OPERATION & CONTROL UNIT
Air Handling Unit RT 250/400S-EC-RS
Configuration
6. Configuration - categories - options
This menu is used for the configuration
of the complete AHU.
Choose group of menus - see Ch. A..
To enter this group of menus, log in with access code
.
Line 1 Set control functions.
Line 2 Set parameters for control.
Line 3 PID - controller output.
Line 4 Set fan speeds.
Line 5 Type of additional heating.
Line 6 Parameters for By-pass, Defrost etc.
Line 7 Parameters for recovery of night chill.
Line 8 Times and parameters for recovery of night chill.
Line 9 Parameters for KAVK / Condensation boiler.
Line 10 Configuration of digital inputs and outputs.
Line 11 System setting, made at the factory.
6.1
Control functions
6.1.1
Control functions - options
Choose control functions - see Ch. A.
Options:
•
Supply air control: the temperature is controlled by the supply air sensor alone.
•
Outdoor temperature compensated supply air control: The temperature is controlled as a
function of the supply air with compensation for outdoor air temperature.
•
Cascaded room control: Cascade control of room temperature and supply air temperature to
achieve a constant, settable room temperature. The room controller output signal generates
the supply air controller’s setpoint value.
•
Cascaded exhaust air control: Cascade control of exhaust air temperature and supply air
temperature to achieve a constant, settable room temperature. The exhaust air controller
output signal generates the supply air controller’s setpoint value.
Line 1 Name of menu.
Line 2 Shows chosen control function.
6.1.1.1
Cascaded room temperature control (min/max supply air setpoint)
Min. and max. parameters can be adjusted - see Ch. A.
Line 1 shows menu.
Line 2 shows which parameters can be adjusted.
Line 3 displays set max. value
Line 4 displays set min. value.
Control function
Control temp.
PID output
Fan speeds
Heating coil
By-pass
Cold air recovery
Night cooling
KAVK
I/O configuration
System
Control function
Cascaded room.
When cascade control
Max/min SA setp.
Max: 52.0 °C
Min: 17.0 °C