FIELD WIRING TERMINATION
7.1
Terminal & Connector Layout
CHANNEL
TERMINAL
DESCRIPTION
1 TC+
2 TC-
3 -
1
4 -
CHANNEL
TERMINAL
DESCRIPTION
5 TC+
6 TC-
7 -
2
8 -
CHANNEL
TERMINAL
DESCRIPTION
9 -
10 -
11 TC-
3
12 TC+
CHANNEL
TERMINAL
DESCRIPTION
13 -
14 -
15 TC-
4
16 TC+
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
(
-
: not connected)
7.2
Wiring Schematic
TC+
TC-
Thermocouple
ICENI/AI-03
7.3
Earthing / Grounding
The metal terminal rail to which the Iceni node is attached should be connected to a
‘clean’ earth / ground point. In many applications this would be the chassis of the
product.
It is recommended that screened thermocouple cable is used, with the screen
connected to a ‘clean’ earth / ground point at the Iceni node end only. This might be
via the terminal rail, for example.