Models with Motorized Modulation: H2, H6, W2

Sizes 2100-4001 are equipped with a single motorized modulating valve  controlled by a temperature

controller that offers full modulation down to 20% of rated  input BTU.

LIMIT CONTROLS

1.

HIGH LIMIT
If boiler is equipped with a manual reset High Limit,

push the reset button and set the Limit(s) to 30° - 40°F
above operating temperature.

2.

FLOW SWITCH
Dual purpose control shuts off boiler in case of

pump failure or low water condition.

3.

100% PILOT SAFETY
All standard boilers above 400,000 BTUH input are

equipped with pilot safety(ies), which close the main
valve within 8/10 of a second whenever the pilot flame
is interrupted.  Pilot flame is automatically lit when the
device is powered. Unit performs its own safety check
and opens the main valve only after the pilot is proven
to be lit.

4.

LOW WATER CUTOFF
The low water cut off automatically shuts down

burner whenever water level drops below probe.  90
second time delay prevents premature lockout due  to
temporary conditions such as power failure or air pock-
ets.

5.

HIGH AND LOW GAS PRESSURE SWITCHES
These switches sense either high or low gas pres-

sures and automatically shut down burners if abnormal
pressures exist.

6.

BLOCKED VENT SHUT-OFF SYSTEM
All indoor boilers below 300,000 BTUH input em-

ploy a blocked vent shut-off system designed to shut off
main burner gas in the event the venting system is
totally blocked.

 In the event the blocked vent shut-off system is

actuated, do not attempt to place the boiler in operation,
but contact a qualified service agency.

7.

FLAME ROLL-OUT
SAFETY SHUT-OFF SYSTEM
All boilers below 300,000 BTUH input employ a

flame roll-out safety shut-off system designed to shut-
off the main burner gas in the event of sustained flame
roll-out.

In the event the flame roll-out safety system is

actuated, do not attempt to place the boiler in operation,
but contact a qualified service agency

2

MANUAL RESET

HI LIMIT

FLOW SWITCH

PILOT SAFETY

LOW WATER

CUTOFF

HIGH OR LOW GAS

PRESSURE SWITCH

HIGH LIMIT AND

TEMP CONTROL

TEMP CONTROL

FOR MOTORIZED MODULATION

1

2

3

4

5

Fig # 9314

Fig # 9317

Fig # 8929

Fig # 9316

Fig # 9312

Содержание Gas Fired Boiler

Страница 1: ...turn off or disconnect the electrical supply to the pump Instead shut off the gas supply at a location external to the appliance Raypak recommends that this manual be reviewed thoroughly before insta...

Страница 2: ...vents premature lockout due to temporary conditions such as power failure or air pock ets 5 HIGH AND LOW GAS PRESSURE SWITCHES These switches sense either high or low gas pres sures and automatically...

Страница 3: ...BOILERS WITH MANUALLY LIT PILOTS FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury o...

Страница 4: ...ian or gas supplier 10 Stand to the side of the boiler and turn the gas control knob counter clockwise to ON 11 Replace boiler door panel 12 Turn on all electric power to the appliance 13 Set the ther...

Страница 5: ...etting 2 Turn off all the electric power to the appliance if service is to be performed 3 Remove boiler door panel 4 Turn gas control knob clockwise to OFF Make sure knob rest against stop 5 Replace b...

Страница 6: ...ontrol cover Pilot is automatically lighted 12 Set thermostat to desired setting 13 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technic...

Страница 7: ...ranty conditions you must also specify date of installation 7 Fig S8144 0 RAYPAK HEATING AND HOT WATER SUPPLY EQUIPMENT LIMITED WARRANTY SCOPE Raypak Inc Raypak warrants to the original owner that all...

Страница 8: ...Raypak Inc 31111 Agoura Road Westlake Village CA 91361 4699 818 889 1500 FAX 818 889 4522 Litho In U S A www raypak com...

Отзывы: