Catalog No.: 2000.205D
Effective: 1-1-08
Replaces: 4-1-05
Raytherm - Type H
Hydronic Heating Boilers - Indoor
Model
K
(C)
INDOOR
DRAFT
38"
13-1/4"
GAS
CONNECTION
26-1/2"
10-1/4
3-7/8
3-7/8
26-1/2"
40"
21-1/4"
ELECT.
CONN
STACKLESS
OUTDOOR TOP
PUMP
(OPTIONAL)
PUMP COVER
(OPTIONAL)
J
3/4 NPT
GAS CONNECTION
(OUTDOOR
MODELS ONLY)
11"
Dimensions (Inches)
Shipping Weight
(Lbs.) – Approx.
Model
No.
MBTU
Input
MBTU
Output
AFUE*
(%)
Width
A
Height
C
J
Flue Dia.
K
No Pump
w/ Pump
H-182 181 148 82.6 18-1/4
62-5/8 12-1/16
6
191
221
H-260 264 216 82.7 22-3/8
62-7/8 11-1/8
7
214
244
H-330
334 274 N/A
25-3/4
63-3/4 10-3/4
8
234
264
H-400
399 327 N/A
29-1/4
65-3/8 12-1/2
9
253
283
* With Vent Damper
NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each
1,000 feet above sea level.
BOILER RATE OF FLOW AND PRESSURE DROP
10°
∆
T
20°
∆
T
30°
∆
T
Model
No.
GPM
∆
P FT
GPM
∆
P FT
GPM
∆
P FT
H-182 30 4.2 N/A N/A N/A N/A
H-260 43 8.5 22 2.2 N/A N/A
H-330 N/A N/A 27 3.4 N/A N/A
H-400
N/A N/A 33 5.2 22 2.3
N/A – Not Applicable
Raypak, Inc.
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300
Fax (800) 872-9725
www.raypak.com