NOTE – for multiple interconnected smoke alarms, only the RED indicator light (LED) of 

the originating unit will flash rapidly. All other units in the interconnect system will sound 

an alarm but their RED indicator light (LED) will NOT flash. Test each alarm checking that 

the alarm is triggered on all other alarms installed.

HUSH OR SILENCE FEATURE

• This Smoke Alarm has a built-in Hush or Silence feature incorporated into the Test 

   button.  If cooking or other non-hazardous sources cause the unwanted alarm, it can be 

   temporarily silenced by depressing the test button and holding for approximately three 

   seconds.  The alarm will enter a dormant period for ten minutes.  The red LED will flash 

   every ten seconds to indicate the sensitivity is reduced.  At the end of the hush period 

   the alarm will reset to normal sensitivity.
NOTE – If the smoke density increase during this period (i.e. from a fire) the unit will go 

into alarm mode.

PHOTOELECTRIC SMOKE ALARM

FOR MODEL: SMAS-P2

LOW BATTERY WARNING

• If the smoke alarm emits a short ‘beep’ once a minute the battery is at the end 

   of its life and should be replaced immediately. This low voltage warning will be 

   given for at least 30 days. In this case, the other interconnected units in the 

   system which are not in low battery condition will chirps for a few seconds once 

   an hour as long as the detector with the “dead” battery beeps. 

• If the red indicator light (LED) does not flash every minute then replace the 

   battery.

PHOTOELECTRIC SMOKE ALARM

FOR MODEL: SMAS-P2

MAINTENANCE

• Clean your smoke alarm at least once every six months to prevent any dust 

   build up. This can be done using a vacuum cleaner with the brush attachment. 

   Clean gently around the front grilled section and sides.

• The unit should not be exposed to dripping or splashing and no objects filled 

   with liquids, such as vases, shall be placed on the unit.

BATTERY REPLACEMENT

• Always TURN OFF the A.C. supply to the smoke alarm before replacing the 

   battery. 

• Replace the battery at least once annually, or immediately when the low battery 

   signal sounds once a minute, even though the smoke alarm is receiving A.C. 

   power.

• Test the alarm for correct operation using the test facility, whenever the battery 

   is replaced.

WARNING: DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED.  

THE USE OF BATTERIES OTHER THAN THOSE RECOMMENDED ON THE BACK 

OF THE SMOKE ALARM MAY BE DETRIMENTAL TO ITS OPERATION.

• Gently unlock the detector unit from the base by pushing back the snap lock 

   with a screw driver and turn the alarm unit clockwise to release it. See Figure 5 

   and 6. 

• Remove the battery from the compartment.

• Insert a new, healthy 9V battery. NOTE POLARITY OF CONNECTIONS. Ensure 

   the metal tab is fully depressed when the battery has been fitted.
• Using the Push-to-Test button, test the smoke alarm to verify 9V DC battery 

   back-up. See “TESTING YOUR SMOKE ALARM.”
• Re-attach the smoke alarm to the mounting plate by rotating the alarm unit 

   counter-clockwise until it snaps into place (see Figure 4). 
• Turn on the AC power and test the smoke alarm using the Push-to-Test button. 

   See “TESTING YOUR SMOKE ALARM.”

IMPORTANT SAFETY GUARDS

Installation of your smoke alarm is only one step in your safety plan. Other 

important steps should be taken to further improve your safety:-
• Install the smoke alarm properly, following this instruction leaflet.
• Test your smoke alarm weekly.
• Replace the battery immediately once depleted.
• Do not smoke in bed.
• Keep matches and lighters away from children.
• Store flammable materials in a proper manner and never use them near naked 

   flames or sparks.
• Maintain emergency equipment such as Fire Extinguishers, escape ladders etc 

   and ensure all occupants know how to use them correctly.
• Plan an escape route/s from your building in advance and ensure all occupants 

   are aware of them. Re-enforce this awareness periodically through-out the 

   year.
• Make sure escape routes remain free of any obstructions.
WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE OF AN ALARM IT 

SHOULD BE ASSUMED THAT THE ALARM IS DUE TO AN ACTUAL FIRE AND 

THE DWELLING SHOULD BE EVACUATED IMMEDIATELY.

PHOTOELECTRIC SMOKE ALARM

FOR MODEL: SMAS-P2

PHOTOELECTRIC SMOKE ALARM

FOR MODEL: SMAS-P2

THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF THE 

UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. IF THE 

UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL SUPPLIER WITH 

YOUR PROOF OF PURCHASE.

ADDITIONAL INFORMATION

This is a multiple station photoelectric smoke alarm and can be connected 

  to other alarms of the same make and type. The interconnect feature 

  allows up to 40 units to be connected together over a distance of 150 

  metres maximum, using the single white wire, therefore allowing all alarms 

  to sound when any one is activated.
Note: This smoke alarm cannot be connected to any other device such as a 

fire alarm panel.
• All the Smoke Alarms should be interconnected to ensure the early 

   warning will be heard, particularly by somebody sleeping. A properly 

   designed early warning fire system ensures the alarm is given before the 

   escape routes become blocked with smoke.

SMOKE ALARM WARRANTY

These smoke alarms are warranted to be free from defects in materials and 

workmanships under normal use and service for a period of five years from 

date of purchase. The company will not be obligated to repair or replace 

parts which are found to be in need of repair because of misuse, damage 

or alterations occur after the date of purchase. Send the Smoke Alarm with 

proof of purchase, postage and return postage prepaid, to local distributor. 

The liability of the company arising from the sale of this smoke alarm shall 

not in any case exceed the cost of replacement of smoke alarm and in no 

case shall the company be liable for consequential loss or damages resulting 

from the failure of the smoke alarm.

INS

TALLA

TION INS

TRUCTIONS

GUARANTEE

This product is guaranteed for a period of 5 years from the date of purchase. The guarantee is invalid in the case of 

improper use, tampering, removal of the Q.C. date label, installation in an improper working environment or installation 

not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is also invalidated if the 

luminaire has been Mega tested. Should this product fail during the guarantee period it will be replaced free of charge, 

subject to correct installation and return of the faulty unit. We do not accept responsibility for any installation costs 

associated with the replacement of this product. Your statutory rights are not affected. We reserve the right to alter 

specifications without prior notice.

Red Arrow Trading

Elsworth House, Herries Road South

Sheffield, S6 1QS

T: 0800 195 0006   F: 0870 195 0006 

E: [email protected] 

www.redarrowtrading.com

PHOTOELECTRIC SMOKE ALARM

FOR MODEL: SMAS-P2

RED ARROW TRADING LTD. SHALL HAVE NO LIABILITY FOR 

ANY PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY 

SPECIAL INCIDENTAL, CONTINGENT OR CONSEQUENTIAL 

DAMAGE OF ANY KIND RESULTING FROM A FIRE. THE 

EXCLUSIVE REMEDY FOR BREACH OF THE LIMITED WARRANTY 

CONTAINED HEREIN IS THE REPAIR OR REPLACEMENT OF THE 

DETECTIVE PRODUCT AT GARVAN ENTERPRISES LTD. OPTION. 

IN NO CASE SHALL GARVAN ENTERPRISES LTD.’S LIABILITY 

UNDER ANY OTHER REMEDY PRESCRIBED BY LAW EXCEED THE 

PURCHASE PRICE. YOUR SMOKE ALARMS IS NOT A SUBSTITUTE 

FOR PROPERTY, DISABILITY, LIFE OR OTHER INSURANCE OF 

ANY KIND. APPROPRIATE COVERAGE IS YOUR RESPONSIBILITY. 

CONSULT YOUR INSURANCE AGENT.

This does not affect your statutory rights.

This alarm is only suitable for single occupancy private dwellings 

only and not intended for multi occupancy private dwellings or 

commercial or industrial dwellings.

Waste electrical products should not be disposed of with normal 

household waste. Please recycle where facilities exist. Check 

with your Local Authority or retailer for recycling advice. New 

regulation will encourage the recycling of Waste from Electrical 

and Electronic Equipment (European “WEEE Directive” effective 

August 2005).

KM 638574

BS EN14604:2005

Отзывы: