background image

3

CUB4V SIGNAL INPUT

The voltage range is selected by setting one of the DIP switches S1 to S4 for 

the desired input voltage. The unit will indicate the direct readout for the range 

selected.

Note: Only one Voltage Range switch (S1-S4) should be selected (ON).

The SCALE DIP switch (S5) and the Scaling Potentiometer are used when it 

is necessary to scale the display to indicate other engineering units. The Scale 

switch should be left in the “OFF” position when the application requires direct 

voltage readout on the display.

The Calibration Potentiometer has been set at the factory and should not be 

adjusted unless the unit is being re-calibrated with an accurate voltage source.

The power supply common and signal common are connected internally at 

the same screw terminal marked COMM. The power supply common, and the 

signal common must be at the same voltage potential. The voltmeter cannot 

measure a voltage with a reference that is different than the power supply 

common. 

Caution: The Maximum Voltage for each switch position must not be 

exceeded or the unit may be damaged (See Specifications).

Caution: 9 to 28 VDC power circuit is not isolated from the  

signal circuit.

VOLTMETER SCALING

In many industrial applications, a voltmeter is required to display a reading 

in terms of PSI, RPM, or some other unit of measure. The signal voltage being 

measured is normally generated by a transducer which senses the variable and 

delivers a linear output voltage. To provide the desired readout at the specified 

voltage, the voltmeter must be scaled. The Scale switch, when in the “ON” 

position, enables the Scale Potentiometer. The Scale Potentiometer is used with 

a voltage range to provide a method of scaling the unit. The voltage DIP 

switches are used to select one of the four coarse Division Factor ranges and the 

Scale Potentiometer is a fine scale adjustment within the selected range. The 

chart below shows the division factor range associated with each range 

selection switch.

DIVISION FACTOR RANGE SELECTION CHART

S1:  0-199.9 mVDC  (0.1  D.F.  1.2)

S2:  0-1.999 VDC  (1.2  D.F.  10.5)

S3:  0-19.99 VDC  (10.5  D.F.  100.5)

S4:  0-199.9 VDC  (100.5  D.F.  1300)

Note: Enabling the Scale Potentiometer does NOT affect the calibration of  

the unit.

To determine the proper voltage range for an application requiring scaling, 

the “Division Factor” required to provide the proper display reading must first 

be determined by using the following formula.

USING THE FORMULA:

D.F  =  VT x D.D.P.

D.R.

WHERE:

VT 

=  Maximum Transducer Output

D.D.P.  =  Display Decimal Point

D.F. 

=  Division Factor

D.R. 

=  Desired Reading

D.D.P.

0.000  = 1 

The DISPLAY DECIMAL POINT (D.D.P.)

00.00  =  10 

is determined by the desired decimal

000.0  =  100 

point placement in the readout.

0000  = 1000

POINTS

DECIMAL

SWITCHES

VOLTAGE

CAL. POT.

SCALE POT.

8

7

6

5

4

3

2

1

0.000

0.00

0.

0

SCAL

E

199.9VDC

19.99VDC

1.999VDC

199.9mVD

C

4

199.9VDC

YORK, PA. 

RED LION CONTROLS

1 COM

3 SIG.+

1.999VDC

199.9m

V

19.99VDC

ON

2

1

3

CALIB

.

SCAL

E

0.

0

SCAL

E

0.000

0.00

MADE IN U.S.A.

6

5

7 8

D.P.

V+ 2

CUB4V

M1508F

After the Division Factor for the application has been calculated, the proper 

voltage range switch that will provide for the Division Factor is set to the “ON” 

position. Use the “Division Factor Range Selection Chart” to choose the proper 

DIP switch setting.

Note: Only one voltage DIP switch should be turned on. Set the switch before 

the voltage signal is applied.

EXAMPLE:

 A relative humidity transducer delivers a 7.0 VDC voltage at a 

relative humidity of 75%.

D.F.  =  VT x D.D.P.  =  7.0 x 1000  =  93.3

D.R.                  75

This Division Factor is between 10.5 and 100.5, therefore DIP switch 

position S3 is set to the “ON” position. The Scaling Potentiometer is then 

adjusted for the desired readout at a known relative humidity.

CUB4I SIGNAL INPUT

The CUB4 Current Meter has four current ranges that are selected by 

positioning the jumper in the proper location on the male header strip.

The SCALE DIP switch (S1) and the Scaling Potentiometer are used when it 

is necessary to scale the display to indicate other engineering units. The Scale 

switch should be left in the “OFF” position when the application requires direct 

current readout on the display.

When the power supply is floating (unreferenced) to the desired measurement 

points, the (-) signal input and the power supply common should be connected. 

If the power supply is not floating (referenced), the common mode voltage 

between the (-) signal input and power supply common terminal must not be 

greater than 1.0 V peak. A common mode voltage higher than 1.0 V peak will 

result in a measurement error.

The Calibration Potentiometer has been set at the factory and should not be 

adjusted unless the unit is being re-calibrated with an accurate current source. 

Caution:  The  Maximum  Current  for  each  jumper  position  must  not                                                     

be exceeded or the unit may be damaged (See Specifications).

BLOCK DIAGRAM CUB4V

19.99m

A

199.9m

A

199.9µA

1.999m

A

CAL. POT.

SCALE POT.

4

3

2

1

0.000

0.00

0.

0

SCAL

E

YORK, PA. 

RED LION CONTROLS

3 SIG.-

1 COM

1.999mA

199.9uA

SCAL

E

ON

1

0.00

0.00

0

3

0.

0

2

4

199.9mA

19.99mA

MADE IN U.S.A.

CALIB

.

SCAL

E

V+ 2

SIG.+ 4

Отзывы: