Repairs
4
record sliding door system 20
Article no. 102-020.110.805
page 9
No. Display text
Type
Res Comments and possible troubleshooting
3
AKI > 60 sec. active
Inside radar longer than 60 sec. active and door remains open.
Check that no moving objects are activating the radar.
Door can be locked with
5
AKA > 60 sec. active
Outside radar longer than 60 sec. active and door remains
open.
Check that no moving objects are activating the radar.
Door can be locked with
6
Unlocking error
X
Unlocking error: it is impossible to unlock the door.
Repeat unlocking attempt after changing the BDE operating
mode.
If door cannot unlock, set it on MANUAL operating mode and
actuate hand unlocking device (if existing) and then select
AUTOMATIC mode, reset hand unlocking device, inform after-
sales service and check locking device.
7
No redundancy test
RED
X
When no „redundancy“ test could happen within the last 24 h or
the „redundancy“ test was not correctly performed on a door
not locked. Reset. Control settings.
9
Battery fuse open
X
Battery fuse is disconnected or battery is not plugged in.
Door works if mains voltage is provided and it is no RED instal-
lation, or rather the parameter „Basic escape route„ is not acti-
vated.
9
Open. unsuccessful
Door does not open or only slowly.
SIO might possibly be active or motion be mechanically hin-
dered (e.g. dirt in floor track).
10
Locking error
Locking error and door remains approx. 10 cm open
de-
pending on parameterising door remains closed.
Door might possibly be hindered or locking device might need
to be adjusted.
11
Difference AKI
RED
X
Error in the interpretation of the inside radar signal. Check
inside radar.
12
Low BAT voltage
X
Battery is missing or is not plugged in.
Door works if mains voltage is provided.
12
BAT capacity
X
Battery not fully powerful anymore.
Replacement by after-sales service. Door goes on working.
13
Redundancy test
RED
Information:
2 test cycles on open door are performed.
14
VAK defective
X
Locking device hampered.
VRR cable might possibly not be connected. Adjust door lea-
ves and locking device.
15
EMERG. OPEN.
RED
On RED installations emergency opening switch has been
actuated.
17
Timeout open. time
RED
X
80% of escape route opening not reached within 3 sec. Control
with FPC, adjust opening speed. Under „Status”, opening time
+ 400 ms.