ORDERING INFORMATION

MODEL NO.

DESCRIPTION

PART NUMBERS

CUB4LP

Reflective LCD Loop Powered Process Indicator

CUB4LP00

Red Backlit LCD Loop Powered Process Indicator 

Positive Image Transflective LCD

*CUB4LP40

CUB4CL

Yel/Grn Backlit LCD External Powered Process 

Indicator Negative Image Transmissive LCD

CUB4CL10

Red Backlit LCD External Powered Process 

Indicator Negative Image Transmissive LCD

CUB4CL20

Yel/Grn Backlit LCD External Powered Process 

Indicator Positive Image Transflective LCD

CUB4CL30

Red Backlit LCD External Powered Process 

Indicator Positive Image Transflective LCD

CUB4CL40

MLPS

Micro Line/Sensor Power Supply 

(Non-hazardous use only)

MLPS1000

    *Backlight intensity will vary depending on signal level.

CALIBRATING THE DISPLAY

Calibrating the CUB4LP/CL requires either an accurate adjustable constant 

current supply or the CUB4LP/CL can be installed and scaled with the process 

sensor connected to the CUB4LP/CL. To calibrate the unit, proceed as follows.
1. Set DIP switching for the desired current range.

2. Select the desired decimal point position.

3. Apply the minimum input signal to the CUB4LP/CL and adjust the COARSE 

OFFSET to display the approximate desired minimum value.

4. Apply the maximum input signal to the CUB4LP/CL and adjust the COARSE 

SPAN to display the approximate desired maximum value.

5. Repeat steps 3 and 4 until the minimum and maximum values are within the 

desired values.

6. Apply the minimum input signal to the CUB4LP/CL and adjust the FINE 

OFFSET to display the exact desired minimum value.

7. Apply the maximum input signal to the CUB4LP/CL and adjust the FINE 

SPAN to display the exact desired maximum value.

8. Apply the minimum input signal and verify that the display indicates 

correctly.

9. Apply the maximum input signal and verify that the display indicates 

correctly.

10. Repeat Steps 6 through 9 until display reads exact.

Note: The CUB4LP/CL display is factory calibrated to indicate 0.0 to 100.0 

with an input of 4 to 20 mA at approximately 25°C.

BLOCK DIAGRAM

PROCESS

CIRCUITR

Y

S4

S3

S2

SIG-

SIG+

+VDC

COM 

S1

8.25

Ω

12.7Ω

COARSE

SPAN

GND

1

2

3

4

BACKLIGHT

FINE

OFFSET

OFFSET

COARSE

FINE

SPAN

-V

+V

0.1 

µ

f

50 VDC

(CL ONLY)

(CL ONLY)

Connection for

CUB4LP40 

DECIMAL POINT POSITION SELECTION

The decimal point position is DIP switch selectable for one of three locations.  

The CUB4LP/CL can be set up to read in 10ths, 100ths, or 1000ths.  If all the 

DIP switches are set to the “OFF” position, no decimal point will appear on the 

display.  The DIP switches are located at the rear of the unit.

APPLICATION EXAMPLE

Operation of a refinery process required a local display of the position of a 

remote pipeline valve. The display would indicate 0 (zero) when the valve was 

fully closed with an input signal of 4 mA. When the valve was fully open the 

display would indicate 100 with an input signal of 20 mA.

Both the CUB4LP and the CUB4CL meet the necessary requirements.

VALVE

CONTROL

DEVICE

+

+

-

-

CUB4LP

SIG +

COMM

(SIG -)

TROUBLESHOOTING

For further technical assistance, contact technical 

support at the appropriate company numbers listed. 

Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls

China

Unit 302, XinAn Plaza

Building 13, No.99 Tianzhou Road

ShangHai, P.R. China 200223

Tel +86 21 6113 3688

Fax +86 21 6113 3683

Red Lion Controls

Europe

Softwareweg 9

NL - 3821 BN Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793

Red Lion Controls

India

201-B, 2nd Floor, Park Centra
Opp 32 Mile Stone, Sector-30

Gurgaon-122002 Haryana, India

Tel +91 984 487 0503

Отзывы: