background image

FIII-STARTUP REV 1.0 

TESTING MODULATING BOILER CONTROL 

Remove jumpers from the AA and T1 terminals.  Allow the boiler to control itself through the Modulating Boiler 
Control.  Check sticker on the inside of the door or the Installation Manual for instructions on using the boiler 
control.

BOIL TARGET 

BOIL MIN 

START MODULATION 

MODE

FIRE DELAY 

MIN MODULATION 

TANK TARGET (MODE 3) 

BOIL MASS 

DLY

TANK DIFF (MODE 3) 

DIFF

UNITS

BOIL MAX 

MOTOR SPEED 

SAFETY TESTS CHECKLIST 

FLOW SWITCH 
LOW WATER CUTOFF 

AIR SWITCH 
HIGH-LIMIT

COMMISSIONING THE BOILER/WATER HEATER 

UNIT CYCLED MIN. OF 15 TIMES
CUSTOMER INSTRUCTED 
ALL COVERS REPLACED 
CUSTOMER GIVEN MANUAL 
TARGET TEMP. SET PER CUSTOMER 

COMMISSIONED BY: _____________________________ 
 

 

 

 

 

      (SIGNATURE) 

DATE: ___________________ 

THE DELTA T BETWEEN THE HEATERS INLET 
AND OUTLET IS CRITICAL TO PROPER FLOW. 
BEFORE YOU LEAVE THE JOB SITE YOU 
MUST RECORD THE DELTA T. THIS READING 
SHOULD NOT EXCEED 

35°F

19.4°C

, OR BE 

LOWER THEN 

20°F

11.1°C

INLET TEMPERATURE 

OUTLET TEMPERATURE 

ADDITIONAL NOTES AND COMMENTS 

38

Содержание FUTERA III Series

Страница 1: ...m WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammab...

Страница 2: ...tion et l entretien doivent tre assur s par un installateur ou un service d entretien qualifi ou par le fournisseur de gaz The Futera III Series finned copper heating boiler water heaters have been de...

Страница 3: ...tion of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater in a location that would subject it to temperatures at o...

Страница 4: ...o the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized per Table 2 Ta...

Страница 5: ...take air terminal must terminate as shown in Figure 3 The penetration point in the roof must be properly flashed and sealed Intake Air Option Horizontal Guidelines The maximum equivalent length for th...

Страница 6: ...Horizontal vent systems shall terminate at least 4 ft 1 2 m below 4 ft 1 2 m horizontally from or 1 ft 0 30 m above any door window or gravity air inlet into any building It must not terminate less t...

Страница 7: ...d combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wall or insulated inlet pipe recomm...

Страница 8: ...AND OPERATION INSTRUCTIONS Figure 3 Vertical Air Intake and Venting for Direct Vent System Figure 4 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Страница 9: ...E CATEGORY IV In this configuration the boiler water heater blower is used to push the flue products horizontally to the outdoors see Figure 5 The air for combustion is taken from the space in which t...

Страница 10: ...onry chimney When using a listed metal chimney system use the appropriate vent connector The vent connector should be sloped up toward the chimney at a minimum rate of 1 4 in ft 21 mm m On masonry chi...

Страница 11: ...tion commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse maximale Ne pas faire fonc...

Страница 12: ...REQUIREMENTS CAUTION Improper piping of this boiler water heater will void the manufacturer s warranty and can cause boiler failure resulting in flooding and extensive property damage Excessive water...

Страница 13: ...thru 1000 2 NPT 2 NPT 1250 thru 2000 2 1 2 NPT 2 1 2 NPT Pump Requirements This low mass boiler requires a continuous minimum water flow for proper operation The system pump must be sized to overcome...

Страница 14: ...ated pump is used to maintain a constant water flow through the boiler This secondary pump is sized to overcome the head loss of the boiler and secondary piping system while supplying the flow rate re...

Страница 15: ...ntain Inlet Temperature Above Dew Point T1 Temp Min 110 For Atmospheric T1 Temp Min 125 Sealed Combustion NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2...

Страница 16: ...obe Valve Balance Valve Backflow Prevention Device 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units NOTES 1 Boiler circuit piping must be sized large...

Страница 17: ...excessive corrosion of the heat exchanger Water that has a hardness greater than 18 grains per gallon and or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump siz...

Страница 18: ...changer Selection Graph Table 8B Futera III Pumping Performance Requirement To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed Pro...

Страница 19: ...g the warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting...

Страница 20: ...e remote aquastat well in lower 1 3 of tank Install aquastat with heat sensing compound 3 Thermal expansion tank may be required check local codes 4 When using optional factory mounted pump max pipe l...

Страница 21: ...e type of gas that will be used If it isn t do not connect the boiler water heater to the gas supply Gas supply piping must be in accordance with the National Fuel Code ANSI Z223 1 latest revision or...

Страница 22: ...ions GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attempt to operate this boiler water heater if it has not been installed in...

Страница 23: ...voisin Suives les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur appelez le service de incendies C Do not use this appliance if any part has been under water Immediately call...

Страница 24: ...lumage 14 R glez la pression de la veilleuse tel qu indiqu la section V RIFICATION ET R GLAGES 15 Commutez nouveau le Honeywell 7895C en mode marche 10 Monitor the flame current on the Honeywell Burne...

Страница 25: ...ot gas manual valves in the closed position energize the unit Observe the trial for ignition to confirm that the spark is strong and continuous If not check and adjust the spark gap as shown in Figure...

Страница 26: ...ion control too high can result in scalding resulting in severe personal injury High Limit Aquastat The high limit is located in the top control area of the boiler water heater A remote capillary bulb...

Страница 27: ...ns off the control keeps the boiler pump running for the time selected This setting allows purging of any excess heat out of the boiler after the boiler is shut off When PMP DLY is set to OFF there is...

Страница 28: ...perly Also check to see if the sensor is shorted or open using an ohmmeter MAINTENANCE WARNING Disconnect electrical power and close the manual gas shut off valve before performing maintenance or seve...

Страница 29: ...water heater is returned to service 8 Replace the heat exchanger and other components in the reverse order of their removal Air Intake Vent System Thoroughly inspect the air intake and vent systems f...

Страница 30: ...ove setpoint temperature Lockout gas pressure is displayed with a call for heat Ensure that the manual main gas valve is open Ensure that there is sufficient gas pressure supplying the boiler Check pr...

Страница 31: ...31 FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS Figure 18 Exploded View RIOM 20 REV B SEE VIEW A SEE VIEW B 15C 15B SEE VIEW C...

Страница 32: ...32 FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS VIEW B ROTATED VIEW 16 18 VIEW A VIEW C RIOM 37 REV B...

Страница 33: ...Gas Train Support Bracket Assembly 70 2344 1 1 70 2345 1 1 1 70 2346 1 1 15 Burner 10 0280 1 10 0309 1 10 0308 1 10 0286 1 10 0288 1 10 0290 1 10 0292 1 15a Burner Gasket 06 0026 1 1 1 06 0027 1 1 1 1...

Страница 34: ...412 1 1 1 70 2413 1 1 1 1 28 Upper Rear Panel 70 2414 1 1 1 70 2415 1 1 1 1 29 Rear Pipe Enclosure Assembly 70 2333 1 1 1 70 2334 1 1 1 1 30 Lower Rear Jacket Panel 03 2822 1 03 2823 1 03 2824 1 03 28...

Страница 35: ...Heat Exchanger Cupronickel 70 2193 1 70 2194 1 70 2195 1 70 2196 1 70 2197 1 70 2198 1 70 2199 1 47 Air Damper Assembly 70 2351 1 1 1 70 2353 1 1 70 2354 1 1 48 High Limit L4008E MB 14 0112 1 1 1 1 1...

Страница 36: ...043 1 1 1 06 0044 1 1 1 1 61 Relay 2P 15 0107 1 1 1 2 2 2 2 NS Stainless Steel Wipes 66 0050 1 1 1 1 1 1 1 NS Rating Plate 82 0054 1 1 1 1 1 1 1 NS Paint 66 0013 1 1 1 1 1 1 1 NS Silicone 66 0151 1 1...

Страница 37: ...right of the electrical panel on the control relay board Also locate the gas pressure tapping upstream of the main gas valve 1 Create head demand jumper the T1 terminals on the control board 2 With g...

Страница 38: ...TS BOIL MAX MOTOR SPEED SAFETY TESTS CHECKLIST FLOW SWITCH LOW WATER CUTOFF AIR SWITCH HIGH LIMIT COMMISSIONING THE BOILER WATER HEATER UNIT CYCLED MIN OF 15 TIMES CUSTOMER INSTRUCTED ALL COVERS REPLA...

Страница 39: ...39 FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS...

Страница 40: ...260 North Elm Street 1300 Midway Boulevard Westfield MA 01085 Mississauga Ontario L5T 2G8 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwaterheaters com...

Отзывы: