Raypak BACnet Interface Module Скачать руководство пользователя страница 3

BaCnet Interface Module Installation and Configuration Manual

 

3

OvervIeW

The BACnet Interface Module adds BACnet MS/TP communication capability to the Raypak TempTracker mod+ 

Hybrid (Hybrid) control.  It does that by connecting to both, the control and the BACnet MS/TP network.  All the 

BACnet settings are configured through the control.  The BACnet Interface Module has LEDs that can help in displaying 

communication status.

BACnet Interface Module

MSTP

1

2

3

A   GND   B

PRODUCT

COMM

RS485

RS485

to EMS

RJ45

Communication

to Control

Operation

LEDs

RJ11

to Extension

Mounting

Tab

ITeM LIST

•   BACnet Interface Module,

•   RJ45 cables (Ethernet Cable),

InSTaLLaTIOn

The BACnet Interface Module communicates with the Raypak Hybrid control using the RJ45 cable.  Thus, it needs to be 

installed in close proximity to the control.

•   Mount the BACnet Interface Module on a flat surface next to the control.

•   The module can be mounted horizontally or vertically.

•   Keep the module away from extreme heat, cold, or humidity.

•   Screw the module to the flat surface using the two side tabs with holes.

•   No need to remove the BACnet Interface Module cover.

WIrIng

•   No power wiring is required for the BACnet Interface Module.  It gets its power through the 

control's RJ45 connection. 

•   The module's MS/TP terminals are of the removal type.  That facilitates easy wiring.  Just 

unscrew the terminal block side screws to remove the full terminal block.

BACnet Interface Module

MSTP

1

2

3

A   GND   B

PRODUCT

COMM

RS485

A (+)

Ground

B (-)

To BACnet

MSTP

BaCnet MS/TP Wiring

•   Use 18# AWG Twisted Pair cable.  The cable length must not exceed 3500 feet.

•   Connect the MS/TP cable coming from the BACnet MS/TP network to the MS/TP terminals 

on the BACnet Interface Module.  Communication on the BACnet MS/TP network is polarity 

sensitive.

•   The ground terminal (GND) MUST be connected to the BMS Ground.

HT# 

0591

19-00B

Содержание BACnet Interface Module

Страница 1: ...GND B PRODUCT COMM RS485 SYSTEM A B C D 1 2 RUN PROGRAM DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS 3 4 5 6 7 8 9 10 11 12 13 15 14 17 16 18 20 19 21 24 23 29 25 27 26 28 32 30 31 L N T T O O RS 485 mA GND VLT SYS A B C D PWR CUR VLT A mA GND VLT mA GND VLT mA 22 GND VLT mA TEMP OUTDOOR O O TEMP SYSTEM EXTENSION MODULE CUR VLT B CUR VLT C CUR VLT D PROVE DHW SHUTDOWN SETBACK FOR ALL CIRCUITS 120VA...

Страница 2: ...ntent 2 Overview 3 Item List 3 Installation 3 Wiring 3 BACnet MS TP Wiring 3 Connecting to Control 4 Connecting to Extension 4 BACnet Startup Menu Setup 5 LED 5 Troubleshooting 6 No LED Light 6 No Communication 6 Specification 6 Wiring to Control and Extension 7 HT 059119 00B ...

Страница 3: ...Mount the BACnet Interface Module on a flat surface next to the control The module can be mounted horizontally or vertically Keep the module away from extreme heat cold or humidity Screw the module to the flat surface using the two side tabs with holes No need to remove the BACnet Interface Module cover Wiring No power wiring is required for the BACnet Interface Module It gets its power through th...

Страница 4: ...IRE ONLY CAUTION RISK OF ELECTRIC SHOCK More than one disconnect switch may be required to de energize the equipment before servicing ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA TSTAT HYBRID RJ45 Communication Cable A Ground B To BACnet MSTP Connecting to Control The BACnet Interface Module communicates all of its information to the control using RJ45 cable the cable is provided with the module Both...

Страница 5: ...rate could be the cause Check with the network administrator for the network baud rate Then match it on the control BACNET BAUDRATE 9600 19200 38400 BACK SAVE MS TP Address 1 to 127 Default 64 Button MENU System Startup BACnet Mode BACnet Baudrate MSTP Address Each device on the MS TP network must have a unique address This is the MS TP address on a RS485 network Its MS TP range is 1 though 127 Th...

Страница 6: ... and Green LEDs If the Yellow LED is continuously On or Off then check the cable connecting the module to the control If the Green LED is continuously On or Off then check the cable connecting the module to the BACnet network Make sure that the control s Baud Rate and the BACnet Network s are the same See BACnet Baud Rate on page 5 Specification Control Communication RJ45 to control Cable is provi...

Страница 7: ... switch may be required to de energize the equipment before servicing ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA TSTAT HYBRID RJ45 Communication Cable RJ45 Cable Extension RJ11 Extension Cable F H J Power CAUTION Risk of Electric Shock More than one disconnect switch may be required to de energize the equipment before servicing PWR L N 1 2 E 3 4 F 5 6 G 7 8 H 9 10 I 11 12 EXTENSION MODULE RS 485 Ex...

Страница 8: ...HT 059119 00B Raypak Inc 2151 Eastman Ave Oxnard CA 93030 PH 805 278 5300 FAX 805 278 5468 ...

Отзывы: