OPERATION & CONTROL
Ventilation Unit RT 250/400S-EC-RS
a) Supply air control
b) Exhaust air control
c) Room control
d) Outdoor compensated supply air
control
The menu frost protection temperature is only shown when water heating is configured.
Limit for cooling
The default setting is that cooling is not activated until the outside temperature is above +20 degrees. If you want
to change this, set the outdoor temperature at which the cooling can start. There is also an adjustable hysteresis
so that the cooling does not open and close all the time if the temperature is around the set value.
Cont
’d. below
|
|
|
~
€
~
€
Extract air temp.
↑
Actual: 11.5 ºC
↓
~
€
Exhaust air temp.
↑
Actual: 20.1 ºC
↓
Freeze P. temp.
↑
Actual: 8.5 ºC
↓
~
€
|
Cooling limit
↑
Outd. Temp> 20.0˚C
Hysteresis 1.0 ˚C
Cont
’d. from Temperature p. 7 and above
page
|
|
|
}
|
|
}
~
€
Supply air temp
↑
Actual : 25.1 ºC
↓
~
€
~
€
Supply air temp.
↑
livingroom
Actual: 26.5 ºC
~
€
Outdoor air temp.
↑
Actual: 15.5 ºC
↓
Room temp. bedroom
Actual : 19.2 ºC
Setpoint: 19.0 ºC
ECO adjust.: 2 ºC
↓
Room temp livingroom
Actual : 20.6 ºC
Setpoint: 21.0 ºC
ECO adjust.: 2 ºC
↓
e) Zonal room control
Cont
’d. from Temperature p. 7
|
|
}
|
|
|
}
|
|
|
}
|
|
}
|
|
~
€
~
€
~
€
Outdoor comp. Setp.
↑
10 ºC = 18 ºC
15 ºC = 12 ºC
~
€
~
€
Supply air temp
↑
Actual : 25.1 ºC
↓
~
€
Supply air temp
↑
Actual : 25.1 ºC
↓
~
€
~
€
Outdoor comp. Setp.
↑
-5 ºC = 23 ºC
0 ºC = 22 ºC
5 ºC = 20 ºC
↓
~
€
Supply air temp
↑
Actual : 25.1 ºC
↓
~
€
Outdoor air temp.
↑
Actual: 15.5 ºC
↓
~
€
Outdoor air temp.
↑
Actual: 15.5 ºC
↓
~
€
Outdoor air temp.
↑
Actual: 15.5 ºC
↓
|
}
Supply air temp
Actual : 25.1 ºC
Setpoint: 25.0 ºC
↓
Exhaust air temp.
Actual : 20.1 ºC
Setpoint: 20.0 ºC
ECO adjust.: 2 ºC
↓
Room temp.
Actual : 20.1 ºC
Setpoint: 20.0 ºC
ECO adjust.: 2 ºC
↓
OD temp.: 15.5 ºC
Supply air temp.
Act.: 25.1ºC Setp.->
Comp.SP: 12.0 ºC
↓
Outdoor comp. Setp.
-20 ºC = 25 ºC
-15 ºC = 24 ºC
-10 ºC = 23 ºC
↓