background image

13

CAUTION:

 To clean the fins, spray gently with a garden 

hose.  DO NOT  pressure  wash.  Doing  so  will  bend  the 

fins, causing damage which will not be covered under 

warranty.

Cabinet Care (optional)

The cabinet is designed for outdoor use and requires little 

care. However, you can clean it if you wish.

A

WARNING:

  Shut  OFF  electricity  to  the  unit  before 

cleaning.

Wash the cabinet with soap and water.

Unplug Condensation Drain Holes

The unit extracts humidity from the air as it passes through 

the coil, similar to the way a cold drink outside “sweats” 

on a hot day. This condensation drains from the bottom of 

the unit.
1.  Routinely  check  to  be  sure  the  condensation  drain 

holes in the base of the unit are not plugged with dirt 

or debris.

2.  If  condensation  becomes  a  problem,  optional  drain 

pans  are  available  from  your  heater  distributor  or 

pool dealer.

18.  TROUBLESHOOTING

If your unit does not operate, or simply does not heat your 

pool water, Fault Codes (digital models), or the indicator 

lamps  (analog  models)  on  the  front  control  panel,  can 

provide  valuable  clues  as  to  what  is  wrong,  and  may 

even  indicate  precisely  what  the  problem  is.  Always 

observe these codes (or lamps) before calling a service 

representative.  By  reporting  on  the  telephone  the  Fault 

Codes (or which lamps are ON or OFF) that are showing, 

the service rep may be able to solve the problem without 

the expense of a service call.

NOTE:

 If the compressor fails to start when energized, 

and there are no faults detected in the wiring, contact the 

factory for the appropriate “Hard Start Kit.”

A. Unit Is Running, But Not Heating

•  Is water flow through the unit adequate? Check the 

unit for obstructions, such as a clogged filter pump 

strainer, a dirty filter, or valves not positioned correctly.

•  Is the ejected air from the unit 8°–10°F (4.4°–5.6°C) 

cooler than incoming air? If so, the unit is extracting 

heat from the air and transferring it to the pool.

•  Is water condensing on the evaporator and internal 

copper pipes? This is also evidence of heat removal 

from the air. When the air is cool with low humidity, 

condensation may not be evident.

•  How long has the unit been operating? During initial 

pool heating in cold weather, it may require a week to 

elevate the water temperature to a comfortable level. 

Normally, it takes about 4 days. 

How many hours per day is the unit operating? 

Remember 

that the heater only operates while the pool pump is 

running.

  Set  the  time  clock  to  permit  24  hour  per  day 

operation. After the desired temperature is reached, return 

the unit to normal operation of 8–10 hours per day.

NOTE:

 If the pool pump and heater shut OFF before the 

water temperature is raised to the desired level, you must 

lengthen the running time of both. To do this, reset the 

time clock dial for the longer running time, or manually 

operate the pump with the timer override switch. Since 

the unit capacity and efficiency are both greater at higher 

ambient air temperatures, run time should be set to take 

advantage of all daylight hours, when the air is generally 

warmer.

•  Is  airflow  through  the  unit  being  obstructed? 

Restrictions  such  as  shrubbery,  tall  grass,  dirty 

coils, or any other obstruction to airflow will reduce 

performance.

•  Is the pool blanket/cover being used? Unblanketed 

pools can lose up to 10 degrees per night compared 

to 4 degrees or fewer when a blanket is used. Without 

a blanket, the total heat gained during the day can be 

lost overnight.

•  Are rapid heat losses occurring in some other way, 

such  as  high  wind,  spillage,  rainfall,  flow  through 

solar panels at night, or a high water table?

B. Unit Is Not Running

•  Is  the  temperature  display  or  control  panel  Power 

lamp on? If not, the circuit breaker may be shut OFF 

or  tripped.  Reset  the  breaker  by  switching  it  OFF, 

and then back ON. Verify that the breaker is set and 

operating properly before calling for service.

•  Is  the  thermostat  setting  and  the  Pool/Spa  setting 

correct?  Verify  that  the  temperature  has  been 

properly set on the thermostat, and that it is higher 

than the current water temperature. On analog units, 

all 3 lamps should be illuminated and the fan should 

begin to run.

•  Have you waited approximately 5 minutes for the time 

delay? After the unit has been running and then shut 

OFF for any reason, there is a delay before operation 

can begin again.

•  Is  the  Heat  Light  or  Heat  Demand  lamp  ON?  If 

not,  then  the  thermostat  setting  is  not  higher  than 

the  temperature  of  the  water.  Raise  the  thermostat 

setting.

NOTE:

 The heater will not run when the Remote position 

is selected on the Pool/Spa selector switch and there is 

no remote control system attached.

Содержание 5350 Series

Страница 1: ...o do so may result in an explosion or fire NOTE The instructions in this manual are for the use of qualified individuals specially trained and experienced in the installation and maintenance of this t...

Страница 2: ...anges Reformatted to InDesign from Quark Additional Metric data added as needed to text figures and tables Text clarity improved throughout using improved word choice to avoid ambiguity or incompleten...

Страница 3: ...ANNUAL CHECK 12 15 SUMMER SHUTDOWN 12 16 FREEZE PROTECTION 12 System Drain Down 12 Continuous Pump Operation 12 17 MAINTENANCE 12 Air Coil Cleaning 12 Cabinet Care optional 13 Unplug Condensation Dra...

Страница 4: ...der warranty ALWAYS follow the product manufacturer s directions when adding any chemicals to your pool CAUTION Elevated water temperature can be hazardous The U S Consumer Product Safety Commission h...

Страница 5: ...in a refrigeration cycle to extract heat from ambient air and deliver it to the circulating pool water As with all heaters compared to other types of heaters such as gas or oil fired this heater has l...

Страница 6: ...unit as close as possible to the existing pool pump and filter If the location of the heater is below the water line of the pool the water pressure switch might need to be adjusted or an external wat...

Страница 7: ...h 3 SEC GUST IN ACCORDANCE WITH ASCE 7 2010 CHAPTER 30 WIND LOADS COMPONENTS AND CLADDING FLORIDA BUILDING CODE 2017 SECTION 1609 WIND LOADS FLORIDA BUILDING CODE 2017 SECTION 1620 HIGH VELOCITY HURR...

Страница 8: ...l panel for precise power requirements for your unit and for ampacity and over current protection requirements All wiring must be in accordance with the National Electrical Code NFPA No 70 latest edit...

Страница 9: ...13 89 6 13 89 6 Multiply the pressure drop in PSI by 2 3067 to yield the pressure drop in Ft H2O Head TDH Table C Pressure Drop Across Heater AWARNING Install a check valve and or a Hartford loop AFTE...

Страница 10: ...coil The fan will continue to run but the compressor will stay OFF not heating until weather conditions improve Low Pressure red lamp When lit indicates failure in the refrigeration circuit When this...

Страница 11: ...DOWN key you can switch to POL or SPA To Increase the Desired Water Temperature Pool or Spa Mode Push the SET key until you see POL or SPA The programmed temperature will be displayed Press the UP ar...

Страница 12: ...e timer override switch Since the heater capacity and efficiency are both greater at higher ambient air temperatures run time should be set to take advantage of all daylight hours when the air is gene...

Страница 13: ...a week to elevate the water temperature to a comfortable level Normally it takes about 4 days How many hours per day is the unit operating Remember that the heater only operates while the pool pump is...

Страница 14: ...h buttons Replace keypad Table D Control Board Fault Codes Digital Models 1 Use a pool chemistry test kit to confirm there is no chlorine in the condensation Or 2 Shut the unit OFF and leave the filte...

Страница 15: ...SPA FILTER CHECK VALVE CHEMICAL INTRODUCTION NO EXTERNAL BYPASS IS REQUIRED WATER OUT TO POOL OR SPA F10123 INLET AND OUTLET ARE 2 UNIONS PLUMB THE UNIT AFTER THE FILTER BEFORE ANY CHLORINATORS Figure...

Страница 16: ...AL INTRODUCTION WATER OUT TO POOL OR SPA REQUIRED BYPASS ADJUST TO PROVIDE 40 80 GPM FLOW THROUGH THE UNIT F10124 INLET AND OUTLET ARE 2 UNIONS PLUMB THE UNIT AFTER THE FILTER AND BEFORE ANY CHLORINAT...

Страница 17: ...17 4 SYSTEM PIPE DIAMETERS OR 12 30 5 cm MAX WHICHEVER IS LESS MINIMUM SYSTEM FLOW IS 120 OF THE FLOW REQUIRED BY EITHER UNIT Figure 10 Piping for Heat Pump Pool Heater and Gas Pool Heater...

Страница 18: ...2 3 Sizing based on10 ft sec flow rates MINIMUM PIPE SIZES 2 UNITS 3 4 UNITS 5 6 UNITS 5450 8450 BRANCH MAIN BRANCH MAIN BRANCH MAIN 30 GPM 40 60 80 2 2 2 2 2 3 3 4 30 GPM 40 60 80 2 2 2 2 2 1 2 3 4 4...

Страница 19: ...19 H C F DUAL CAPACITOR V V V 21 WIRING DIAGRAMS 208V 230V Single Phase Analog Models 5350 6350 8350...

Страница 20: ...20 H C F DUAL CAPACITOR V V 208V 230V Single Phase Digital Models 5350 6350 8350 8360...

Страница 21: ...21 208V 230V 3 Phase Analog Models 5350 6350 8350...

Страница 22: ...22 208V 230V 3 Phase Digital Models 5350 6350 8350...

Страница 23: ...23 460V 3 Phase Analog Model 8354...

Страница 24: ...control use the TOTAL and COMMON connections on the heater wiring block For a 3 wire control use the COMMON SPA and POOL connections on the heater wiring block Figure 13 Heater Wiring Block Digital H...

Страница 25: ...25 24 ILLUSTRATED PARTS LIST 1 H 5 S 1 F 2 F 4 S 6 S 8 S 8 S 6 H 2 H 8 S 1 C 4 H 3 C 2 C 5 C 7 H 8 H 12 H 5 H 2 S 7 S 4 C 6 C 9 S 2 M 1 S 3 S 5 C 5 C 10 H 4 H 6 S 9 H...

Страница 26: ...26...

Страница 27: ...27 17 J 2 J 1 J 3 J 7 J 4 J 5 J 18 J DIGITAL 6 J 17 J 8 J 2 J 1 J 3 J 4 J 5 J 15 J 16 J 15 J 9 J 10 J 7 J 18 J 14 J 11 J 13 J 12 J ANALOG...

Страница 28: ...28...

Страница 29: ...29...

Страница 30: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...

Страница 31: ...ut causer un incendie ou une explosion NOTE Les pr sentes instructions sont destin es des personnes qualifi es sp cialement form es et exp riment es dans l installation et l entretien de ce type d qui...

Страница 32: ...vants Reformat InDesign de Quark Mise jour du texte et des figures au besoin Am lioration du texte notamment par l utilisation d un meilleur choix de mots pour viter toute ambigu t ou information inco...

Страница 33: ...ESTIVALE 12 16 PROTECTION CONTRE LE GEL 12 Vidange du syst me 12 Fonctionnement en continu 12 17 MAINTENANCE 12 Nettoyage des serpentins 12 Entretien du bo tier optionnel 13 D boucher les orifices de...

Страница 34: ...relativement l ajout de produits chimiques votre piscine ATTENTION de l eau chauff e constitue une source de danger La Commission am ricaine sur la s curit des produits de consommation CPSC met les di...

Страница 35: ...ambiant et la transf re l eau de la piscine ou du spa Comme tout autre appareil de chauffage cet appareil poss de une puissance brute exprim e en BTU h inf rieure celle d autres types d appareils de c...

Страница 36: ...errasse voir Figure 1 Afin de minimiser la longueur des conduites d eau positionnez l appareil aussi pr s que possible de la pompe et du filtre de la piscine Si l appareil est install en dessous de la...

Страница 37: ...OUR SURCHARGE DE VENT NIVEAU 1 SANGLES EN ACIER GALVANIS 18 GA X 5 LARG MIN G90 OU L QUIVALENT MIN 4 SANGLES MIN 3 VIS AUTOTARADEUSES 1 2 12 PAR SANGLE ENDUIT PROTECTEUR 1000 H MIN APPAREIL 27 686 mm...

Страница 38: ...xigences de la plus r cente dition du National Electrical Code NFPA No 70 ainsi qu tous les codes nationaux et locaux applicables Les sch mas de c blage se trouvent aux pages 19 23 NOTE reportez vous...

Страница 39: ...7 12 82 7 12 82 7 80 max 303 13 89 6 13 89 6 13 89 6 Note multipliez la perte de charge en psi par 2 3067 pour obtenir la perte de charge en en pi H2O pi c e Table C Perte de charge dans l appareil AV...

Страница 40: ...ode de d givrage s active lorsque de la glace commence se former sur le serpentin ext rieur Le ventilateur continue tourner mais la temp rature doit remonter avant qu un nouveau cycle de chaleur ne pu...

Страница 41: ...he UP pour augmenter le r glage de la temp rature cible d un degr la fois Baisse de la temp rature cible mode piscine ou spa Appuyez sur la touche SET jusqu ce POL ou SPA s affiche La temp rature cibl...

Страница 42: ...n correctement faire circuler l eau travers l appareil 15 MISE HORS SERVICE ANNUELLE Si vous ne pr voyez pas utiliser l appareil pendant toute une saison veuillez la prot ger comme suit 1 Ouvrez le di...

Страница 43: ...ction de la chaleur de l air Si l air ambiant est frais et sec il se pourrait qu il n y ait pratiquement pas de condensation Depuis combien de temps l unit fonctionne t elle Par temps frais la suite d...

Страница 44: ...nctionne en mode d givrage le ventilateur tourne mais le compresseur est l arr t L enfoncement d un bouton active deux touches Remplacer le clavier Table D Codes d erreur Mod les num riques C Condensa...

Страница 45: ...CHIMIQUES ICI AUCUNE D RIVATION EXTERNE REQUISE SORTIE D EAU VERS PISCINE OU SPA F10123 LES RACCORDS D ENTR E ET DE SORTIE SONT DES RACCORDS UNIONS 2 PO POSITIONNER L APPAREIL APR S LE FILTRE AVANT T...

Страница 46: ...OU SPA D RIVATION EXTERNE REQUISE R GLER POUR ASSURER UN D BIT DE 40 80 GPM DANS L APPAREIL F10124 LES RACCORDS D ENTR E ET DE SORTIE SONT DES RACCORDS UNIONS 2 PO POSITIONNER L APPAREIL APR S LE FIL...

Страница 47: ...US LA THERMOPOMPE DOIT TRE INSTALL E SELON LES EXIGENCES DU FOURNISSEUR DE LA THERMOPOMPE NOTAMMENT LA PROTECTION CONTRE LA SURCHAUFFE OU LE GEL MOD LES ILLUSTR S TITRE INDICATIF LA CONFIGURATION PEUT...

Страница 48: ...SIBLE THERMOPOMPE THERMOPOMPE THERMOPOMPE 3 4 APPAREILS VOIR TABLEAU DIA MIN TUYAUX 5 6 APPAREILS VOIR TABLEAU DIA MIN TUYAUX THERMOPOMPE THERMOPOMPE THERMOPOMPE PRODUITS CHIMIQUES ICI BOUCLE PRIMAIRE...

Страница 49: ...2 44 k V V V FUSIBLE MALT ALIMENTATION CHAUFFAGE EAU COMPRESSEUR D GIVRAGE PRESSOSTAT AMBRE VERT ROUGE AMBRE ROUGE ROUGE DEL D TAILS C BLAGE TENSION ALIM ALIMENTATION LECTRIQUE C BL USINE 24 VOLTS CA...

Страница 50: ...LA TENSION D ALIMENTATION 230 V PAR D FAUT R GLER 210 V SI ALIMENTATION 208 V MODIFI E AU CHANTIER R GLER D LAI DU CADRAN BLEU 0 1 MINUTE R SISTANCE DES CAPTEURS 75 10 5K 77 10K 84 8 50K MONITEUR DE T...

Страница 51: ...e cut R GLER TEMP RATURE DE LA PISCINE OFF ET CELLE DU SPA 104 C RACCORDEMENTS POMPES RAYPAK VOIR LE MANUEL DE LA POMPE POUR THERMOSTAT 2 FILS UTILISER BORNES 21 ET 22 POUR LE RACCORDEMENT DE THERMOST...

Страница 52: ...AIL B MOTEUR VENTILATEUR RACCORDEMENTS POMPES RAYPAK VOIR LE MANUEL DE LA POMPE D TAIL C D TAIL C ASSERVI 1 ASSERVI 2 ASSERVI 3 ASSERVI 4 D TAILS RELAIS PRINCIPAL D TAIL B COMPRESSEUR CONTR LEUR TRIPH...

Страница 53: ...OTEUR VENTILATEUR RELAIS SPST RELAIS DPST D TECTEUR DE FUITES D TAIL C R GLAGES THERMOSTAT 75 F 4 73 k 77 F 4 25 k 84 F 2 44 k R GLAGES CAPTEUR 75 F 10 5 k 77 F 10 k 84 F 8 50 k 2 POUR THERMOSTAT 2 FI...

Страница 54: ...t COMMON du bornier de l appareil Dispositif de commande 3 fils raccordez le aux contacts TOTAL et COMMON du bornier de l appareil Figure 13 Bornier de l appareil Mod les num riques Param tres de l ap...

Страница 55: ...25 24 ILLUSTRATION DES PI CES 1 H 5 S 1 F 2 F 4 S 6 S 8 S 8 S 6 H 2 H 8 S 1 C 4 H 3 C 2 C 5 C 7 H 8 H 12 H 5 H 2 S 7 S 4 C 6 C 9 S 2 M 1 S 3 S 5 C 5 C 10 H 4 H 6 S 9 H...

Страница 56: ...22 H000024 3 H Assemblage de d rivation H000042 H000042 H000042 H000042 H000042 H000042 10 H Union en PVC N A N A N A N A N A N A Union en PVC avec s cheur de ligne de H000317 H000317 H000317 4 H liqu...

Страница 57: ...27 17 J 2 J 1 J 3 J 7 J 4 J 5 J 18 J NUM RIQUE 6 J 17 J 8 J 2 J 1 J 3 J 4 J 5 J 15 J 16 J 15 J 9 J 10 J 7 J 18 J 14 J 11 J 13 J 12 J ANALOGIQUE...

Страница 58: ...e 01 04 13 H000117 H000117 H000117 H000117 Unit s fabriqu es partir du 01 04 13 H000265 H000265 3 PH 460V Unit s fabriqu es avant le 01 04 13 H000113 H000113 Unit s fabriqu es partir du 01 04 13 H0002...

Страница 59: ...H000086 H000086 H000085 H000086 H000086 Gris fonc chaud H000207 H000208 H000208 H000207 H000208 H000208 4 S Veste Haut Vert H000092 H000092 H000092 H000092 H000092 H000092 Gris fonc chaud H000211 H00...

Страница 60: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...

Отзывы: