Troubleshooting Guide

Problem

Solution

- Check AC and DC LED’s on power 

supply board. Both should be on for 
proper operation AC ON –GREEN, 
Trouble: Normal – AMBER, DC ON - RED.

- If LED’s are not on, check AC power.

- Disconnect AC power, battery(s) and all 

connected equipment IMMEDIATELY.

- Change voltage selection switch to 

desired voltage.

- Reconnect equipment and reapply

AC power.

-Check battery voltage.

No DC output from terminals.

Output voltage is not correct for the con-
nected equipment.

Trouble output relay is de-energized. (Relay
terminals are labeled shown in the Normal,
energized, “no trouble” condition. Relays are
energized when no trouble is detected.

Supervision

Form “C” AC fail relay output 2A @ 120VAC

Form “C” battery trouble relay output 2A @ 120VAC

Internal battery cut-off relay to protect batteries from deep discharge 9.8VDC & 19.6VDC

Enclosure tamper switch for connection to a UL approved burglary panel when used in 
UL 603 applications

Environmental

For indoor use only

Operating temperature -0˚C to 49˚C - (32˚F to 120˚F)

Maintenance

Under normal conditions the power supply should be checked for proper operation on an
annual basis

Check output voltage

It is also recommended that the current draw is checked to ensure that the current is 
within specifications. Check battery voltage. Under normal  conditions the battery will 
last approximately 4-5 years. If battery backup is critical it is recommended to change 

the battery every 4 years or less. 

For Technical Support:

1-800-265-6630 or 519-621-7651  www.rutherfordcontrols.com

©2011 RUTHERFORD CONTROLS INT’L CORP. • WWW.RUTHERFORDCONTROLS.COM

USA: 2517 SQUADRON COURT, SUITE 104, VIRGINIA BEACH, VA 23453

CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON  N1T 1J6 

PHONE:1.800.265.6630 • 519.621.7651 • FAX: 519.621.7939 • E-MAIL: [email protected]

Отзывы: