Catalog No.:
2000.441E
Effective: 11-15-07
Replaces: 1-1-07
Hi Delta – Type H
Models 302BE-902BE, 87% Efficiency
Model
RATES OF FLOW AND PRESSURE DROPS
10°F
∆
T 20°F
∆
T
30°F
∆
T
Min. Flow
Max. Flow
Model GPM
∆
P (ft)
GPM
∆
P (ft)
GPM
∆
P (ft)
GPM
∆
P (ft)
∆
T
GPM
∆
P (ft)
∆
T
302BE 52 3.4 26 <1
N/A
N/A
20
<1
26
90
9.8 6
402BE
69 5.8 35 1.5 23 <1 20 <1 35
90 10.0
8
502BE
87 9.9 44 2.5 29 1.2 22 <1 40
90 10.5
10
652BE
N/A
N/A 57 4.3 38 2.0 28 1.2
40
90 10.7
13
752BE
N/A
N/A
65 5.8 44 2.7 33 1.7
40
90 11.0
15
902BE
N/A N/A 78 9.0 52 4.1 39 2.4
40
90 11.8
17
Basis is 20 GPM or 40°F
∆
T for minimum flow, 90 GPM for maximum flow.
NOTE: Pump location
varies based on model
and application
NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.
2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC.
SPECIFICATIONS
Approx.
MBTUH
A
G H
K T W
Amp. Shipping
Model
Input Output Width NPT NPT
Draw Wt.
(Lbs)
302BE
300
261
36
3/4 2 5
6 18
6
380
402BE
399 347 43 3/4 2
6
6
18-1/2
6 445
502BE
500 435 50
1-1/4
2
6
6 22 6 545
652BE
650 566
60-1/2 1-1/4
2
8
6
27-1/4
6 590
752BE
750 653
67-1/2 1-1/4
2
8
6
30-3/4
6 675
902BE
900 783 78
1-1/4
2
8
6 36 7 740
Dimensions are in inches.
Raypak, Inc.
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300
Fax (800) 872-9725