SPECIFICATIONS

1. 

POWER

: 24 VDC ± 10% 

200 mA min., without expansion card

1 Amp maximum with expansion card fitted

Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.

2. 

COMMUNICATIONS

:

USB/PG Port

: Adheres to USB specification 1.1. Device only using Type B 

connection.

Serial Ports

: Format and Baud Rates for each port are individually software 

programmable up to 115,200 baud.

RS232/PG Port

: RS232 port via RJ12

COMMS Ports

: RS422/485 port via RJ45, and RS232 port via RJ12

DH485 TXEN

: Transmit enable; open collector, V

OH

 = 15 VDC,  

V

OL

 = 0.5 V @ 25 mA max.

Ethernet Port

: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).

3. 

LEDs

:

STS – Status LED indicates condition of Data Station.

TX/RX – Transmit/Receive LEDs show serial activity.

Ethernet – Link and activity LEDs.

CF – CompactFlash LED indicates card status and read/write activity

4. 

MEMORY

:

On-board User Memory: 4 Mbytes of non-volatile Flash memory.

On-board SDRAM: 2 Mbytes

Memory Card: CompactFlash Type II slot for Type I and Type II cards.

Used for optional database storage only

5. 

REAL-TIME CLOCK

: Typical accuracy is less than one minute per month drift.

Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.

A “Battery Low” system variable is available so that the programmer can 

choose specific action(s) to occur when the battery voltage drops below 

its nominal voltage.

This unit is NOT field serviceable. All work must be done by a qualified 

technician.

6. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: 

DSPLE000: 0 to 50 °C

DSPLE001: -20 to 70 °C

Storage Temperature Range: -30 to 70 °C

Operating and Storage Humidity: 80% max relative humidity, 

 non-condensing, from 0 to 50 °C

Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.

Shock to IEC 68-2-27: Operational 30 g

Altitude: Up to 2000 meters

7. 

CONSTRUCTION

: Case body is burgundy high impact plastic and 

stainless steel. For indoor use only. Installation Category II, Pollution 

Degree 2.

8. 

POWER CONNECTION

: Removable wire clamp screw terminal block.

Wire Gage Capacity: 24 AWG to 12 AWG

Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)

9. 

MOUNTING

: Snaps onto standard DIN style top hat (T) profile mounting 

rails according to EN50022 -35 x 7.5 and -35 x 15.

10. 

CERTIFICATIONS AND COMPLIANCES

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

Safety requirements for electrical equipment for measurement, control, and 

laboratory use: 

EN 61010-1: General Requirements

EN 61010-2-201: Particular Requirements for Control Equipment

RoHS Compliant

UL Listed: File #E302106

UL Hazardous: File #E317425

ABS Certificate #09-HS426719-B-4-PDA

Refer to EMC Installation Guidelines section of the bulletin for additional 

information.

11. 

WEIGHT

: 15.1 oz (428 g)

HARDWARE

INSTALLATION

DIN rail should be mounted horizontally so that the unit’s ventilation holes 

are vertical in relation to cabinet orientation. A minimum clearance of 1 inch 

(25.4 mm) should be maintained above and below the unit in order to ensure 

proper thermal regulation.

The unit shall be installed inside a UL Listed Industrial Control Panel or 

similar type of enclosure. A minimum 3.2 mm distance shall be maintained 

between the hazardous live parts of the equipment and accessible parts of the 

fire/electrical enclosure.

Figure 1 - Attach Data Station To DIN Rail

2

1

ETHERNET

RS485

RS232

USB/PG

CF

RS232/PG

STS

1.00"

1.00"

min. clearance

min. clearance

TOP

BOTTOM

WARNING - DO NOT CONNECT OR DISCONNECT CABLES 

WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE 

NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND 

DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT 

CONNECTION.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 

EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR 

AREA IS KNOWN TO BE NON-HAZARDOUS.

Содержание DSPLE

Страница 1: ...h can be purchased as part of a kit that includes a manual and cables or downloaded free of charge from www redlion net SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not specifi...

Страница 2: ...l 30 g Altitude Up to 2000 meters 7 CONSTRUCTION Case body is burgundy high impact plastic and stainless steel For indoor use only Installation Category II Pollution Degree 2 8 POWER CONNECTION Removable wire clamp screw terminal block Wire Gage Capacity 24 AWG to 12 AWG Torque 4 45 to 5 34 in lb 0 5 to 0 6 N m 9 MOUNTING Snaps onto standard DIN style top hat T profile mounting rails according to ...

Страница 3: ...re the unit is mounted b Connect the shield to earth ground at both ends of the cable usually when the noise source frequency is over 1 MHz 3 Never run Signal or Control cables in the same conduit or raceway with AC power lines conductors feeding motors solenoids SCR controls and heaters etc The cables should be run through metal conduit that is properly grounded This is especially useful in appli...

Страница 4: ...S485 USB PG RS232 PG ETHERNET CF STS CBLxxxxx CHASSIS GND OR CBLPROG0 REM SLC 5 03 CPU RUN BATT FLT RUN RS232 DH485 FORCE PROG VDC PWR OUT 24 PWR OUT COM VAC NEUT 120 240 VAC USER POWER POWER RS232 PG USB PG RS232 PG ETHERNET WARNING EXPLOSION HAZARD DO NOT DISCONNECT WHILE CIRCUIT IS ALIVE UNLESS AREA IS KNOW TO BE NON HAZARDOUS INPUT AND OUTPUT I O WIRING MUST BE IN ACCORDANCE WITH CLASS I DIV 2...

Страница 5: ...of the available cables WARNING Do NOT use a standard DH 485 cable to connect this port to Allen Bradley equipment PORT 3 ETHERNET CONNECTION RS232 RS485 5 EXPANSION 24VDC 10 USB PG TxA PIN 8 GREEN YELLOW LED LED AMBER NIC ETHERNET RS232 PORT COMMS COMMS PORT COMM CTS PIN 1 COMM Rx Tx RTS PIN 6 TxB COMM RxA RxB TxA TxB PIN 1 TxEN RS485 ETHERNET RS232 RS485 CF RS232 PG PORT RTS PIN 6 CTS PIN 1 USB ...

Страница 6: ...ls Crimson 2 0 Device after Crimson 2 0 is installed This may have already been accomplished if your Data Station was configured using the USB port Once the driver is installed connect the Data Station to your PC with a USB cable and follow Mounting the CompactFlash instructions in the Crimson 2 0 user manual Note The USB port is for system set up and diagnostics and is not intended for permanent ...

Страница 7: ...communication drivers and cables 2 Use this part number to purchase the Crimson software on CD with a printed manual USB cable and RS 232 cable Otherwise download free of charge from www redlion net 3 Antenna G3QANT00 is NOT included with the card Must be purchased separately if needed 4 Red Lion offers RJ modular jack adapters Refer to the DR literature for complete details 5 Industrial grade two...

Страница 8: ...demnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P...

Отзывы: