 1 EB PD 24V 1 Splitter 48V PoE 24 VDC 1 EB PD UPS 1 Splitter 48V PoE 14 VDC 1 EB PS 4824 13 Converter 48 VDC 24 VDC Key PD Powered Device accepts 48V PoE power PSE Power Sourcing Equipment puts out 48V PoE power Reference Images EB 5ES PSE 1 EB PSE 48V 2 EB PSE 24V 1 EB PD 24V 1 EB PS 4824 13 Safety Standar...

Страница 4: ...dicators Overview The Etherbus devices have several LEDs to indicate the power and operational status of the unit See below for the location of these LEDs and an explanation of their operation EB 5ES PSE 1 EB 5ES PSE 2ST EB PSE 48V 2 EB PSE 24V 1 EB PD 24V 1 EB PS 4824 13 Typical LED Location for Etherbus Products Note The LED locations may vary slightly from these images ...

Страница 5: ...n the RJ45 connector of Port 5 on the Etherbus switch model EB 5ES PSE 1 It indicates the Speed of the uplink port ON green A 100 Mbps 100BaseT connection is detected OFF A 10 Mbps 10BaseT connection is detected Fiber Optic Port LED This is the Green LED above the fiber port on the Etherbus switch model EB 5ES PSE 2 or 3 It indicates the Link status of the fiber optic port ON green A 100 Mbps 100B...

Страница 6: ... flat panel Refer to the mechanical drawings below to properly mount your switch Note Make sure to allow enough room to route your Ethernet copper or fiber optic cables DIN Rail Mounting Recommended DIN rail mounting steps 1 Hook top back of unit over the din rail 2 Push bottom back onto the din rail until it snaps into place Recommended DIN rail removal steps A Insert screwdriver into din clip an...

Страница 7: ...cal for SC or ST fiber Removable Screw Block Snaps to standard DIN rail EN50022 35 mm 1 01 2 57 cm 1 01 2 57 cm 4 20 10 67 cm EB 5ES PSE 2 90 7 35 cm Mechanical Dimensions for the Etherbus Switch Dia 0 15 0 38 cm Use for direct panel mounting to a flat surface 3 95 10 03 cm 1 98 5 02 cm 1 98 5 02 cm 1 00 2 54 cm 3 26 8 28 cm 0 06 0 15 cm Removable Screw Block Snaps to standard DIN rail EN50022 35 ...

Страница 8: ...able Screw Block Snaps to standard DIN rail EN50022 35 mm 1 01 2 57 cm 1 01 2 57 cm 4 20 10 67 cm EB PSE 24V 2 90 7 35 cm Mechanical Dimensions for the Etherbus Injector with DC DC Converter Dia 0 15 0 38 cm Use for direct panel mounting to a flat surface 3 95 10 03 cm 1 98 5 02 cm 1 98 5 02 cm 1 00 2 54 cm 3 26 8 28 cm 0 06 0 15 cm Removable Screw Block Snaps to standard DIN rail EN50022 35 mm 1 ...

Страница 9: ...rt redlion net Dia 0 15 0 38 cm Use for direct panel mounting to a flat surface 3 95 10 03 cm 1 98 5 02 cm 1 98 5 02 cm 1 00 2 54 cm 3 26 8 28 cm 0 06 0 15 cm Removable Screw Block Snaps to standard DIN rail EN50022 35 mm 1 01 2 57 cm 1 01 2 57 cm 4 20 10 67 cm EB PS 4824 13 2 90 7 35 cm Mechanical Dimensions for the Etherbus DC DC Converter ...

Страница 10: ... operation make sure your 48 VDC supply is rated for at least 16 Watts per PoE channel being sourced plus some overhead for the switch It is recommended that a supply with 75 Watts or more of power be used The Etherbus switch supports dual power inputs allowing you to connect a backup power source The backup power should have the same voltage as the primary power Make your power connections as sho...

Страница 11: ...will put out 48 VDC see note below over the unused pair of lines in the RJ45 connection o V on lines 4 and 5 o V on lines 7 and 8 o TX on lines 3 and 6 o RX on lines 1 and 2 The 2B model special order when sourcing PoE power will put out 48 VDC see note below over the signal pair of lines in the RJ45 connection o V on RX lines 1 and 2 o V on TX lines 3 and 6 o Lines 4 5 7 and 8 are unused DC Suppl...

Страница 12: ...ections as shown in the diagram below There are two models of this injector The standard 1A model when sourcing PoE power will put out 48 VDC over the unused pair of lines in the RJ45 connection o V on lines 4 and 5 o V on lines 7 and 8 o TX on lines 3 and 6 o RX on lines 1 and 2 The 1B model special order when sourcing PoE power will put out 48 VDC over the signal pair of lines in the RJ45 connec...

Страница 13: ...er over the unused lines to the PoE IN port The splitter will convert the 48 VDC to 24 VDC and make it available on the pluggable screw terminal block Make your power connections as shown in the diagram below 24 VDC Load EB PD 24V DC Power Output Chassis GND panel The UPS model special order is the same as above but outputs 14 VDC instead of 24 VDC The 14 VDC can be used to power 12V or 14V device...

Страница 14: ...rter Power The Etherbus DC to DC converter accepts power in the range of 45 to 56 VDC and outputs an isolated and regulated 24 VDC 13 watts This convenient accessory allows you to power typical 24 VDC industrial devices from your 48 VDC system power Make your input and output power connections as shown below 45 56 VDC Input 24 VDC Output EB PS 4824 13 Power Connections ...

Страница 15: ...re Two types of communication ports may be found on these switches RJ45 copper Ethernet ports or fiber optic Ethernet ports Switch RJ45 Port Wiring Use data quality not voice quality twisted pair cable rated category 5 or better with standard RJ45 connectors For best performance use shielded cable Straight through or crossover RJ45 cable can be used regardless of the device the switch is to be con...

Страница 16: ...ce Use standard fiber optic wiring techniques not covered by this manual to make your connections The corresponding ACT LNK LED will be ON solid when you have made a proper connection See images below for typical fiber optic port placement Duplex Operation The RJ45 ports will auto sense for Full or Half duplex operation while the fiber port is configured for full duplex operation Note Fiber device...

Страница 17: ...o the ETH IN port This cable is typically coming from an Ethernet switch or router Then connect the cable to be run to your PoE Powered device PD to the PoE OUT port The PoE LED will be ON when power is being sourced to your device PoE Splitter RJ45 Wiring The Etherbus industrial Ethernet PoE splitter has two RJ45 ports See the diagram below One RJ45 port is labeled PoE IN for PoE input and the ot...

Страница 18: ...d bandwidth 1024 and 3 2 Gbps Power In and PoE Out Redundant input terminals Power input with reverse polarity protection 10 30 VDC with no PoE output 45 56 VDC for PoE output Switch power consumption typical all ports active at 100 Mbps 2 0 W 5 port without fiber PoE 3 0 W 5 port with 1 fiber PoE PoE power consumption Up to 15 4 W per port RJ45 pin assignments for PoE TX V 3 6 RX V 1 2 Power inpu...

Страница 19: ...Etherbus Hardware Manual Page 19 of 23 Last Revised 17 Sep 13 Red Lion Controls 331 Ushers Road Ballston Lake NY 12019 USA 1 518 877 5173 support redlion net MTBF estimated 1 000 000 hours ...

Страница 20: ... PoE protection Over temp over current over under voltage transient Power Input Fully IEEE 802 3af PoE compliant Power input for 48V 2 models 45 56 VDC 31 Watts max Power input for 24V 1 models 18 30 VDC 20 Watts max PoE transient protection 15 000 watts peak PoE spike protection 5 000 watts 10 times for 10 uS Environmental Truly industrial design Operating temperature range 40 to 75 C cold startu...

Страница 21: ... PoE transient protection 15 000 watts peak PoE spike protection 5 000 watts 10 times for 10 uS Power Output Isolated power Voltage output 24 VDC 0 54 Amps 24V model 14 VDC 0 93 Amps UPS model Power output 13 watts Environmental Truly industrial design Operating temperature range 40 to 75 C cold startup 40 Storage temperature range 40 to 85 C Humidity non condensing 5 to 95 RH Vibration shock and ...

Страница 22: ...r voltage Transient 15Kw peak Surge 5K watts 10x10 uS Over temperature 140 C with auto recovery Environmental Operation temp 40 to 75 C Operation humidity 5 to 95 RH non cond Storage 40 to 85 C Vibration shock and freefall IEC68 2 6 27 and 32 Standards Safety UL508 CSA C22 2 14 CUL EN61010 1 Hazardous locations ANSI ISA12 12 01 CSA C22 2 213 CUL Class 1 Division 2 ATEX IEC60079 0 15 Zone 2 EMC emi...

Страница 23: ... will not be billed if the repair is covered under warranty Please supply us with as many details about the problem as you can The information you supply will be written on the RMA form and supplied to the repair department before your unit arrives This helps us to provide you with the best service in the fastest manner Normally repairs are completed in two days Sometimes difficult problems take a...