81
11.14 - Vertical
termination –
Concentric vent
11.14.1 - Description and
usage
Both combustion air and vent pipes
must attach to the termination kit. The
termination kit must terminate outside
the structure and must be installed as
shown in Figure 11-25.
11.14.2 - Determine
location
Locate the vent/air terminations using
the following guidelines:
1. The total length of piping for vent or
air must not exceed the limits given
in Section 11.4.
2. The concentric terminal must
terminate at least 3 feet above the
highest place in which the vent
penetrates the roof and at least 2
feet above any part of a building
within 10 horizontal feet.
3. Locate termination so it is not likely
to be damaged by foreign objects,
such as stones or balls, or subject
to buildup of leaves or sediment.
4. Cut one (1) hole into the structure
to install the termination kit.
5. Install the Concentric vent kit
following the concentric kit
manufacturer’s instruction.
NOTICE!
Ensure termination location
clearance dimensions are as shown in
Figures 11-25 and 11-26.
NOTICE!
Ensure termination height is
above the roof surface or anticipated
snow level (12 inches in U.S.A. or 18
inches in Canada) as shown in Figure
11-25.
CAUTION!!!
DO NOT use fi eld-
supplied couplings to extend
pipes. Airfl ow restriction
will occur and may cause
intermittent operation.
6. Operate the appliance one (1) heat
cycle to ensure combustion air and
vent pipes are properly connected
to the concentric vent termination
connections.
11.14.3 - Vertical
termination installation
1. Determine the best location for the
termination kit (see Figure 11-26).
2. The total length of piping for vent or
air must not exceed the limits given
in Section 11.4.
3. You must consider the surroundings
when terminating the vent and air:
a. Position the vent termination
where vapors will not damage
nearby shrubs, plants or air
conditioning equipment or be
objectionable.
b. The
fl
ue products will form
a noticeable plume as they
condense in cold air. Avoid areas
where the plume could obstruct
window views.
c. Prevailing winds could cause
freezing of condensate and
water/ice buildup where
fl
ue
products impinge on building
surfaces or plants.
d. Avoid possibility of accidental
contact of
fl
ue products with
people or animals
e. Do not terminate above any door
or window. Condensate can
freeze, causing ice formations.
f. Locate or guard vent to prevent
condensate damage to exterior
fi
nishes.
11 - INSTALLATION - Vent and combustion air
Figure 11-25 Concentric vertical
terminations
Vent
Combustion
air intake
Minimum clearance above snow
level (18” for Canada) Maximum
24” above roof or snow level)
Vent
Support
(
fi
eld supplied)
(18” for Canada)
Minimum
clearance above
highest anticipated
snow level.
Maximum of 24”
above roof.
Vent
Combustion
Air
Roof boot /
fl
ashing
(
fi
eld supplied)
Combustion
Air
Combustion
Air
Figure 11-26 Concentric vertical
terminations
Содержание Boiler
Страница 3: ...3 SAFETY INSTRUCTIONS ...
Страница 5: ...5 SAFETY INSTRUCTIONS ...
Страница 56: ...56 10 INSTALLATION Electrical connections Figure 10 4 Electrical customer connection for IB boilers ...
Страница 122: ...122 15 MAINTENANCE ...
Страница 126: ...126 17 SPARE PARTS Spare parts ...
Страница 129: ...129 17 SPARE PARTS 50 48 50 49 53 56 57 55 54 58 47 52 48 52 51 55 52 020010 03 006 199 ...
Страница 152: ...20 SEQUENCE OF OPERATION for BOILER ...
Страница 153: ...21 SEQUENCE OF OPERATION for WATER HEATER ...