Catalog No.: 2000.451E
Effective: 11-15-07
Replaces: 1-1-07
Hi Delta – Type H
Models 992BE-2342BE, 87% Efficiency
Model
SPECIFICATIONS
Approx.
MBTUH
Firing
A
H
K
T
W
Amp.
Shipping
Model Input Output Stages Width NPT
Draw* Wt.
(Lbs.)
992BE 990
861
3
57-1/8
2-1/2
10 10
16-13/16
<12
900
1262BE 1260 1096
4
68-1/2 2-1/2
12 10
20-9/16
<12 1010
1532BE 1530 1331
4
79-7/8 2-1/2
12 10
24-3/8
<12 1225
1802BE 1800 1566
4
91-1/8 2-1/2
14 10
28-1/8
<12 1350
2002BE 1999 1739
4
102-1/2 2-1/2
14 10
31-15/16
<12 1450
2072BE 2070 1801
4
102-1/2 2-1/2
14 10
31-15/16
<12 1450
2342BE 2340 2036
4
113-7/8 2-1/2
16 10
35-11/16
<12 1520
Dimensions are in inches.
* Without pump
RATES OF FLOW AND PRESSURE DROPS
20°F
∆
T
30°F
∆
T
Min. Flow
Max. Flow
Model GPM
∆
P (ft) GPM
∆
P (ft) GPM
∆
P (ft)
∆
T GPM
∆
P (ft)
∆
T
992BE
86
6.0
57
2.7
43 1.6 40
132
14.0
13
1262BE
110
10.7 73 4.9 55 2.8 40 132 15.5 17
1532BE
132
16.5
89 7.6 67 4.4 40 132 16.5 20
1802BE
N/A
N/A
104
11.6 78 6.5 40 132 18.0 24
2002BE
N/A
N/A 116
15.1 87 8.7 40 132 19.5 26
2072BE
N/A
N/A
120
16.2 90 9.3 40 132 19.5 27
2342BE
N/A
N/A
N/A
N/A 102 13.0 40 132 21.0 31
Basis is 30 GPM or 40°F
∆
T for minimum flow, 132 GPM for maximum flow.
NOTE: Pump location
varies based on model
and application.
NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.
2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC.
Raypak, Inc.
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300
Fax (800) 872-9725