background image

POLO 15W LED 
Emergency Bulkhead with 
Microwave Sensor 

Installation Instructions p.1

This installation must be carried out by an electrician. 
Please read these instructions carefully before installation. 
Leave a copy for the user/maintenance engineer for future reference.

For models: POL15LEDEMS

Safety

 This is a mains powered product. It is designed to be 

   installed by a qualified electrician and in accordance 
   with the applicable building and electrical 
   regulations. Before installation or maintenance the 
   electrical supply to the product must be isolated. 

Specification

• 

220-240V

• 

15W

• 

66pcs of 2835 LED

• 

1100 Lumen output / 90lm in emergency mode

• 

30,000 Hours life expectancy

• 

4000K Colour temperature

• 

Three years guarantee

• 

Dimensions: Ø: 326 x D: 108mm

Installation Instructions 

 Remove the diffuser & trim from the base by rotating anti-

   clockwise to unlatch then pull away. 

 Loosen the three gear tray retaining screws, rotate the gear 

   tray anti-clockwise to align the screw heads with the large 
   aperture of the keyhole slots & remove the gear tray 
   away from the base. There is a retaining strap to assist with 
   installation. 

 Prepare the mains supply cable & fixing points on the chosen 

   mounting surface ensuring it is able to retain the weight of 
   the luminaire. 

 Pass the mains supply cable through the hole & grommet 

   provided in the base, position the base to the mounting 
   surface & secure using the screws provided. 

 It is the installer’s responsibility to ensure the fixing points 

   & cable entry point are appropriately sealed to maintain 
   the IP54 rating. Silicone bathroom sealant or equivalent is 
   recommended.  

 Route the mains supply cable to the terminal block on the 

   gear tray & terminate ensuring correct polarity is observed. 
   

WARNING: THIS LUMINAIRE MUST BE EARTHED.

 

   It is important that supply cables fitted to luminaires with an 
   electronic ballast do not run adjacent to leads connected to 
   the ballast output terminals so as not to affect radio 
   frequency interference suppression. 

 Secure the supply cable using the clamp provided in the base. 

 Refit the gear tray & secure by retightening the screws. 

 Refit the diffuser & trim by placing over the base & rotating 

   clockwise until it locks into position. 

 Reconnect power supply & check for correct operation. 

   Luminaires fitted with electronic ballasts are exempt from 
   insulation resistance tests as this may cause damage to the 
   ballast. 

Further Instructions for Emergency 

version

 In addition to the above instructions, a secondary “un-

   switched” live supply should be fed to the luminaire, in line 
   with the “switched” mains supply. This “un-switched” supply 
   MUST be taken from the same phase as the “switched” 
   supply & MUST be wired at the switchboard so that upon 
   test, it is isolated at the same time as the “switched” supply.

 Route to the terminal block & terminate, ensuring correct 

   polarity is observed. 

 Connect the battery supply to the module by joining the 

   connectors, ensuring correct polarity is observed. 

Red Arrow Trading

Elsworth House, Herries Road South, Sheffield, S6 1QS

T:

 0800 195 0006     

F:

  0870  043  3946      

E:

 [email protected]      

www.redarrowtrading.com

Description of Microwave Sensor

 The microwave sensor option offers presence 

   detection to provide automatic control of lighting 
   loads. It is installed inside the luminaire so does 
   not affect external aesthetics or the IP Rating. 
   Manual adjustments on the sensor allow it to be 
   individually tailored to suit your application.  

Отзывы: