![RBH Access Technologies UNC100 Скачать руководство пользователя страница 1](http://html.mh-extra.com/html/rbh-access-technologies/unc100/unc100_manual_792244001.webp)
1 2 3 4 5 6 7 8
TX RX
A+
FG
B-
Input 1(RTE)
C
Input 2 (DC)
RTE
“A”- Request to Exit
DC
“A” - Door contact
RTE
“B”- Request to Exit
DC
“B” - Door contact
Input 3
C
Input 4
Reader B
GRN
BUZ
D0
D1
S
0V
12V
LED
(For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
Reader A
LED
(For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
GRN
BUZ
D0
D1
S
0V
+12V
1NO 1NC 1C 2OC
Output
1
Lock “A”
Output
2
Output
3
Lock “B”
Output
4
Lock
Lock
Power Supply
12-24 VDC
-
+
0V IN [email protected] A
+V OUT 12V@500 mA
THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS
Panel LEDs
Run
Trouble
Host Comm
TX
RX
Function
Heartbeat
Trouble
Com to
software
RS-485
transmitting
RS-485
receiving
Off Malfunction
Normal
No com
No com
No com
Solid Malfunction
Trouble
No Com
Malfunction
Malfunction
Blinking
Normal
Trouble
Red/Green =
Normal
Normal
Normal
Panel LEDs
Cycle power for DIP-switch changes to take effect!
Switch 1
2
3
4
5
Panel
1
On
Panel
2
On
Panel
3
On On
Panel
4
On
Switch 1
2
3
4
5
Panel
9
On
On
Panel
10
On
On
Panel
11
On On
On
Panel
12
On On
Switch 1
2
3
4
5
Panel
13
On
On On
Panel
14
On On On
Panel
15
On On On On
Panel
16
On
Switch 1
2
3
4
5
Panel
5
On
On
Panel
6
On On
Panel
7
On On On
Panel
8
On
Switch 6
7
9.6 K
38.4 K On
57.6K
On
115.2 K On On
Switch 8: Always OFF!
DIP SWITCH SETTINGS : DIP-Switch: UP = ON / DOWN = OFF
Lock
Lock
Power Supply
12-24 VDC
+
-
Link up to 1
5 additional
panels
via RS-485
Belden 8723
20-22 AWG Twisted,
Shielded Pair. 4,000’ Max
To 12 VDC 7 Ah UL Listed
Rechargeable Battery (REQUIRED)
0VDC @ 2A
+12VDC @ 2A
PS-1224 Power Supply
BA
T. TEST
16.5VAC 40Va
16.5VAC 40Va
Press “BAT. TEST” button on
PS-1224 for battery test, Yellow
LED will go ON if test failed
Power Supply (PS-1224) LEDs
LED
On
Off
Green LED
Power On
Power Off
Red LED
Shorted
OK
Yellow LED Battery Fail Battery OK
For Support Call :
01386 425810
All software and hardware manuals are included
on software DVD in “Documents” folder
!
Web site : www.rbh
securitygroup.com
E-mail : support
.uk
@rbh-access.com
UNC100
U
niversal
N
etwork
C
ontroller
with ENCL1 enclosure
and PS-1224 power supply
RUN
TROUBLE
HOST COM
CANADA
ETHERNET
PoE
RS-485
(max 100ma)
LOCK 1
3NO 3NC 3C 4OC
(max 100ma)
LOCK 2
Firmware, use Axiom Lite
software to check
firmware version.
Verify it matches your
software, up/downgrade
as needed via firmware
upgrade utility.
REMEMBER TO REMOVE THE PAPER FROM THE BATTERY CONTACT PRIOR TO INSTALLATION
Belden 9538 20-22 AWG
8 core screened for
readers.
Belden 9538 20-22 AWG
8 core screened for
readers.