35
EXTERNAL INPUT SIGNAL –
Selects external input
signal range (0-10VDC or 2-10VDC):
0-10VDC or 0-20 mA external input signal –
When
the 0-10VDC signal is selected, an input voltage of 1
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 1 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table O). If a volt-
age below 0.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal call for heat. A 0-20 mA
signal can be converted to a 0-10 VDC signal by
installing a 500 Ω resistor on the external input signal
device’s terminals.
2-10VDC or 4-20 mA external input signal –
When
the 2-10VDC signal is selected, an input voltage of 2
VDC corresponds to a boiler target temperature of
50°F (10°C). An input voltage of 10 VDC corresponds
to a boiler target temperature of 220°F (104°C). As the
voltage varies between 2 VDC and 10 VDC, the boiler
target temperature varies linearly between 50°F
(10°C) and 220°F (104°C) (refer to Table P). If a volt-
age below 1.5 VDC is received, the boiler target
temperature is displayed as “– – –” indicating that
there is no longer an internal call for heat. A 4-20 mA
signal can be converted to a 2-10 VDC signal by
Water Heater (WH1)
Item
Modes
Default Setting
Range
Boil Target
2
140°F
OFF, 70 to 190°F
3, 7
160°F
OFF, 70 to 190°F
Boil Max
2, 3, 6, 7
180°F
OFF, 120 to 190°F
Boil Min
2, 3, 7
135°F
OFF, 80 to 180°F
‘Burner’ Delay
All
0:00 min
0:00 to 3:00 min
Boil Mass
All
1 (Low)
1 (Low), 2 (Med), 3 (High)
Diff
2, 3, 7
Auto
Auto, 2 to 42°F
DHW Target
3
120°F
OFF, 70 to 190°F
DHW Diff
3
5°F
2 to 10°F
‘Pump’ Dly
All
3:00 min
OFF, 0:20 to 9:55 min, ON
Units
All
°F
°F or °C
Mode
N/A
3
2, 3, 7
External Input Signal
7
2 to 10 VDC
2 to 10 VDC or 0 to 10 VDC
Offset
7
0°F
-10°F to 10°F
Table S: Modulating Temperature Control Default Setpoints—Water Heater
installing a 500 Ω resistor on the external input signal
device’s terminals.
FP
- Flame proof warning.
MODE
- Operating mode of the heater.
OFFSET
- The Offset setting allows the boiler target
temperature to be fine tuned to the external input sig-
nal. The control reads the external input signal and
converts this to a boiler target temperature. The Offset
setting is then added to the boiler target temperature.
OUTDR
- Outdoor air temperature.
OUTDR DESIGN
- Design outdoor air temperature
used in the heat loss calculation.
OUTDR START
- Starting outdoor air temperature.
PUMP DLY
- Sets the operating time of the pump once
the CFH is satisfied.
TANK
- Current DHW tank temperature (Mode 3).
TANK DIFF
- Storage tank differential (Mode 3).
TANK TARGET
- Target temperature in the DHW
storage tank (Mode 3).