460EAV Gateway 

User Guide 

Содержание 460EAV

Страница 1: ...460EAV Gateway User Guide...

Страница 2: ...forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect to use of information circuits equipment or software described in this manual Governmen...

Страница 3: ...guide you will be able to configure the 460EAV Gateway for basic operation You will set the device s network settings and parameters to the proper configuration for initial operation and physically p...

Страница 4: ...ed the following tools The 460EAV Gateway The provided CD ROM A Working PC Windows based The Supplied Ethernet Crossover Cable A 7 30 VDC power source T strip You will also need to verify the followin...

Страница 5: ...ort 0 T strip to be set to RS485 and Power while Port 1 DB 9 is set to RS232 by default If these default port settings are incompatible with your equipment they can be configured differently For assis...

Страница 6: ...C power source to the device via the T strip 2 Using the crossover cable connect the device to the PC If you are connecting through a hub or switch use a standard Ethernet cable 3 Insert the provided...

Страница 7: ...e 1 Open an MS DOS Command Prompt 2 Type ipconfig and press enter 3 Note the IP Address The previous example was 192 168 0 1 4 To test the communication between the PC and the uni type ping in the pro...

Страница 8: ...te parity data bits and stop bit settings of your Modbus RTU slave device in order to complete device configuration 1 If you would like to change the device description click Edit in the Description r...

Страница 9: ...econds 8 Select the appropriate settings in the Connector Mode Baud Parity Data and Stop fields The settings should match your Modbus RTU slave device 9 Click Save to save your configuration 10 Click...

Страница 10: ...Real Time Automation Inc 8 1 800 249 1612 460 Gateway Device Line 460EAV Modbus TCP Server and Ethernet IP Server Settings The Modbus TCP Server and Ethernet IP Server have no configurable settings...

Страница 11: ...ation Parameters 1 On the Main Page in the RTA 460EAV Application Parameters row select Edit 2 Altivar Pass through is enabled by default 3 Select the method you will be using with the Altivar Pass th...

Страница 12: ...Configuration row click Edit 2 Click Add Altivar 31 3 After the page refreshes a preconfigured device module will be displayed below These options can be configured if needed To do so click on the Edi...

Страница 13: ...s 16 regis ters You cannot configure more than 160 registers across all devices for Data In The same limit applies to Data Out 7 For Data In select the type of data to read Coil Status Input Status In...

Страница 14: ...be read written It is not the number of registers 9 For Data Out select the type of data to write Coil Status or Holding Register 10 Enter the starting address of the write and the length of the writ...

Страница 15: ...eway can communicate with a Programmable Logix Controller PLC you must configure the PLC settings to expect to read and or write data from the gateway Use the following information to configure the PL...

Страница 16: ...Real Time Automation Inc 14 1 800 249 1612 460 Gateway Device Line 460EAV For more specific information on configuring the PLC contact Real Time Automation Inc at 800 249 1612 or 262 439 4999...

Страница 17: ...Status and Summary button located on the left hand side of the screen 2 The 460EAV Device Summary and Status page will be shown 3 The device drop down menu allows you to switch between the different d...

Страница 18: ...evice parameters are incorrect the Device Status will display Enabled NOT Connected If you receive this error verify that the devices are connected properly If your Modbus Master settings do not match...

Страница 19: ...croll down to tag 198 for the RTA_460EAV I DATA 3 To check the status of each of the 12 devices on the network look at the last two words 198 and 199 of the Input Assembly Area Each of the 12 devices...

Страница 20: ...t device buffers of the 460EAV where it is exchanged with the EtherNet IP scanner Bytes 320 through 395 are used for pass through messaging PTM PTM is a feature that allows you to send any Modbus comm...

Страница 21: ...95 34 47 Altivar 4 Predefined Altivar 4 I O 96 99 48 49 Additional User Defined Altivar 4 I O 100 127 50 63 Altivar 5 Predefined Altivar 5 I O 128 131 64 65 Additional User Defined Altivar 5 I O 132...

Страница 22: ...ure shows the data read from Altivar drives 1 and 2 The data bytes are routed through the 460EAV and sent to the Ethernet IP Scanner Bytes 4 through 31 are reserved for additional user defined scan li...

Страница 23: ...gisters 1 Data 55 Pass through Response Byte P T Response Word Length 320 321 5 160 Sequence 322 323 1 161 Modbus Message 324 5 162 High Byte 325 3 162 Low Byte 326 2 163 High Byte 327 328 55 163 Low...

Страница 24: ...ta Users can look at the data in these registers to monitor the status of all 10 Altivar devices For this example Altivar devices 4 and 7 may be mapped but are shown as not connected 0000 1110110111 1...

Страница 25: ...page click the Utilities button 2 Click Save Configuration to File 3 Click Save 4 Browse to the location you want to save the file 5 Click OK 6 Remove the first device 7 Repeat the network configurati...

Страница 26: ...floor or other operating environment 1 Disconnect the crossover cable and power supply from the device 2 Move the device to its intended location 3 Connect an Ethernet cable from the network port on t...

Страница 27: ...making a change disconnect the power cable and any communications cables from the Gateway unit 3 Remove the two small Phillips head screws from each long side of the Gateway unit 4 Remove the green T...

Страница 28: ...3 4 5 Pin Setting GND CANL SHIELD CANH PWR Port 1 DB 9 RS485 1 2 3 4 5 6 7 8 9 Pin Setting NC TX NC NC GND NC TX NC NC NC No connection Port 0 T Strip CAN 1 2 3 4 5 Pin Setting GND CANL SHIELD CANH P...

Страница 29: ...Real Time Automation Inc 150 South Sunny Slope Road Suite 130 Brookfield WI 53005 Local 262 439 4999 Toll free 1 800 249 1612 www rtaautomation com support rtaautomation com...