![RCI 1012 Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/rci/1012/1012_installation-instructions_1424038002.webp)
Fig. 1
No Relay Model
in
10" x 10" x 4" deep enclosure.
NOTE:
-
Maintain a minimum clearance of
1/4” between power limited and
non-power limited circuits.
- We recommend that all connected
devices be UL Listed.
- Prior to using battery back-up,
check with AHJ to ensure code
compliance.
- All Class I wiring into the unit
must meet ANSI/NFPA 70.
©2011 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM
USA: 2517 SQUADRON COURT, SUITE 104, VIRGINIA BEACH, VA 23453
•
CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6
PHONE
•
1.800.265.6630
•
519.621.7651
•
FAX: 1.800.482.9795
•
519.621.7939
•
E-MAIL: [email protected]
10 Series Power Supply Installation Instructions
(Continued)
VOLTAGE
ADJUST
HEAT SINK
WARNING
HOT TO TOUCH
TB1
Factory
Power limited
Class II wiring
AC main input
non-power limited
Class I wiring
TRANSFORMER
12 OR 24 VOLTS
L
N
+
- Lock Power
Outputs are Class II
PDD-FT
TRANSFORMER
12 OR 24 VOLTS
VOLTAGE
ADJUST
HEAT SINK
WARNING
HOT TO TOUCH
Factory
Power limited
Class II wiring
AC main input
non-power limited
Class I wiring
Outputs are Class II
See separate PDD-FT
application diagrams
L
N
Fig. 2
Fire Panel Disconnect Model
in 10" x 10" x 4" deep enclosure
NOTE:
-
Maintain a minimum clearance of
1/4” between power limited and
non-power limited circuits.
- We recommend that all connected
devices be UL Listed.
- Lock output relays on PDD-FT
are separately energized
- Prior to using battery back-up,
check with AHJ to ensure code
compliance.
- Wiring from the Fire Panel Interface
Module to be in accoradance with
NFPA 101, Section 7.6.1.6.2.
- All Class I wiring into the unit
must meet ANSI/NFPA 70.
- Building codes require free egress.