From PRO to NAT:

1.  Turn the boiler off (power switch on front control

panel).

2.  Turn FlexGas key to “OFF”.

3.  Close PRO manual valve.

4.  Open NAT manual valve.

5.  Turn FlexGas key to “NAT”.

6.  Turn the boiler on.

Safety Inspection

1.

Check all thermostats and high limit settings.

2.

During the following safety checks leave ma-
nometers hooked up, check and record.0

3.

If other gas-fired appliances in the room are on the
same gas main, check all pressures on the Hi
Delta with all other equipment running.

4.

Check thermostats for ON-OFF operation.

5.

Check high limits for ON-OFF operation.

6.

While in operation, check flow switch operation.

7.

Check the low gas pressure switch. (For proper
adjustment, use the attached manometers, if
available, to set pressure. The scales on the
switch are approximate only.) Low gas pressure
switch (if equipped) must be set at 5.0 in. WC for
natural gas.

Follow-Up

Safety checks must be recorded as performed.

Turn heater on. After main burner ignition:

1.

Check manometer for proper reading.

2.

Cycle heater several times and re-check readings.

3.   Turn unit off.

8

8.

If burner does not light on first trial. It will retry, up
to three times.

9.

Main burner ignition: Check upper manifold gas
pressure.

10. If the pressure readings differ by more than ± 0.1

in. WC, remove screw cover from the gas pres-
sure regulator on the FlexGas fuel train and adjust
until upper manifold pressure is nominally 2.2  ±
0.1 in. WC (manifold pressure 1.3 ± 0.1 in. WC). If
a flue gas analyzer is used, the CO

on propane

should be 9.0-10.0% and CO should be less than
150 ppm.

11. Replace the screw cover. 

12. Turn the gas selector key on the FlexGas control

panel to “OFF”.

13. Close the manual valve on the propane gas supply

and open the manual valve on the natural gas
supply. Turn the gas selector key on the FlexGas
control clockwise to “NAT”. The heater is now
ready for operation.

FlexGas Operation - Changing Fuels

From NAT to PRO:

1.  Turn the boiler off (power switch on front control

panel).

2.  Turn FlexGas key to “OFF”.

3.  Close NAT manual valve.

4.  Open PRO manual valve.

5.  Turn FlexGas key to “PRO”.

6.  Turn the boiler on.

NOTE: 

Reset Low Gas Pressure Switch (when

equipped) if necessary. Refer to Fig. 2 for location.

CAUTION:

Special manifold and air settings may

be required. Verify rating plate and blower housing.

CAUTION: 

Once the natural gas pressures are

established, DO NOT adjust the Hi Delta gas valves
to attain the required propane pressures.
Adjustments must be made to the FlexGas propane
regulator.

Содержание FlexGas 302BD-2342BD

Страница 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the...

Страница 2: ...he following Changes to step 4 of the FlexGas System Start up section on page 7 the Wiring Diagram was moved from page 5 to page 9 the addition of a note to the Attach Manometers to Measure Pressures...

Страница 3: ...er to the Hi Delta manual for available firing options The second group of characters identifies the size of the heater four numbers representing the approximate MBTUH input and where applicable a let...

Страница 4: ...gas and 13 0 in WC for propane gas The regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls The heater must be isolated from the gas supply p...

Страница 5: ...et taps on propane gas See Fig 5 for gas pressure measure ment locations Bleeds Vents This FlexGas gas train is equipped with an propane gas regulator and low gas pressure switch optional on 302BD 902...

Страница 6: ...esult in a fire or explosion Do not use this appliance if any part has been under water immediately call a qualified service technician to inspect the appliance and to replace Initial Start up Tools N...

Страница 7: ...ould open in 45 60 seconds 3 If burner does not light on first trial It will retry up to three times 4 Main burner ignition Check manifold gas pres sure at gas valve outlet pressure tap This should re...

Страница 8: ...three times 9 Main burner ignition Check upper manifold gas pressure 10 If the pressure readings differ by more than 0 1 in WC remove screw cover from the gas pres sure regulator on the FlexGas fuel t...

Страница 9: ...ll manometers and replace caps and screws 5 Replace all gas pressure caps 6 Check for gas leaks one more time 7 Restart unit Fig 5 FlexGas Control Panel Fig 6 Wiring Diagram Optional on 302BD 902BD Wi...

Страница 10: ...10...

Страница 11: ...LENOID VALVE PRO 012125F 011910F 011910F 011910F 4 G MANUAL GAS VALVE NAT 011945F 011945F 007665F 007665F 5 G MANUAL GAS VALVE PRO 011944F 011945F 011945F 011945F F 8 4 9 1 1 0 F 7 4 9 1 1 0 F 7 4 9 1...

Страница 12: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A www raypak com...

Отзывы: