background image

Catalog No.:  2000.313A 

Effective:  11-15-07   

Replaces:  8-15-07 

Hi Delta FlexGas – Type H 

Models 992BD-2342BD 

Model 

           

 

 
 

 

SPECIFICATIONS 

 

 

 

 

 

 

 

 

Approx.

 MBTUH 

Firing 

A B 

T

W

Amp.

Shipping

Model Input Output Stages Width 

 

NPT    

 

Draw* Wt. (Lbs.)

992BD 990  832 

57-1/8 41-3/8 

2-1/2 

10 

10 16-13/16

<12

930

1262BD 1260  1058 

68-1/2  41-1/2  2-1/2 12 10

20-9/16 

<12 1040 

1532BD 1530  1285 

79-7/8 

36 

2-1/2 12 10

24-3/8 

<12 1255 

1802BD 1800  1512 

91-1/8  33-1/2  2-1/2 14 10

28-1/8 

<12 1380 

2002BD 1999  1679 

102-1/2  39 

2-1/2 14 10 31-15/16

<12 1480 

2072BD 2070  1739 

102-1/2  39 

2-1/2 14 10 31-15/16

<12 1480 

2342BD 2340  1966 

113-7/8  34 

2-1/2 16 10 35-11/16

<12 1550 

* Without pump 

RATES OF FLOW AND PRESSURE DROPS 

 

20°F 

T

30°F 

T

Min. Flow 

Max. Flow

Model GPM

P (ft) GPM

P (ft) GPM 

P (ft) 

T  GPM

P (ft)

T

992BD

84

5.6

56

2.5

42 1.5 40 

132

14.0

13

1262BD

107 10.0  71 

4.5 53 2.6 40 

132 

15.5 

16

1532BD

130 

16.0 

86 

7.1 65 4.1 40 

132 

16.5 

20

1802BD

N/A N/A 102 

10.8 76  6.0 40 132 18.0 23

2002BD

N/A N/A 113 

14.0 85  8.1 40 132 19.5 26

2072BD

N/A N/A 117 

15.0 88  8.7 40 132 19.5 27

2342BD

N/A N/A 132 

21.0 99 12.0 40 132 21.0 30

Basis is 30 GPM or 40°F 

T for minimum flow, 132 GPM for maximum flow. 

NOTE:  Pump location 
varies based on model 
and application

 

NOTES: 

1.  Dimensions are in inches. 

2.  Rates shown are for natural or propane gas, 

and elevations up to 5,000 feet. For 
installation above 5,000 feet, please contact 
manufacturer. 

3.  Required natural gas supply pressure is  

7 - 10.5” WC. Required propane gas supply 
pressure is 11 - 13” WC.

 