TROUBLESHOOTING - ELECTRICAL
(ELECTRONIC IGNITION IID)
WARNING
HIGH VOLTAGE
For qualified Technicians ONLY
NOTE: Some heaters may be equipped with
an ignition module that shuts off pilot gas if
pilot fails to light. To reset, interrupt power
to heater.
NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout
procedure.
Check line voltage power, low voltage transformer, limit controller, thermostat
(controller) and wiring.
Pull ignition lead and check spark at module.
If spark is okay:
• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
• Check boot of the ignition cable for signs of melting or buckling. Take protective
action to shield cable and boot from excessive temperatures.
If not, replace module.
• Check that all manual gas valves are open, supply tubing and pressures are good,
and pilot burner orifice is not blocked.
• Check electrical connections between module and pilot operator on gas control.
• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is
okay, replace gas control; if not, replace module.
NOTE: If S8600H goes into lockout, reset system. Lockout is used on propane
models.
• Check continuity of ignition cable and ground wire.
• Clean flame rod.
• Check electrical connections between flame rod and module.
• Check for cracked ceramic flame rod insulator.
• Check that pilot flame covers flame rod and is steady and blue.
• Adjust pilot flame.
• If problem persists, replace module.
• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.
• Check electrical connections between module and gas control. If okay, replace
gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.
NOTE: IF S8600H goes into lockout, reset system.
• Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though
operation is normal at the time of checkout.
• Check that pilot flame covers flame rod and is steady and blue.
• If checks are okay, replace module.
• Check for proper thermostat (controller) operation.
• Remove MILLIVOLT lead at module; if valve closes, recheck temperature
controller and wiring; if not, replace gas valve.
START
TURN GAS SUPPLY OFF.
TURN THERMOSTAT
(CONTROLLER) TO CALL
FOR HEAT
POWER TO MODULE
(24 V NOMINAL)?
YES
SPARK ACROSS
IGNITER/SENSOR GAP?
YES
TURN GAS SUPPLY ON
PILOT BURNER LIGHTS?
YES
SPARK STOPS WHEN
PILOT IS LIT?
YES
MAIN BURNER LIGHTS?
YES
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS?
YES
CALL FOR HEAT ENDS
SYSTEM SHUTS OFF?
YES
TROUBLESHOOTING ENDS
NO
NO
NO
NO
NO
NO
NO
Intermittent Pilot System
HONEYWELL S8600
37
Содержание 0133-4001 WH
Страница 19: ...19 FLOW RATES...
Страница 21: ...21 TYPE WH UNITEMP 80 SYSTEM PIPING DIAGRAMS...
Страница 28: ...LOCATION OF CONTROLS 28 400 WH1 WH2 WH3 181 LOW NOx WH1 Fig 9360...
Страница 29: ...29 Fig 9334 LOCATION OF CONTROLS...
Страница 38: ...WIRING DIAGRAM WH2 182 260 38 WIRING DIAGRAMS...
Страница 39: ...WIRING DIAGRAM WH2 330 400 39...
Страница 40: ...40 WIRING DIAGRAM WH2 514 624...
Страница 41: ...41 WIRING DIAGRAM WH2 724 1336...
Страница 42: ...42 WIRING DIAGRAM WH2 1414 1826...
Страница 43: ...43 WIRING DIAGRAM WH2 2100 2500...
Страница 44: ...44 WIRING DIAGRAM WH2 3001 4001...
Страница 45: ...WIRING DIAGRAM WH1 181 261 LOW NOx 45...
Страница 46: ...46 WIRING DIAGRAM WH1 331 401 LOW NOx...