RCS ZC2S Скачать руководство пользователя страница 7

 DCN: 141-00240-02  7/03 

SW1-1  TEST MODE 

OFF = NORMAL OPERATION

 

ON = TEST MODE- ALL DELAYS CANCELED 

 

1

 

1

 

SW1-2  FAN MODE SELECT 

OFF = Gas Systems.   NO fan w/heat   
 
ON = Electric Systems. Fan w/heat 

 
 

DAMPERS 

FUSE 

2 ZONE HVAC CONTROLLER

 

MODEL:  ZC2S 

PN: 001-00240

 

ZC2S REV E 

NORMAL1 

STD FAN 2 

EQ OFF 3 



 

TEST MODE 
F/HEAT 
ERT1 
ERT2 
HRT1 
HRT2

 

SW1

 

OFF - ON

 

2AG 

2A

 

STATUS LED  
1 FLASH = OK 
2 FLASH = EQ ON 
3 FLASH = SCP ON

 

ZONE1

 

ZONE2

 

FAN

 

HEAT

 

COMP

 

• 

For Standard Thermostats 

• 

For Standard HVAC Systems 

• 

One Stage Heat, One Stage Cool 

• 

Thermal Equalizer

 Feature 

WIRING  DIAGRAM 

Standard 

Thermostats 

Motorized  Dampers 

Normally Open 

24VAC 

Two Position 

Spring Return 

SW1 DIP SWITCH SETTINGS 

REV E 

RCS 

OPTIONAL 

POWER TO 

STATS

 

24V    C 
24V    R 

FAN    G 
HEAT W 

COMP Y 

24V    C 
24V    R 

FAN    G 
HEAT W 

COMP Y 

ZONE 1

 

ZONE2 

24V    C
24V    R

FAN    G

 HEAT   W

COMP    Y

75

 

24V    C 
24V    R 

FAN    G 

   HEAT   W 

COMP    Y 

75

 

24V COM 
R 24V 
G  FAN 
W HEAT 
Y  COMP 

HVAC SYSTEM 

C 24V COM  
R   24V 
G   FAN 
W  HEAT  
Y   COMP 

Standard 

HVAC System 

Outdoor 

Compressor 


RESET 

STATUS LED:

 The status LED shows normal operation by flashing slowly.  If the Status LED is not flashing, check power/fuse. 

Two flashes indicate that the Equalizer run cycle is on.  Three flashes indicate that the Short cycle protection is on. 

 

SHORT CYCLE PROTECTION (SCP) DELAY.

  The control unit protects the compressor from short cycling by a 5 minute delay at 

the end of every compressor “run” cycle.  The Status LED will flash rapidly three times to indicate SCP delay is active. 

Zone 1 
Com 
Zone 2  
Com 

SW1- 3 & 4  EQUALIZER MODE SELECTION 

Equalizer OFF 

Equalizer Run Time = 6 Min 

Equalizer Run Time = 8 Min

 

Equalizer Run Time = 10 Min

 


4

 

3
4

 

3
4

 

3
4

 

SW1-5 & 6 HEAT RUN TIME SELECTION  

Heat Run Time = 8 Min 

Heat Run Time = 12 Min 

Heat Run Time = 16 Min

 

Heat Run Time = 20 Min

 

5
6

 

5
6

 

5
6

 

5
6

 

Note:  There is a 2 Min Minimum 
Heat Run Time (MHRT).  If the 
Heat Call is terminated during this 
period, no Equalizer cycle will be 
started at the end of the call.   If 
the Heat Call last longer than the 
MHRT, but less than 8 Min, then 
an Equalizer cycle will be started 
at the end of the call. 

Dipswitch Settings: 

Содержание ZC2S

Страница 1: ...RCS MODEL ZC2S 2 ZONE HVAC CONTROL UNIT INSTALLATION AND OPERATION MANUAL DCN 141 00240 02 7 25 03 ...

Страница 2: ... are either battery operated or that use both sides of the 24VAC power they have R and C terminals from the HVAC system DO NOT USE POWER STEALING THERMOSTATS Typically these thermostats steal power from the W or Heat connection on the HVAC system THESE WILL NOT WORK WITH THE ZC2S ZONE CONTROL UNIT It is also recommended that you do not use older style mechanical thermostats that use anticipator ci...

Страница 3: ...ne This equalizer cycle will reduce the heat buildup upstairs and put the heat back downstairs where it is still needed The net effect is a more comfortable temperature in the upstairs zone and an energy saving reuse of the excess heat in the downstairs zone The Thermal Equalizer feature monitors Zone 1 for heat run times and this zone must be the downstairs zone When the Thermal Equalizer cycle i...

Страница 4: ... 18 gauge thermostat wire for the dampers Power ZC2S Control Units are powered from the HVAC system s 24VAC R and C common terminals No external transformer is required Total damper draw must be limited to 1 Amp per zone Fuse The controller is supplied with a 2AG style 2 Amp fuse Thermostat Wiring Connect the zone thermostats to their respective zone input terminals J1 J2 Both the 24VAC Common C a...

Страница 5: ...e Select Select OFF for Standard Gas systems no fan with heat calls Select ON for Electric Heating systems fan with heat calls SW1 Position 3 4 Thermal Equalizer Mode Select These two dipswitch positions determine the length of time the equalizer cycle will run after it has been tripped on by the Heat Run Time timeout C 24VAC COM R 24VAC G FAN W HEAT Y COMP R 24VAC G FAN W HEAT Y COMPRESSOR RED GR...

Страница 6: ...ermine the length of time that a Zone 1 Heat Call can be on before it times out and is interrupted by an equalizer cycle OFF ON 5 Off Heat Run Time 8 Min 6 Off 5 On Heat Run Time 12 Min 6 Off 5 Off Heat Run Time 16 Min 6 On 5 On Heat Run Time 20 Min 6 On SW1 FIG 5 DIPSWITCH SW1 EQUALIZER HEAT RUN TIME SETTINGS HRT1 HRT2 ...

Страница 7: ...MP Standard HVAC System Outdoor Compressor C Y RESET STATUS LED The status LED shows normal operation by flashing slowly If the Status LED is not flashing check power fuse Two flashes indicate that the Equalizer run cycle is on Three flashes indicate that the Short cycle protection is on SHORT CYCLE PROTECTION SCP DELAY The control unit protects the compressor from short cycling by a 5 minute dela...

Отзывы: