background image

3

INPUT FUSES

The internal input fuse (included) is not user accessible. The unit is tested 

and approved for branch circuits up to 20 A. An external protection is only 

required if the supplying branch has an ampacity greater than 20 A, however, 

in some countries local regulations might apply. Check local codes and 

requirements. If an external fuse is necessary or utilized, minimum 

requirements need to be considered to avoid nuisance tripping of the circuit 

breaker. See unit specifications for the minimum value Characteristic breaker 

that should be used:

INPUT 

The input con nection is made by the connections “L” and “N” (torque 0.5 

Nm) on the terminal block connection. 

 

If the internal fuse is triggered, there is most probably a malfunction 

in the device. In this case, the device must be returned to the 

factory for inspection

OUTPUT

The 24 VDC connection is made by the connections labeled “+” and “-” on 

the terminal block connection. At the time of delivery, the output voltage is 

24.5 VDC. The output voltage can be set from 24 to 28 VDC using the 

potentiometer.

The device is electronically protected against short circuits and idling. In 

the event of an error, the output voltage is limited to the max VDC listed in 

the specifications. The unit includes an LED indicator “DC on”. This indicator 

will illuminate when DC out is >17 VDC for 30W and 60W, >20 VDC for 

95W.

Output and Overload Characteristic

The units are overload, no-load, short-circuit proof. Above the rated output 

current, the output voltage will decrease as a result of the output current 

limitation. The current flows continuously. No hiccup or shut-down behavior. 

DIELECTRIC STRENGTH

The output voltage is floating and separated from the input according to 

SELV (IEC/EN 60950-1) and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 

60364-4-41) requirements. Type and factory tests are conducted by the 

manufacturer. Field tests may be conducted in the field using the appropriate 

test equipment which applies the voltage with a slow ramp (2 sec up and 2 sec 

down).

Connect all phase-terminals together as well as all output poles before the 

test is conducted. When testing, set the cut-off current settings to the value in 

the table below.

PSDR030W

A

C

Type Test (60 sec) 

2500 VAC

3000 VAC 

500 VAC

Factory Test (5 sec) 

2500 VAC 

2500 VAC

500 VAC

Field Test (5 sec) 

2000 VAC

2000 VAC

500 VAC

Cut-off current setting 

>6 mA 

>6 mA

>1 mA

PSDR060W

A

C

Type Test (60 sec) 

2500 VAC

4000 VAC 

2000 VAC

Factory Test (5 sec) 

2500 VAC 

2500 VAC

500 VAC

Field Test (5 sec) 

2000 VAC

2000 VAC

500 VAC

Cut-off current setting 

>4 mA 

>4 mA

>1 mA

PSDR095W

A

C

Type Test (60 sec) 

2500 VAC

3000 VAC 

500 VAC

Factory Test (5 sec) 

2500 VAC 

2500 VAC

500 VAC

Field Test (5 sec) 

2000 VAC

2000 VAC

500 VAC

Cut-off current setting 

>6 mA 

>6 mA

>20 mA

AC 100-120 / 220-240V

N

24-28V

DC on

24V 

+ +

3.9A

Power Supply

L

PSDR095W

NEC Class 2

_

_

AC 100-240V

PSDR030W

Power Supply

L

N

24-28V

+ _ _

24V  1.3A

DC on

Power Supply

N L

AC 100-240V

PSDR060W

_ _

+ +

24V  2.5A

DC on

24-28V

Output Voltage

0

0

0.8

1.6

4

8

12

28V

16

20

24

2.8A

2.0

1.2

0.4

2.4

Adjustment

Range

Output Current

Output Voltage

0

0

4

8

12

28V

16

20

24

6A

3

2

1

5

4

Adjustment

Range

Output Current

PSDR060W

PSDR030W

A

C

N

L

Input

Earth, PE

Output

 -

+

B

Output Voltage

0

0

2

4

4

8

12

28V

16

20

24

8A

5

3

1

6

7

Adjustment

Range

Output

Current

 

PSDR095W

Отзывы: