Installer Settings Summary 
 

Setting 

Range 

Default 

 

Display Lock 

Y or N 

Locks out front buttons 

Service Mode Submenu 

 

 

 

   Test Mode 

Y or N 

Reduces delays for testing 

System Settings Submenu 

 

 

 

Mechanical Settings Submenu 

 

 

 

   Sys Type 

Std or HP 

Std 

 

   Fan Type 

Gas or Elec 

Gas 

 

   C/O Type 

w/Heat or w/Cool 

w/Cool 

 

   2

nd

 Stage Heat 

Y or N 

 

   Aux Heat 

Y or N 

 

    2

nd

 Stage Cool 

Y or N 

 

H/C Delta 

– 15 deg 

 

Heat Delta Stage 1 On 

– 8 

 

Heat Delta Stage 1 Off 

– 8 

 

Heat Delta Stage 2 On 

– 8 

 

Heat Delta Stage 2 Off 

– 8 

 

Heat Delta Stage 3 On 

– 8 

 

Heat Delta Stage 3 Off 

– 8 

 

Cool Delta Stage 1 On 

– 8 

 

Cool Delta Stage 1 Off 

– 8 

 

Cool Delta Stage 2 On 

– 8 

 

Cool Delta Stage 2 Off 

– 8 

 

Max Heat SP 

40-109F (4-42C) 

90F 

 

Min Cool SP 

44-113F (6-45C) 

60F 

 

Min Run Time 

1-9 min 

 

Min Off Time 

1-9 min 

 

Temp Response 

1-6 

 

Fan Cycler Submenu 

 

 

 

   Fan Cycler ON time 

– 120 min 

0 = Fan Cycler OFF 

   Fan Cycler Off Time 

10 

– 120 min 

10 

 

Remote Sensors Submenu 

 

 

 

   RS1 Type (curve type) 

Curve A, Type 2, Type 3 

Type 3 

 

   RS2 Type (curve type) 

Curve A, Type 2, Type 3 

Type 3 

 

   RS2 Location (Indoors or Outdoors) 

In, Out 

In 

 

   R1 Node ID (Zwave node address) 

0-252 

 

   R2 Node ID (Zwave node address) 

0-252 

 

 

 

 

 

Restore Defaults (factory defaults) 

Yes or No 

No 

Exit = no 

 

 

 

 

USER SETTINGS 

 

 

 

Filter Service Submenu 

 

 

 

   Service Interval 

Disabled, 100-4000 hrs 

300 

 

Maint Service Submenu 

 

 

 

   Maint Interval 

Disabled, 100-4000 hrs 

3000 

 

Screen Timeout (to minimized screen) 

0, 20-120 sec 

0 = off , will not timeout  

F/C Mode 

F or C  

 

Sensor Calibration Submenu 

Internal -7 to +7 

 

Backlite/Display Submenu 

 

 

 

   Backlight Timeout 

0, 20-120 

0 = backlite off 

   Backlight On Brightness 

0-100% 

100% 

 

   Backlight Off Brightness 

0-100% 

0% 

 

   Contrast 

0-20 

14 

 

 

 

 

 

 

 

 

 

Содержание TZ45R

Страница 1: ...o them below Standard HVAC System Wiring Terminal Marking Meaning Typical Wire Color May be different Take a picture Record the old thermostat wire color that was connected to the terminal C 24VAC Com...

Страница 2: ...dard systems Ignore this setting 4 2nd Stage Heat Enable second stage heating outputs If you have a single stage heating system leave this set to N If you have a 2 stage heating system set to Y to ena...

Страница 3: ...ts W2 O terminal The setting of the C O Type will set the correct system operation For change over with cool systems Orange wire O terminal set C O type to w cool most common and default setting For c...

Страница 4: ...ust be changed to match Go to the Installer Settings Menu to complete the HVAC setup Installer Settings Menu To change the HVAC setup go to the Installer Settings Menu This is a hidden menu and it can...

Страница 5: ...ric heat Default Gas C O Type if Type HP Selects the Changeover Valve type for Heat Pump systems Options w Cool or w Heat Default w Cool For retrofit installations refer to the existing thermostat con...

Страница 6: ...em delays CAUTION in test mode all system safety delays are shorten Do not operate the system compressor in test mode Disconnect Y1 or Y2 outputs if using test mode on a live system System Settings Su...

Страница 7: ...delta from setpoint that stage 2 cooling starts Options 1 to 8 degrees Default 2 Cooling Delta Stage 2 OFF Sets the delta from setpoint that stage 2 Cooling stops Stage 2 turns off at setpoint Delta...

Страница 8: ...installed location as indoor sensor or outdoor sensor Options IN indoor or OUT outdoor Default IN R1 Node ID Selects the node ID for a remote Z Wave temp sensor to be used as RS1 Options 0 252 Default...

Страница 9: ...in Cool SP 44 113F 6 45C 60F Min Run Time 1 9 min 3 Min Off Time 1 9 min 5 Temp Response 1 6 2 Fan Cycler Submenu Fan Cycler ON time 0 120 min 0 0 Fan Cycler OFF Fan Cycler Off Time 10 120 min 10 Remo...

Страница 10: ...SYS OFF ECON HOLD NO MSG Temperature Setting Warmer Cooler Fan Mode Selection Heating Cooling Mode Selection Run Hold Mode Selection Menu Selection Room Temperature Setpoints Backlite Display Main The...

Страница 11: ...if you try to lower the cooling setpoint below the heating setpoint It maintains a 3 degree separation between the heating and cooling setpoint The same is true for raising the heating setpoint above...

Страница 12: ...Emergency Heat will be displayed if the HVAC system type is set to Heat Pump If there is a compressor failure with the Heat Pump system setting the mode to EHEAT will allow the supplemental Aux heat...

Страница 13: ...cooling HEAT MRT 2 displayed System is ON and heating Minimum Run Time MRT delay off is active COOL MRT displayed System is ON and cooling Minimum Run Time MRT delay off is active Staging display 2nd...

Страница 14: ...ermostat Provides for local schedule control The Schedules Screen allows you to review and set the setback schedule for the thermostat The thermostat has a 4 x 7 schedule Four times a day can be selec...

Страница 15: ...To copy a days schedule to another day or group of days move the cursor to C on the bottom right of the schedule screen When you highlight the c the button below will become Copy Press this button to...

Страница 16: ...reminder that the HVAC system may require periodic maintenance Pressing the Menu button will take you to the Filter Service screen The Reset button can be pressed and the HEAT and COOL Runtime values...

Страница 17: ...splay Typically 10 15 is a good setting Adjust as needed Away Setpoints Away setpoints are used when the thermostat is set to the setback or away mode ZWave Install This menu item allows you to instal...

Страница 18: ...OFF will cancel the MRT and the system will turn off immediately The MRT can be adjusted in the Installer Settings menu of the thermostat Note The MRT status is shown in the thermostat System Status o...

Страница 19: ...temperature RS1 X Use RS1 sensor for room temperature Internal sensor not used RS2 X X Average internal sensor with RS2 sensor and use the average for room temperature RS1 and RS2 X X Average RS1 and...

Страница 20: ...ork use the Z Wave Install procedure Note Before adding the thermostat to a Z Wave Network check that it does not already belong to one by viewing the Node ID ZNID located in the Thermostat Info scree...

Страница 21: ...uipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equ...

Отзывы: