![RBH Access Technologies UNC100 Скачать руководство пользователя страница 3](http://html.mh-extra.com/html/rbh-access-technologies/unc100/unc100_manual_792244003.webp)
Panel LEDs
LED1 (Red)
LED2 (Green)
LED3 (Red)
FUNCTION
Receive
Transmit
Host
OFF Host not polling Panel not responding
Power is off
ON SOLID
Malfunction
Malfunction
Online
BLINKING
Receiving
Transmitting
Offline
Cycle power for DIP-switch changes to take effect!
To
12 VDC 7 Ah
Rechargeable Battery
0VDC @ 2A
+12VDC @ 2A
PS-1224
Power
Supply
BAT. TEST
Press “BAT. TEST” button
on PS-1224 for battery test,
Yellow LED will go ON if
test failed
16.5V
AC 40V
a
16.5V
AC 40V
a
Green LED
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
Switch
1
2
3
4
5
Panel
1
On
Panel
2
On
Panel
3
On On
Panel
4
On
Switch
1
2
3
4
5
Panel
9
On
On
Panel
10
On
On
Panel
11
On On
On
Panel
12
On On
Switch
1
2
3
4
5
Panel
13
On
On On
Panel
14
On On On
Panel
15
On On On On
Panel
16
On
Switch
1
2
3
4
5
Panel
5
On
On
Panel
6
On On
Panel
7
On On On
Panel
8
On
Switch
6
7
9.6 K
19.2 K On
38.4 K
On
56 K On On
Switch 8: Always OFF!
THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS
Panel LEDs
Power Supply (PS-1224) LEDs
DIP SWITCH SETTINGS : DIP-Switch: UP = ON / DOWN = OFF
LED
On
Off
Green LED
Power On
Power Off
Red LED
Shorted
OK
Yellow LED Battery Fail Battery OK
For Support Call :
01386 425810
All software and hardware manuals are included
!
on
Axiom Lite
software CD in “Documents” folder
Web site : www.rbh
securitygroup
.com E-mail : support
.uk
@rbh-access.com
URC-200
2
Universal
R
eader
C
ontroller
with ENCL1 enclosure
and PS-1224 power supply
Communications
Shielding
Refer to hardware
manual
Reader Color code
Refer to reader manual
Output
1
Lock Door “B”
Output
2
(100mA
max.)
Output
3
Lock Door “B”
Output
4
(100mA
max.)
URC-2000-4
P2
Outputs
URxxxxxxx
LED3
LED1 LED2
JP1- RS-485
Termination
JP2
JP3
All jumpers off, change
only with tech support!
RS-485 BIAS
158
FIRMWARE
Use
Axiom Lite
software
to check firmware
version
Verify it matches
your software, up/
downgrade as needed
via Frmware Upgrade
Utility
RX TX
A+
B-
GND
1 C 2
N.O. N.C. COM 0V
20-22 AWG
Twisted,
Shielded Pair.
4,000’ Max.
Relay
Output 1
5A@30V
Relay
Output 3
5A@30V
RTE
“A”- Request to Exit
DC
“A”- Door contact
DIAG
LED BUZ D0 D1 A 0V 12V
LED BUZ D0 D1 A 0V 12V
N.O. N.C. COM 0V
3 C 4
-12V
D+ D-
+12V
P4
Reader A
P5
Reader B
P7
Outputs
P3
Inputs
P6
Inputs
RTE
“B”- Request to Exit
DC
“B”- Door contact
Lock
Power
12-24 VDC
+
-
P1
RS
48
5
12v
0v
+
-
P9
Exp. Bus
URC controlers in RBH-URC-2004 get addressed individually, con-
nect via RS-485 on P1 for both panels.
iButton
URC-2000-4
URxxxxxxx
LED3
LED1 LED2
RX TX
Serial #
A+
B-
GND
DIAG
-12V
D+ D-
+12V
P1
RS
48
5
12v
0v
+
-
P9
Exp. Bus
Model #
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
URC-2004 contains 2 URC-2000-4 boards
Link up to 16 panels via RS-485
Add up to 4 ELV8 out-
put boards in Elevator
Control Configuration
(RBH-URC-2008)
See LED function
table below
Lock
Diode 1N4004
White stripe to +
+
-
Lock
Belden 9538 cable for readers and Belden 8723 cable for data between panels