LCD Series Finned Copper Tube Gas Boilers & Water Heaters – Boiler Manual

24

GAS SUPPLY PIPING

  Check the boiler/water heater rating plate to make 

sure that the boiler/water heater is for the type of gas 

that will be used. If it isn’t, do not connect the boiler/

water heater to the gas supply. Gas supply piping must 

be in accordance with the National Fuel code, ANSI 

Z223.1-latest revision or applicable provisions of the 

local building codes. Canadian installations must 

comply with CAN/CGA B149.1 or .2 Installation 

Code. Failure to comply with this warning can result 

in extensive property damage, severe personal injury 

or death!

The LCD comes from the factory ready to be piped to the gas 

supply. If for any reason the boiler/water heater is not for the type 

of gas available at the installation site, call your RBI Water Heaters 

representative to resolve the problem.

  A minimum gas supply pressure of 

7 in

178 mm

WC natural or 

11 in

279 mm

 WC propane and 

maximum 

14 in

356 mm

 WC natural or propane, 

must be available at the safety shutoff valve inlet with 

the unit(s) operating. 

Table 10 should be used to ensure that the gas supply piping is 

sized properly. If more than one appliance is supplied by the same 

supply pipe, the piping must be sized based on the maximum possible 

demand. Do not neglect the pressure drop due to pipe fittings. Table 

10 should be used in conjunction with Table 11 to ensure that the 

gas supply piping has the capacity to meet the demand.
Figure 16 depicts the proper way to connect the boiler/  

water heater to the gas supply piping. The manual shut-off valve 

must be installed in the supply piping. It should be installed 

5 ft

1.5 m

 above the floor where required by local codes. Provide a 

sediment trap at the bottom of the vertical section of the gas supply 

pipe upstream of the gas controls.
A ground joint union should be installed between the boiler gas 

controls and the supply piping. Each of these items are needed to 

ensure long life and ease of servicing. Always use a pipe sealant that 

is suitable for use with LP gas.

Table 10  Gas pipe capacity

Maximum pipe capacity in ft

3

/hr based on 0.60 specific gravity gas

at a pressure of 0.5 psig or less and a 0.3" WC pressure drop. 

Nominal

Iron Pipe

Size

Pipe length in feet

10

20

30

40

50

60

80

100

150

Maximum gas volume of pipe, (ft

3

/hr)

3/4"

278

190

152

130

115

105

90

79

64

1"

520

350

285

245

215

195

170

150

120

1 1/4"

1050 730

590

500

440

400

350

305

250

1 1/2"

1600 1100 890

760

670

610

530

460

380

2"

3050 2100 1650 1450 1270 1150 990

870

710

2 1/2"

4800 3300 2700 2300 2000 1850 1600 1400 1130

3"

8500 5900 4700 4100 3600 3250 2800 2500 2000

Note:   Multiply the gas volume by 0.62 for propane flow capacity in ft

3

/hr.

Multiply the propane flow capacity by 2500 Btu/ft

3

 to determine

the propane Btu/hr capacity for a given pipe size and length.

Table 11  Equivalent pipe length chart

Nominal

Iron Pipe

Size

Type of pipe fitting

90˚ Elbow

Tee

1

Gate Valve

2

Gas Cock

2

Equivalent pipe length, (ft)

1"

2.6

5.2

0.6

1.5

1 1/4"

3.5

6.9

0.8

1.9

1 1/2"

4.0

8.0

0.9

2.3

2"

5.2

10.3

1.2

3.0

2 1/2"

6.2

12.3

1.4

3.7

3"

7.7

15.3

1.8

4.5

Notes: 

1. For flow through branch.

 

2. For flow at full open.

  Always use a wrench on the gas valve body when 

making gas connections to it. Never over-tighten the 

piping entering the gas valve body or gas valve failure 

may result!

Figure 16 

Gas supply piping

When applicable, provisions for vent, bleed and gas relief lines must 

be made in accordance with the latest revision of ANSI Z223.1/

NFPA 54.
Safe lighting and other performance criteria were met with the gas 

manifold and control assembly provided on the boiler. All gas 

connections MUST be leak tested before putting the boiler into 

operation.

  Never use an open flame to test for gas leaks. Always 

use an approved leak detection method. Failure to 

comply with this warning can cause extensive property 

damage, severe personal injury or death!

Whenever the gas supply piping is pressure tested the boiler/water 

heater gas controls must be protected. If the test pressure is equal 

to, or less than 

1/2 psig

3.5 kPa

 isolate the boiler/water heater 

by closing it's manual shut off valve, see Figure 

16. If the test 

pressure is greater than, or equal to 

1/2 psig

3.5 kPa

, disconnect 

the boiler/water heater and its individual shut-off valve.

Содержание LCD OMINATOR Series

Страница 1: ...ion dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be opera...

Страница 2: ...allation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 If the information in this manual is not followed exactly afireorexplosionmayresul...

Страница 3: ...heater is level from front to back and from side to side Use metal shims to level the boiler water heater Electrical and electronic components must also be protected from exposure to water during oper...

Страница 4: ...onmentsubjectedto anegativepressureunlesstheairintakeisconnectedto the outdoors Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or...

Страница 5: ...Vertical venting using a masonry chimney system and inside air Figure 3 Horizontal venting using inside air 305 TO 457 127 TO 254 VENT PIPE DIAMETER 5 TO 10 12 TO 18 MINIMUM VERTICAL RISE OFF THE TOP...

Страница 6: ...not less than 1 in2 per 7 000 Btuh 310 mm2 per kW up to and including 1 million Btuh plus 1 in2 per 14 000 Btuh 155 mm2 per kW in excess of 1 million Btuh Intake Air Option General Guidelines This co...

Страница 7: ...r single or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates doubl...

Страница 8: ...n air and venting metal chimney system shown Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Figure 7 Combination air intake and venting masonry chimney...

Страница 9: ...follow the instructions provided with the barometric damper Check with local codes for specific requirements In Canada B149 7 25 Draft Regulators states the damper shall be of double acting type To a...

Страница 10: ...ce of 2 ft 61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended abo...

Страница 11: ...0 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertica...

Страница 12: ...porch deck or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the cur...

Страница 13: ...f 1 4 in ft 20 mm m On masonry chimneys the connector must terminate flush with the inside of the chimney flue Figure 2 Fasten each single wall vent connection with at least 3 corrosion resistant shee...

Страница 14: ...horizontal vent systems should be as short and straight as possible Whenhorizontalventrunsexceed5ft 1 5mtheymustbesupported at3 ft 0 9 mintervalswithoverheadhangers Theventsystemmust be pitched down t...

Страница 15: ...nclinaisonhorizontalequiconviennent ets assurerquelesyst meestexemptd obstruction d tranglement de fruite de corrosion et autres d faillances qui pourraient pr senter des risques c Insofar as is pract...

Страница 16: ...er piping of this boiler water heater will void themanufacturer swarrantyandcancauseboilerfailure resulting in flooding and extensive property damage Excessivewaterhardnesscausingscalinginthecopper he...

Страница 17: ...piping Figure 10 Relief valve piping Never install any type of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property damage severe personal injury or death may...

Страница 18: ...mp is sized to overcome the headlossoftheboilerandnear boilerpipingsystemwhilesupplying theflowraterequiredtomaintainthedesiredtemperatureriseacross the boiler heat exchanger The system pump is sized...

Страница 19: ...adjust to lower desired temperature above Temp Min 4 Check after system operating temperature has stabilized Make final adjustments 5 Follow same adjustment procedure for sealed combustion H 3 Rev 6 N...

Страница 20: ...gh unit 2 Boiler pump sized to boiler design flow requirements 3 All boilers furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secon...

Страница 21: ...between 8 and 18 and by maintaining the pH between 5 and 9 Follow the conditions listed underNORMALinthetable Insomeareasofthecountryadditional precautions must be observed due to unusual characterist...

Страница 22: ...LCD Series Finned Copper Tube Gas Boilers Water Heaters Boiler Manual 22 Table 9A LCD Heat exchanger selection graph Table 9B LCD Pumping performance requirement...

Страница 23: ...oint 10 A thermostatic mixing valve may be required at the outlet of the tank in order to limit the mixed water to a desirable temperature helping to prevent scalding and injury Consult local codes No...

Страница 24: ...e with LP gas Table 10 Gas pipe capacity Maximum pipe capacity in ft3 hr based on 0 60 specific gravity gas at a pressure of 0 5 psig or less and a 0 3 WC pressure drop Nominal Iron Pipe Size Pipe len...

Страница 25: ...erstand the instructionscontainedinthismanual Donotattempt to operate this boiler water heater if it has not been installed in accordance with the guidelines set forth in this manual Failure to comply...

Страница 26: ...condition A single pressure switch is used on the standard models One low fire and one high fire pressure switch is used when the two stage option is employed The low fire pressure switch serves to s...

Страница 27: ...l The blower s pump s and optional power venter will remain on during this time 5 On CSD 1 equipped units the blower s and optional power venter will shut down and the boiler water heater will lock if...

Страница 28: ...n attempt then begin the ignitionprocessdescribedinstep3above TheFSMwillcontinue to cycle the unit through steps 3 4 and 6 until the unit lights or the demand for heat is removed Main Burner Once the...

Страница 29: ...n voisin Suives les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur appelez le service de incendies C Do not use this appliance if any part has been under water Immediately call...

Страница 30: ...witches for proper operation before placing boiler on line LP Nat Minimum in WC 11 7 Maximum in WC 14 14 Measure pressure when the boiler is firing at full rate Low gas pressurecouldindicateundersized...

Страница 31: ...hat the gas piping is fully purged of air Inspect the ignition system and ensure that it is operating properly 2 Totesttheignitionsafetyshutoffdevice closethemanualshutoff valve in the gas supply line...

Страница 32: ...t pressure and counter clockwise to decrease it 5 Replace the pressure regulator adjustment screw cap Gas Pressure Adjustment The maximum inlet gas pressure listed on the rating plate must not be exce...

Страница 33: ...the water outlet piping to prevent the boiler waterheaterfromfiringwithoutadequatewaterflowthrough the heat exchanger Low Water Cutoff If the boiler is to be installed above radiation or if required b...

Страница 34: ...tioncomponentsarefreefromdust soot dirt corrosionorother deposits that would impair the boiler water heater s performance Refer to page 39 for component identification Burner Inspection And Removal Fi...

Страница 35: ...ide the heat exchanger out of the unit 10 Remove the V baffle straps and V baffles 11 Thoroughly inspect the heat exchanger for signs of damage If there is no damage clean the heat exchanger with wate...

Страница 36: ...charge water at normal system pressure this may be due to thermal expansion in a closed water supply system If it does contact a qualified service technician to have it inspected NEVER try to clean or...

Страница 37: ...Power venter interlock not wired 1 Wire power venter interlock as shown in connection diagram 6 No Power To Blower s 1 Blower s not plugged in 2 Defective blower timer TD3 3 Blower s malfunctioning 1...

Страница 38: ...ol set too low 1 Increase control temperature setting 11 Unit Consistently Shuts Down On High Limit 1 High limit set to low 1 Increase high limit setting 12 Bad Combustion High CO Yellow Flames 1 Insu...

Страница 39: ...LCD Series Finned Copper Tube Gas Boilers Water Heaters Boiler Manual 39 Figure 23 Exploded view REPAIR PARTS...

Страница 40: ...0 10 12 12 14 14 Manning Glass Tape per ft 66 0105 4 6 8 14 14 16 16 18 18 PVC Gasket Foam per ft per roll 50 66 0103 50 50 50 50 50 50 50 50 50 2 Blanket Insulation per sq ft 05 0200 20 22 24 30 34 3...

Страница 41: ...0 1 70 3091 1 70 3092 1 29 Main Orifice NG 10 0087 7 9 13 15 10 0130 17 19 23 27 Main Orifice LP 10 0088 7 9 13 15 17 19 23 27 Main Orifice NG 10 0115 5 Main Orifice LP 10 0116 5 NS Pilot Orifice NG 1...

Страница 42: ...Headers 70 3003R 1 70 3004R 1 70 3006R 1 70 3007R 1 70 2832R 1 70 2833R 1 70 2834R 1 70 2835R 1 Heat Exchanger Assembly Copper 70 3024R 1 Bronze Headers 70 3025R 1 70 3026R 1 70 3028R 1 70 3029R 1 70...

Страница 43: ...65 1 70 3066 1 70 3067 1 70 3069 1 70 3070 1 70 2917 1 70 2918 1 70 2919 1 70 2920 1 NS Heat Exchanger V Baffles 03 2011 36 03 2012 7 36 03 2013 7 03 2014 7 03 2016 14 03 2017 18 18 03 2019 18 34 Hold...

Страница 44: ...44 High Limit LB 14 0009 1 1 1 1 1 1 1 1 1 High Limit LW 14 0008 1 1 1 1 1 1 1 1 1 NS High Limit Well 3 8 x 3 13 0104 1 1 1 1 1 1 1 1 1 NS Operator LB 14 0007 1 1 1 1 1 1 1 1 1 Operator LW 14 0010 1 1...

Страница 45: ...r LW 13 0302 2 2 2 2 2 1 1 1 1 NS Flow Switch 14 0203 1 1 1 1 1 1 1 1 1 Flow Switch Outdoor 14 0205 1 1 1 1 1 1 1 1 1 Flow Switch Potter 14 0201 1 1 1 1 1 1 1 1 1 Flow Switch Outdoor Potter 14 0202 1...

Страница 46: ...nt Termination Hood 14 09 0141 1 1 1 NS Air Intake Hood 6 09 0102 1 Air Intake Hood 8 09 0103 1 1 Air Intake Hood 10 09 0104 1 Air Intake Hood 12 09 0105 1 1 1 1 1 NS Barometric Damper 6 09 0405 1 Bar...

Страница 47: ...PROPER SERVICE CLEARANCE PROVIDED IS VENT VERTICAL THROUGH THE ROOF OUTDOOR AIR SENSOR INSTALLED WIRED IS VENT THROUGH THE WALL ARE UNITS RACKED IS POWER VENT INSTALLED AND WIRED IS RACK ASSEMBLED TI...

Страница 48: ...ckout CSD 1 Pump Delay Combustion Air Damper Power Vent Proving Switch Barometric Damper COMMISSIONING THE UNIT Customer Instructed Yes No All Covers Replaced Yes No Wiring Secure Tight Yes No Custome...

Страница 49: ...inal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIO...

Страница 50: ...arranty Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instr...

Страница 51: ...LCD Series Finned Copper Tube Gas Boilers Water Heaters Boiler Manual 51...

Страница 52: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 833 265 5371 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwaterheaters com...

Отзывы: