background image

Catalog No.: 

 

2000.441E 

Effective:  11-15-07 

Replaces:  1-1-07  

 

Hi Delta – Type H 

Models 302BE-902BE, 87% Efficiency

 Model 

           

 

 

 

 

 

 

 

 

 

RATES OF FLOW AND PRESSURE DROPS

 

10°F 

T 20°F 

T

30°F 

T

Min. Flow

Max. Flow 

Model GPM 

P (ft) 

GPM 

P (ft) 

GPM 

P (ft) 

GPM 

P (ft) 

GPM 

P (ft) 

302BE 52  3.4  26  <1

N/A

N/A

20

<1

26

90

9.8 6 

402BE 

69 5.8 35 1.5 23  <1  20  <1 35 

90 10.0 

502BE 

87 9.9 44 2.5 29 1.2 22  <1 40 

90 10.5 

10 

652BE 

N/A 

 

N/A 57 4.3 38 2.0 28 1.2 

40 

90 10.7 

13 

752BE 

N/A 

N/A 

 65 5.8 44 2.7 33 1.7 

40 

90 11.0 

15 

902BE 

N/A N/A 78 9.0 52 4.1 39 2.4 

40 

90 11.8 

17 

Basis is 20 GPM or 40°F 

T for minimum flow, 90 GPM for maximum flow.

 

NOTE: Pump location 
varies based on model 
and application 

NOTES:  1.  Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer. 
 

2.  Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC.

 

SPECIFICATIONS 

 

 

 

Approx.

MBTUH

A

G H 

K T  W

Amp. Shipping

Model

Input Output Width NPT NPT     

 

Draw Wt. 

(Lbs)

302BE

300

261

36

3/4 2 5 

6  18

6

380

402BE

399 347  43 3/4 2 

18-1/2

6  445 

502BE

500 435  50 

1-1/4 

6 22  6  545 

652BE

650 566 

60-1/2 1-1/4 

27-1/4

6  590 

752BE

750 653 

67-1/2 1-1/4 

30-3/4

6  675 

902BE

900 783  78 

1-1/4 

6 36  7  740 

Dimensions are in inches. 

Raypak, Inc.  

ƒ

  2151 Eastman Avenue, Oxnard, CA  93030  

ƒ

  (805) 278-5300  

ƒ

  Fax (800) 872-9725  

ƒ

  www.raypak.com 