DCN: 141-01652-07 4/30/09
26
Installer Settings Summary
Setting
Range
Default
Display Lock
Y or N
N
Locks out front buttons
F/C Mode
C or F
F
Screen Timeout
0, 20-120
0
seconds
Schedule Enable
Y or N
N
Max heat setpoint
50F-90F (4C-32C)
90F (32C)
Min cool setpoint
55F-99F(10C-37C)
55F (10C)
Min Run Time (MRT)
1 – 9
3
Min Off Time (MOT)
5 – 9
5
Mechanical - Type
Std or HP
Std
Mechanical - Fan Type
Gas or Elec
Gas
Mechanical - C/O Type
w/Heat or w/Cool
w/Cool
Mechanical - 2
nd
Stage Heat
Y or N
N
Mechanical - Aux Heat
Y or N
Y
Mechanical - 2
nd
Stage Cool
Y or N
N
Filter Interval
300
Maint Interval
3000
H/C Delta
3 – 15
3
Heat Delta Stage 1 On
1 – 8
1
Heat Delta Stage 1 Off
0 – 8
0
Heat Delta Stage 2 On
1 – 8
2
Heat Delta Stage 2 Off
0 – 8
0
Heat Delta Stage 3 On
1 – 8
3
Heat Delta Stage 3 Off
0 – 8
0
Cool Delta Stage 1 On
1 – 8
1
Cool Delta Stage 1 Off
0 – 8
0
Cool Delta Stage 2 On
1 – 8
2
Cool Delta Stage 2 Off
0 – 8
0
Fan Cycler ON time
0 – 120
0
0 = Fan Cycler OFF
Fan Cycler Off Time
10 – 120
10