ALARM #2 ASSIGNMENT TO INPUT OR INTEGRATOR/
TOTALIZER
Alarm #2 may be programmed to activate on either the input or the
integrator/totalizer value. If the integrator/totalizer option is not installed, this
step defaults to the input.
“ASN-2” < > “INPUt”or “totAL”
PROGRAM VALUE FOR ALARM #2
The range of the alarm value is -999 to 9,999 for the input display and -99999
to 999999 for the totalizer option display.
“AL-2” < > “-999” to “9999”
PROGRAM HYSTERESIS VALUE FOR ALARM #2 (Cannot be
programmed if alarm latch is programmed)
The hysteresis
(deadband)
value for alarm #2 may be programmed from 1 to
9,999 for the input and 1 to 999999 for the totalizer option. The value is either
added to or subtracted from the alarm value depending on whether the alarm is
high or low acting.
(See “alarms” section for operation.)
“HyS-2” < > “1” to “9999”
ALARM #2 HIGH OR LOW ACTING
The action of alarm #2 may be programmed to activate either when the signal
goes above the alarm value
(high acting)
or goes below it
(low acting)
.
“Act-2” < > “HI”or “LO”
Note: Depending on options selected under Pro 3 and Pro 6, alarms, hysteresis,
peak, and valley values can be monitored and/or changed when PGM. DIS. is
tied to COMM. This provides a “QUICK PROGRAMMING” method for “day
to day” process changes. (See QUICK PROGRAMMING SECTION for more
details.)
-15-