Страница 1: ...1 Grid connected PV Inverter Three Phase Dual MPPT RCM 4 TP D RCM 5 TP D RCM 6 TP D RCM 8 TP D RCM 10 TP D RCM 12 TP D RCM 15 TP D RCM 17 TP D RCM 20 TP RCM 25 TP D User Manual RECOM TECHNOLOGIES ...
Страница 2: ...2 ...
Страница 3: ...acking List 13 4 Product Installation 13 4 1 Selection of Installation Location 13 4 2 Mounting the Inverter 15 4 3 Electrical Connection 17 4 4 Monitoring Device Installation 22 4 5 RS485 DRED Connection 23 4 6 System Layout of Units without Integrated DC Switch 26 5 Start and Stop 27 5 1 Start Inverter 27 5 2 Stop Inverter 27 6 General Operation 28 6 1 Display Operation 28 6 2 Auto Test 29 7 Tro...
Страница 4: ...ny express or implied declaration or guarantee of the contents of this document Due to product version upgrades or other reasons the contents of this document will be updated periodically Unless otherwise agreed this document serves only as a guide to use and all statements information and recommendations in this document do not constitute any express or implied guarantee RECOM SILLIA SAS Address ...
Страница 5: ...llow the instructions in this manual strictly 2 1 2 Installation operators need to undergo professional training or obtain electrical related professional qualification certificates 2 1 3 When installing do not touch any part of the inner part of the inverter except the terminals 2 1 4 All electrical installations must conform to local electrical safety standards 2 1 5 If the inverter needs mainte...
Страница 6: ...on t follow the local standards and regulations 2 2 10 Products beyond the warranty period 2 3 Important Safety Matters The following symbols may appear in this manual which represent the following meanings Danger Warning Caution Used to warn of urgent dangerous situations if not avoided it could result in death or serious personal injury Description Symbol Used to warn of potentially dangerous si...
Страница 7: ...d of with household waste Description Symbol Please read the instructions carefully before installation Do not touch any internal parts of the inverter until 5 min after being disconnected from the mains and PV input CE mark the inverter complies with the requirements of the applicable CE guidelines Danger Risk of electric shock TUV certification The surface is hot during operation and no touch is...
Страница 8: ...8 Handle with care Description Symbol This side up Keep dry Stacked layers 2 4 3 Symbol on the Packing box ...
Страница 9: ... D RCM 10 TP D RCM 12 TP D RCM 15 TP D RCM 17 TP D RCM 20 TP D RCM 25 TP D 3 1 3 Applicable grid type The applicable grid types for the RECOM RCM 4 25 TP D series are TN S TN C TN C S IT and TT When applied to the TT grid the voltage of N to PE should be less than 30V See Figure 3 1 for details 3 1 4 Storage conditions 1 Inverter must be stored in its original packaging 2 The storage temperature s...
Страница 10: ...e 3 2 Front view Figure 3 3 Side view 3 2 Appearance Introduction 3 2 1 Inverter front view as shown in Figure 3 2 3 2 2 Inverter side view as shown in Figure 3 3 410mm 175mm Name Plate Logo Display 550mm 410mm ...
Страница 11: ...Inverter back view 3 2 3 Inverter bottom view as shown in Figure 3 4 3 2 4 Inverter back view as shown in Figure 3 5 175mm DC Switch Optional Com2 Port Optional DC Input Terminal Back Rail Com1 Port AC Output Terminal Back Rail Vent Valve ...
Страница 12: ...c fault information Off The inverter is running normally Slow flashing The monitoring device is not connected to the router or is not connected to the base station Quick flashing The monitoring device is connected to the router or connected to the base station but not connected to the server 3 OLED Display On Display the inverter operating information Off If the button pressed without any response...
Страница 13: ... wall on which the inverter is mounted must be strong and can withstand the weight of the inverter for a long time 2 The inverter needs to be installed in a well ventilated environment 3 Do not expose the inverter directly to strong sunlight to prevent the power derating due to excessive temperature 4 The inverter should be installed in a place with shelter to prevent direct exposure to sunlight a...
Страница 14: ...ded installation Figure 4 2 Recommended installation space Figure 4 3 Recommended installation angle Do not put flammable and explosive articles around the inverter Warning 500mm 500mm 500mm 500mm 300mm 300mm 300mm 4 1 3 The installation angle of the inverter is recommended as shown in Figure 4 3 Max 30 ...
Страница 15: ...tion Dimensions of wall bracket see Figure 4 4 1 Use the wall bracket as the template to mark the position of 5 holes on the wall See Figure 4 5 for details Figure 4 4 Dimensions of wall bracket Figure 4 5 Mark the hole position 150mm 300mm 150mm 150mm 150mm ...
Страница 16: ... 10mm diameter bit to drill 5 holes on the wall and make sure hole depth is 80mm 3 Insert the expansion tubes into the holes and tighten them then fix the bracket onto the wall with expansion screws by using a cross screwdriver as shown in Figure 4 6 4 2 2 Mounting the inverter Lift up the inverter with both hands hang the back rail on the fixed wall bracket carefully see Figure 4 7 for details Wa...
Страница 17: ...n the conductive part of the inverter may cause an electric shock When performing any installation on the inverter make sure that the AC and DC sides of the inverter are completely de energized Do not ground the positive or negative pole of the PV string otherwise it will cause serious damage to the inverter Static may cause damage to the electronic components of the inverter Anti static measures ...
Страница 18: ...the positive and negative cables into the corresponding positive and negative connectors pull back the cable to ensure that the terminal is tightly attached in the connector 6 Use an open end wrench to screw the nut to the end to ensure that the terminal is well sealed as shown in Figure 4 11 1 Before assembling the DC connector make sure that the cable polarity is correct 2 Use a multimeter to me...
Страница 19: ...the positive and negative connectors into the inverter DC input terminals respectively and a click sound represents the assembly in place as shown in Figure 4 12 4 3 2 Connection of AC output The RECOM RCM 4 25 TP D series three phase inverter applies to the three phase power grid with a voltage of 230 400V and a frequency of 50 60Hz The recommended cable and AC breaker for the RECOM RCM 4 25TP D ...
Страница 20: ... head by following the rules yellow green wire to PE port red or brown fire wires to L ports no requests for the sequence of three fire wires and blue or black wire to the N port Please try to pull out the cable to make sure it s well connected As shown in Figure 4 15 4 According to the arrow direction to push the threaded sleeve to make it connected with the AC terminal head and then rotate the c...
Страница 21: ...onding 5 Connect the AC connector to the inverter AC terminal and rotate the AC connector buckle clockwise until its tight enough As shown in figure 4 17 4 3 3 External ground connection Ground terminal connection steps 1 The external grounding terminal is located in the lower right side of the inverter 2 Fix the grounding terminal to the PE wire with a proper tool and lock the grounding terminal ...
Страница 22: ...d RS485 communication you can choose according to your specific needs Plug the WiFi or GPRS module into the COM1 port in the bottom of inverter by following the direction the side with indicator is up as shown in Figure 4 19 A slight click sound during the installation represents that the assembly is in place Figure 4 18 Grounding terminal connection ...
Страница 23: ...sealed by waterproof plug after replacing Any damages caused by the waterproof plug sealing problem will be invalid of warranty Attention Note 4 5 RS485 DRED Connection 4 5 1 Terminals definition Inverter communication ports are located at the rear of the CT DRED plate at the bottom and include RS485 port used for Meter or Datalogger connection and DRED port as shown in Figure 4 20 Figure 4 20 1 1...
Страница 24: ...to realize the communication 1 RS485 A 2 RS485 B 3 PE NULL Port 3 1 Only DRED version with this port 2 DRED means demand response enable device The AS NZS 4777 2 2015 requires inverters to support demand response mode DRM This function is for inverter that comply with AS NZS4777 2 2015 standard 3 RECOM inverter is fully complied with all DRM The 6pin connector is used for DRM connection 4 Support ...
Страница 25: ...ealing ring insulator metal plate nut and 3 6pin connector as shown in Figure 4 22 3 Insert the cable to the port in the 3 6pin connector and fasten with a screwdriver 4 Insert the 3 6pin connector into the 3 6pin connecter inside the inverter and screw the CT DRED plate back with a cross screwdriver as shown in Figure 4 23 The maximum distance between the inverter at the end of the daisy chain an...
Страница 26: ...ide The DC switch must be able to safely disconnect the open circuit voltage of the PV array plus a safety reserve of 20 Install a DC switch to each PV string to isolate the DC side of the inverter We recommend the following electrical connection 20 25mm 1 3 3 1 2 4 6 2 2 1 3 5 Port 1 Port 2 Port 3 6mm 6mm 20 25mm Screw cap Sealing ring Insulator ring Metal plate 3 6pin connector Nut ...
Страница 27: ...flash and the Waiting message will be displayed on the OLED display 4 After self checking completed the inverter will start generating electricity the green light will remain on and the OLED display will display real time power information 5 2 Stop Inverter When turning off the inverter please follow the steps below 1 Turn off the AC breaker first 2 Wait 30 seconds and then turn the DC switch to t...
Страница 28: ...utomatically save your settings or modifications Short press 1s switch window Long press 3s enter the lower Menu Firmware Updating PV Voltage PV Current Grid Voltage Grid Current Grid Freq E Day Not WiFi E Total H Total Model Name Safety Set WIFI Reload WIFI Reset Fault Info RSSI Setting Export Limit Modbus Addr Setting Setting Feed in Grid Time Set Setting Setting Power Factor Language Set Settin...
Страница 29: ...est order is 59 S1 59 S2 27 S1 81 S2 81 S2 2 Remote set as 1 Local set as 1 then the test order is 59 S1 59 S2 27 S1 81 S1 81 S1 3 Remote set as 0 Local set as 1 then the test order is 59 S1 59 S2 27 S1 81 S2 81 S2 Connect the AC cable auto test will start after the inverter connected to the grid see the operation steps below The auto test will start when the correct test item is selected and the ...
Страница 30: ...f the AC cable is too high to lead the grid voltage increased Change a thicker AC cable if it is Grid Frequency Fault 1 Check whether the safety regulation setting is correct 2 Check the frequency of the grid If the grid frequency exceeds the allowed range of inverter protection parameters please contact the local grid company to resolve ISO Over Limitation 1 Check whether the PV panels cables and...
Страница 31: ...Restart the inverter only after removing the fault that impairs safety performance As the inverter contains no component parts that can be maintained never arbitrarily replace any internal components For any maintenance need please contact RECOM TECHNOLOGIES Otherwise RECOM TECHNOLOGIES shall not be held liable for any damage caused Servicing of the device in accordance with the manual should neve...
Страница 32: ...30 30 30 30 30 30 Max Short circuit Current A 20 20 20 20 20 20 20 20 20 20 20 20 20 40 40 40 40 40 40 40 Backfeed current to the array A 0 0 0 0 0 0 0 0 0 0 AC Output Rated Output Power KW 4 5 6 8 10 12 15 17 20 25 Max Output Power KW 4 4 5 5 6 6 8 8 11 13 2 16 5 18 7 22 25 AC output rated apparent power KVA 4 5 6 8 10 12 15 17 20 25 Max Apparent Power KVA 4 4 5 5 6 6 8 8 11 13 2 16 5 18 7 22 25 ...
Страница 33: ...mperature Protection Integrated Residual Current Protection Integrated Islanding protection Frequency shift Integrated AC Short circuit Protection Integrated AC Over voltage Protection Integrated General Data Dimensions mm 550W 410H 175D Weight kg 23 26 29 Protection Degree IP65 Self consumption at Night W 1 Topology Transformerless Operating Temperature Range C 30 60 Relative Humidity 0 100 Opera...