background image

24

Program Button

1.  Remove the four screws holding the control cover, and 

swing the panel down so the back side of the board 

is visible. Locate the Program Mode button (SW1) as 

shown in 

Figure 39

. Press and hold the button for 5-7 

seconds  until  SET  FACTORY  DEFAULTS  appears 

on the display. Release the program button.

2.  Press the MODE button sequentially until the desired 

program  event  is  reached.  There  are  5  different 

events that can be programmed. They appear in the 

sequence listed in 

Figure 44 

below.

Resets  board  to  factory  default 

settings.

Resets faults in the History File.

Change from Fahrenheit to 

Celsius.

SPA setpoint maximum  

adjustment.
POOL setpoint maximum 

adjustment.

Figure 44.  Programmable Events

Set Factory Defaults

Refer to step one above to access the program screen. 

SET FACTORY DEFAULTS should appear on the screen. 

If it does not, press the MODE button until it appears on 

the  digital  display.  Press  and  hold  both  UP  and  DOWN 

buttons  for  5-7  seconds  until  DEFAULTS  SET  appears. 

This operation resets the operating program to its factory 

default values.
Both  the  POOL  and  SPA  setpoints  will  revert  to  65°F 

(18°C)  and  both  POOL  and  SPA  maximum  temperature 

settings will be 104°F (40°C). The Control Lockout PIN will 

be cleared and the control will resume normal operation.

Clear Faults

Refer to step one above to access the program screen.  

Press  the  MODE  button  until  CLEAR  FAULTS  appears 

on the digital display. Press and hold both UP and DOWN 

buttons for 5-7 seconds until FAULTS CLEARED appears. 

This operation resets the Fault History file to “0” and clears 

all the stored faults.

Fahrenheit or Celsius

Refer to step one above to access the program screen.  

Press the MODE button until FAHRENHEIT

 

or CELSIUS 

appears on the digital display. The UP or DOWN buttons 

will select FAHRENHEIT

 

or CELSIUS on the temperature 

display. Choose the desired temperature scale.

Spa Max Temp – Spa Setpoint Maximum Adjustment

Refer to step one above to access the program screen.  

Press the MODE button until SPA MAX TEMP appears on 

the digital display. Using the UP and DOWN buttons will 

change the Maximum Temperature Setting to your desired 

value.  The  control  can  be  set  for  a  maximum  of  107°F 

(42°C).

Pool Max Temp – Pool Setpoint Maximum 

Adjustment

Refer to step one above access into the program screen.  

Press the MODE button until POOL MAX TEMP appears 

on the digital display. Using the UP and DOWN buttons 

will  change  the  Maximum  Temperature  Setting  to  your 

desired value. The control can be set for a maximum of 

107°F (42°C).

Control Lockout

The  heater  is  equipped  with  a  Control  Lockout  feature 

to  prevent  unauthorized  tampering  or  adjustment  of  the 

control settings. To lock out the controls, press the DOWN 

button and MODE button for 5 seconds. Choose a three 

digit PIN, using the UP and DOWN buttons to select the 

digits and the MODE button to lock in selections. Confirm 

your selection and record your PIN.
To unlock the controls, press any button to bring up the 

ENTER PIN

 

menu. Enter the PIN that was used to lock the 

control. Note that power cycling will not clear the lockout.  

Successfully unlocking the control will display LOCKOUT 

CLEARED.  Failure  to  enter  the  correct  PIN  will  display 

INVALID PIN.
In the event that the user-selected PIN is lost or does not 

clear the Control Lockout, use the Program Button to SET 

FACTORY DEFAULTS. This will clear the PIN and allow 

normal operation and selection of a new PIN if desired. 

See the 

"Program Button" on page 24

 for details. 

NOTE:

  Both  the  POOL  and  SPA  setpoints  will  revert 

back  to  65°F  (18°C)  and  the  POOL  and  SPA  maximum 

temperature  settings  will  be  104°F  (40°C).  These 

setpoints will need to be readjusted to desired settings.

NOTE:

 The LCD temperature display may not agree with 

the temperature reading of your pool or spa thermometer. 

The heater reads the water temperature at the inlet. Due 

to the circulation characteristics of any pool or spa, the 

water  temperature  at  the  inlet  to  the  heater  may  differ 

from that observed at a given location in the pool or spa.

Содержание 207A

Страница 1: ...other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immed...

Страница 2: ...See page 15 for flow rate values GAS Distance to regulator pipe lengths and gas inlet sizes See page 14 Required pressure for Natural Gas Min 5 WC Max 10 5 WC Sediment trap is required for all install...

Страница 3: ...ve 17 Auxiliary Bypass Valve Adjustment 17 Pressure Relief Valve Installation 17 Plumbing Diagram 18 Heat Exchanger Reversal 19 5 ELECTRICAL WIRING 19 Electrical Power Draw 20 Transformer Wiring 20 6...

Страница 4: ...uld cause severe personal injury death or substantial property damage if ignored ACAUTION Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or pr...

Страница 5: ...and dissolved solids in the water become too high scale NOTE It is recommended that the pump be run at least 5 minutes after the heater has been turned off This helps in taking away residual heat from...

Страница 6: ...eet 1524 m elevation For elevations above 5 000 feet 1524 m consult the factory F10639 1 THE MODEL AND SERIAL NO CAN ALSO BE FOUND INSIDE THE BEZEL ABOVE THE DISPLAY MODEL AND SERIAL NO LOCATED ON RAT...

Страница 7: ...n side This will enable the heater to be serviced in its installed location that is without movement or removal of the heater Clearances less than these may require removal of the heater to service ei...

Страница 8: ...learances to Protected Surfaces Heaters must not be installed under an overhang of less than three 3 0 9 m from the top of the heater Three sides must be open in the area under the overhang Roof water...

Страница 9: ...edition of the National Fuel Gas Code U S ANSI Z223 1 or Canada CAN CSA B149 and any local codes that may have jurisdiction The most common approach is the 2 opening method with combustion air opening...

Страница 10: ...hor Bracket Use hole closest to unit 4 total 2 x 6 x 1 8 Pallet Anchor Bracket 4 Total Kit 011636 1 4 x 1 3 4 S S Tapcon Bolt and Washer Field Supplied NOTE Use hole closest to unit with washer overla...

Страница 11: ...48 13 0 330 10 5 8 270 3 4 2 219 99 238 108 19 8 6 399L 399 116 9 29 737 9 229 58 1 2 1486 14 5 368 12 1 2 318 3 4 2 237 108 N A 21 9 5 407A 256 116 Table G Heater Specifications and Dimensions Specif...

Страница 12: ...2 4 m Vent stack shall be at least 5 1 5 m in vertical height above the drafthood outlet The vent cap location shall have a minimum clearance of 4 1 2 m horizontally from and in no case below unless a...

Страница 13: ...re under load and no load conditions must be provided for natural gas Gas Pressure Regulator The gas pressure regulator is preset at 3 1 in WC for natural gas The pressure at the gas valve taken with...

Страница 14: ...1 1 4 1 1 2 2 20 75 100 378 266L 267A 1 1 4 1 1 2 2 25 95 100 378 337A 1 1 4 1 1 2 2 35 132 100 378 399L 407A 1 1 4 1 1 2 2 40 151 100 378 When flow rates exceed maximum GPM an external auxiliary byp...

Страница 15: ...ction can be ordered that will allow a standard ASME unit to comply with the code requirements ProTek Shield Assembly This heater is equipped with a ProTek Shield Assembly located under the inlet conn...

Страница 16: ...eratures well below accelerated scaling temperatures F10725 GASKET UG PLUG UNITHERM GOVERNOR Figure 20 Unitherm Governor Polymer F10642 2 UG BYPASS ASSY UNITHERM GOVERNOR Figure 21 Unitherm Governor B...

Страница 17: ...tlet and run to a safe place of discharge Drain pipe must be the same size as the valve discharge connection throughout its entire length and must pitch downward from the valve No shutoff valve shall...

Страница 18: ...IPING SYSTEM BY A PROFESSIONAL ENGINEER Figure 29 Single Pool Heater Installation THIS DIAGRAM IS A RECOMMENDATION AND IS NOT INTENDED TO REPACE AN ENGINEERED PIPING SYSTEM BY A PROFESSIONAL ENGINEER...

Страница 19: ...ch access panels to the opposite sides For instructions on reversing the heat exchanger connections on ASME models call your factory representative 5 ELECTRICAL WIRING NOTE If it is necessary to repla...

Страница 20: ...LACK BLACK BLACK GREEN GREEN WHITE WHITE WHITE GROUND Figure 32 120 VAC Wire Connection Models 240 VAC Wiring For 240 VAC input power to the unit connect the black wire to the L1 or hot leg of the pow...

Страница 21: ...21 6 WIRING DIAGRAM...

Страница 22: ...l panel 3 Rotate control panel down until panel stops Do not force NOTE Caution must be used to not damage controls or wiring F10647 3 KNURLED SCREW Figure 36 Knurled Screw Location Control Adjustment...

Страница 23: ...d UP buttons simultaneously for 3 to 5 seconds The heater will continue to operate while in the Service Menu The first screen displayed is the Flame Strength indicator which indicates the pilot flame...

Страница 24: ...mum Adjustment Refer to step one above to access the program screen Press the MODE button until SPA MAX TEMP appears on the digital display Using the UP and DOWN buttons will change the Maximum Temper...

Страница 25: ...t clear Clock Fireman Sw Time clock fireman switch circuit is open Low Temp Lockout Water temperature below 36 F 2 C Table N Heater Status Messages Active Faults The following conditions are displayed...

Страница 26: ...Heating in the POOL Mode Heating in the SPA Mode Remote Mode Figure 45 Remote Control Menu Remote Operation Activating the Remote To activate or deactivate the remote function 1 Press and hold the UP...

Страница 27: ...e nut on unused wire to the Remote Interface Harness 7 Install the 7 Pin Remote Interface Harness to the P8 connector and turn power ON to the heater See Figure 48 For activation of the remote control...

Страница 28: ...ure switch is closed use a multimeter to check If the pressure switch fails to close either the switch setting is too high or not enough pressure is being supplied by the filter pump 4 Turn the heater...

Страница 29: ...imit Switches High Limit Removal 1 Shut off main electrical power switch to heater 2 Remove inlet outlet sheet metal access panel 3 Remove defective high limit and replace with the correct new high li...

Страница 30: ...combustion blower to blower box 6 Reverse above procedure to reinstall Heat Exchanger Removal 1 Shut water gas and electricity off close valves and relieve pressure then remove relief valve Remove si...

Страница 31: ...cleaning spills use wet sweeping or High Efficiency Particulate Air HEPA filtered vacuum to minimize airborne dust Use feasible engineering controls such as local exhaust ventilation or dust collecti...

Страница 32: ...ating occur or the gas supply fail to shut off turn off the manual gas control to the appliance Visual Inspection Flames can be observed through the opening below the plenum Flame color is blue and ev...

Страница 33: ...nd to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electrica...

Страница 34: ...y look to see if the filter pressure is higher than usual 4 The pump may have lost its prime and be running dry Check the pressure on the filter If there is no pressure then you are not moving water o...

Страница 35: ...lazy flame Low gas pressure Adjust gas pressure Insects or debris clogging burner intake ports Clean burners Outer jacket very hot paint blistered Broken refractory caused by shipping damage or improp...

Страница 36: ...en PC board and pilot operator on gas control Check for 24 VAC across PV MV PV terminals on PC board If voltage is okay replace gas control if not replace PC board NOTE If PC board goes into lockout r...

Страница 37: ...15 21 27 32 38 41 Resistance k 261 1 199 0 153 1 118 8 93 0 73 3 58 3 51 0 If okay replace Circuit Board Sensor Failure Inspect thermistor wires and connector at Terminal P1 Check resistance value of...

Страница 38: ...ent under standard company warranties must be properly tagged with a return parts tag completely filled in with the heater serial number model number etc and shipped to the Company freight prepaid If...

Страница 39: ...C 8 C 14 S 15 M 25 M 20 HP 3 V 1 V 2 V 9 M I S I3 S 2 S 5 HP 4 HP 7 HP 6 HP I2 S 6 HP I5 HP 3 HP 7 S 4 S 17 HM 11 S 4 C 6 M 8 S 8 M 7 M 3 S 3 B 4 B 1 G 10 S 1 B 2 B 2 M 3 J 10 M 6 B 5 B 7 C 1 J 4 S 5...

Страница 40: ...AVAILABLE ON ASME HEATERS UNTIL END Q3 2020 FOR UNITS WITH ASME CAST IRON HEADERS PRIOR TO 12 2019 16 HM 15 HM 12 HM 9 HM 10 HM 2 C 6 M 11 HM 8 HM OPTIONAL 1 M 3 C 6 C 5 HM 17 HM 14 HM 13 HM 2 HM 4 H...

Страница 41: ...EK ADPTER AND POLYMER UNITS PRIOR TO 10 2019 6 M 17 HP 14 HP INLET 13 HP 2 HP 10 HP 12 HP 11 HP 16 HP 1 C 1 M 6 C 19 HP 19 HP 8 HP 15 HP 18 HP OPTIONAL 18 HP 23 M OUTLET 24 M 29 HM 27 HM 22 M 26 HM 24...

Страница 42: ...7 2013 thru 9 2019 006827F 006827F 006827F 006827F Inlet Outlet Header Includes 6 HP Units manufactured from 10 2019 017965F 017965F 017965F 017965F Units manufactured from 7 2013 thru 9 2019 014648F...

Страница 43: ...o 12 2019 010055F 006733F 010057F 010058F Tube Bundle Cupronickel ASME Units manufactured from 12 2019 017978F 017979F 017980F 017981F Units manufactured prior to 12 2019 010368F 010369F 010370F 01037...

Страница 44: ...87F 9 M Gasket Insulation Swaybrace Jacket Top 010350F 010350F 010350F 010350F 10 M Blower Air Pressure Switch Sample Tube 010348F 010348F 010348F 010348F 11 M Touch up Paint Green 750125 750125 75012...

Страница 45: ...Header 010311F 010311F 010311F 010311F Access Panel Set ASME Access Panel Set 3 Pcs for BR Header from 12 2019 017967F 017967F 017967F 017967F Access Panel Set 3 Pcs for CI Header prior to 12 2019 01...

Страница 46: ...46 NOTES...

Страница 47: ...47 NOTES...

Страница 48: ......

Отзывы: