TROUBLESHOOTING 

SYMPTOM 

CAUSE 

CURE 

Sensor fails to add to the 
network (slow blinking of the 
Status LED and no pairing 
action seen on the bridge) 

Out of range 

Add a Z-Wave repeating device (e.g. light module/dimmer) at a location between the bridge and 
the sensor.   
1. Add a repeater to the network 

following that device’s instructions.

2. Try to add the sensor to the network again at the desired sensing location.

Improperly removed from 

network previously 

1. Remove the sensor from the network following the steps in the “REMOVE” table.
2. Try to Add the sensor to the network again.

Sensor drops connection 
intermittently 

Edge of range 

Add a Z-Wave repeating device (e.g. light module/dimmer) at a location between the bridge and 
sensor.  

FACTORY RESET 

Factory Reset should only be used when the primary controller is missing or otherwise inoperable. 

ASSOCIATION GROUP INFORMATION TABLE

 

Group 

Profile 

Command Classes 

Group Name 

Max Devices 

Lifeline 

Battery Report, Multilevel Sensor Report, Device Reset 
Locally Notification 

Lifeline 

Sensor 

Multilevel Sensor Report 

Temperature Reports 

Sensor 

Multilevel Sensor Report 

Humidity Reports 

Sensor 

Basic Set 

Temperature Driven Basic Sets 

Sensor 

Basic Set 

Humidity Driven Basic Sets 

Sensor 

Battery Report 

Battery Reports 

Z-WAVE CONFIGURATION TABLE

Parameter 

Description 

Length 

(Bytes) 

R/W 

Default 

Value 

Valid Values 

Time between Battery Reports (hours) 

R/W 

Range: 1

–127 hours 

0 = Do not send periodically 

Send BASIC SET ON above this temperature  (See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET ON below this temperature  (See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET OFF above this temperature  (See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send BASIC SET OFF below this temperature  (See #20) 

R/W 

121 

Range: 15° 

– 120° F 

121 = Disabled 

Send multiple attempts for all BASIC SET commands 

R/W 

1-5 = Number of extra attempts sent every minute after
first send 
0 = Disabled

Temperature Units 

R/W 

1 = Fahrenheit 
0 = Celsius 

Association Group1 

– Temperature delta auto send threshold 

R/W 

10 

Range: 1 - 200 
Parameter is in tenths of degrees. 

Association Group1 

– Periodic temperature send interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

10 

Association Group2 

– Temperature delta auto send threshold 

R/W 

10 

Range: 1 - 50  
0 = Disabled 
Parameter is in tenths of degrees. 

11 

Association Group2 

– Periodic temperature send interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

12 

Send BASIC SET ON above this humidity  
(See #20) 

R/W 

Range: 1

–100% 

0 = Disabled 

13 

Send BASIC SET ON below this  humidity  (See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

14 

Send BASIC SET OFF above this  humidity  (See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

15 

Send BASIC SET OFF below this  humidity  (See #20) 

R/W 

Range: 1-100% 
0 = Disabled 

16 

Association Group1 

– Humidity delta auto send threshold 

R/W 

1-50%

17 

Association Group1 

– Periodic humidity send interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

18 

Association Group3 

– Humidity delta auto send threshold 

R/W 

Range: 1-30% 
0 = Disabled 

19 

Association Group3 

– Periodic humidity send interval 

R/W 

Range: 1-120 minutes 
0 = Disabled 

20 

BASIC SET options for temperature and humidity 

R/W 

Configuration Register Combinations: 
1 = Enable Registers 2, 5, 12 15 
2 = Enable Registers 2, 5, 13, 14 
3 = Enable Registers 3, 4, 12, 15 
4 = Enable Registers 3, 4, 13, 14 

21 

Temperature Offset 

R/W 

Range: -7° to 7° F 

22 

Humidity Offset 

R/W 

Range: -7% to 7% 

23 

Humidity Filter Time Constant 

R/W 

30 

Range: 1 

– 60 minutes 

PN: 1

40-02312 Rev A