0049-1200-XXX RM16M – USER’S GUIDE 12/29/2010
Rev. C
Page 5
of
27
CHAPTER TWO – INSTALLATION
This chapter describes how to install the Data Shelf.
UNPACKING and INSPECTING the EQUIPMENT
Unpack the equipment and compare the contents to the packing list. Inspect the equipment for any
damage that may have occurred in shipment. If you see any damage or if items are missing, contact
Raymar-Telenetics. Keep the shipping container and packing material for future shipment.
SITE PREPARATION
When selecting a location to install the Data Shelf, choose a site that:
•
Is clean, well lit, and free from extremes of temperature, humidity, appreciable shock, and
vibration.
•
Is within seven feet of a power source that can furnish 48 ±4 VDC at 3.5 amps, or 90 – 265
VAC.
•
Is within 50 feet of the associated data terminal.
•
Provides at least 36 inches of clearance at the front for operating and maintenance accessibility.
•
Provides at least 4 inches at the back of the enclosure for interface cable clearance and
unobstructed airflow.
•
Provides at least 1U above and below the enclosure for airflow.
Side and top clearances for rack-mounted equipment are dictated by the rack-cabinet provisions, but
should allow a free flow of cooling air (Figure 2-1). An optional fan tray (1U), part number 0058-1639-
005 (see below), can be installed to improve airflow.