8
GETTING STARTED QUICKLY
WARNINGS!
BEFORE OPERATING THIS OR ANY OTHER TEST EQUIPMENT READ ALL SAFETY
WARNINGS AND UNDERSTAND THEM FULLY.
DO NOT VARY INPUT VOLTAGE (MAINS) AFTER POWERING ON TEST SET.
The T-Rex and TR-Spy or Mark II auto-senses the input (mains) voltage from 100 TO 250 vac
50/60 Hz. The TR-
Spy then “locks–in” the test voltage range. If the input voltage (mains) is
varied after the TR-Spy was powered on the actual test voltage may be higher or lower than
indicated and damage to the test set may result.
CONNECTION:
6
–
0
Connection of the T-Rex to the TR-Spy, Mark II is straight forward and relatively easy.
1. Connect the two short Red leads from the H & X connectors located on the top, right side of
the T-
Rex (marked “TO TURNS RATIO SPY”) to the H & X connectors on the TR
-Spy or
Mark II.
2. Connect the 25 pin Interface cable from the connector located on the middle- right side of the
T-
Rex (marked “TO TR SPY”) to the Printer port of the TR
-Spy or Mark II.
3. Connect the Power Interface cable from the connector located on the bottom- right side of
the T-
Rex (marked “POWER OUTPUT”) to the Power connector of the TR
-Spy or Mark II.
4. Connect the multi-colored test lead cables that were supplied with the TR-Spy or Mark II to
the respective connectors, H & X, located on the top, left side of the T-
Rex (marked “TO
TEST OBJECT”). The clip lead end would then be connected to the respectiv
e connections
on the transformer under test (Note: The long Red extension cables may be used, if required).
Basically, this connection is performed as if a standard ratio test was to be made.
5. Connect the power cord supplied with the TR-Spy or Mark II to t
he “POWER INPUT” of the
T-Rex. Plug the power cord into a grounded 100
–
250 vac outlet.