MODBUS REGISTER ADDRESSES LIST 

Modbus Register Addresses List 

Address 

Hex Address 

Parameter 

Range 

Length 

(Register) 

Data 

Structure 

 

 

 

Min Value 

Max Value 

 

 

40000 

0x00 

Password 

9998 

Integer 

 

 

 

Value 

Meaning 

 

 

40001 

0x01 

Network Selection 

0x0000 

3P4W 

Integer 

 

 

 

0x0001 

3P3W 

 

 

 

 

0x0002 

1P2W-P1 

Integer 

 

 

 

0x0003 

1P2W-P2 

Integer 

 

 

 

0x0004 

1P2W-P3 

Integer 

 

 

 

Min Value 

Max Value 

 

 

40002 

0x02 

CT Secondary (Readable Only) 

Integer 

40003 

0x03 

CT Primary 2 

10000 

Integer 

40004 

0x04 

PT Secondary 

100 

500 

Integer 

40005 

0x05 

PT Primary 

100 

10000 

Integer 

40007 

0x07 

Slave ID 

255 

Integer 

 

 

 

Value 

Meaning 

 

 

40008 

0x08 

Baud Rate 

0x0000 

300 bps 

Integer 

 

 

 

0x0001 

600 bps 

Integer 

 

 

 

0x0002 

1200 bps 

Integer 

 

 

 

0x0003 

2400 bps 

Integer 

 

 

 

0x0004 

4800 bps 

Integer 

 

 

 

0x0005 

9600 bps 

Integer 

 

 

 

0x0006 

19200 bps 

Integer 

40009 

0x09 

Parity 

0x0000 

None 

Integer 

 

 

 

0x0001 

Odd 

Integer 

 

 

 

0x0002 

Even 

Integer 

40010 

0x0A 

Stop Bit 

0x0000 

Integer 

 

 

 

0x000 

Integer 

 

 

 

Min Value 

Max Value 

 

 

40011 

0x0B 

Backlight OFF 

7200 

Integer 

40012 

0x0C 

Factory Default Reset 

Set to factory setting range 

Integer 

40013 

0x0D 

Reset KWh 

Reset Total Active Energy 

Integer 

40014 

0x0E 

Reset KVah 

Reset Total Apparent Energy 

Integer 

40015 

0x0F 

Reset KVArh  

Reset Total Reactive Energy 

Integer 

40016 

0x10 

Auto mode sequence 

18 

Integer 

 

 

 

Page No. 

Meaning 

Integer 

40017 

0x11 

Page Sequence 1 

1-18 

1– First page ; 18-Last page 

Integer 

40018 

1x12 

Page Sequence 2 

1-18 

1– First page ; 18-Last page 

Integer 

40019 

0x13 

Page Sequence 3 

1-18 

1– First page ; 18-Last page 

Integer 

40020 

0x14 

Page Sequence 4 

1-18 

1– First page ; 18-Last page 

Integer 

40021 

0x15 

Page Sequence 5 

1-18 

1– First page ; 18-Last page 

Integer 

40022 

0x16 

Page Sequence 6 

1-18 

1– First page ; 18-Last page 

Integer 

40023 

0x17 

Page Sequence 7 

1-18 

1– First page ; 18-Last page 

Integer 

40024 

0x18 

Page Sequence 8 

1-18 

1– First page ; 18-Last page 

Integer 

40025 

0x19 

Page Sequence 9 

1-18 

1– First page ; 18-Last page 

Integer 

40026 

0x1A 

Page Sequence 10 

1-18 

1– First page ; 18-Last page 

Integer 

40027 

0x1B 

Page Sequence 11 

1-18 

1– First page ; 18-Last page 

Integer 

40028 

0x1C 

Page Sequence 12 

1-18 

1– First page ; 18-Last page 

Integer 

0.1 Resolution [ 1= 0.1 seconds ]  0.01 Resolution [ 1 = 0.01 KWh ] 

 

 

Address 

Hex Address 

Parameter 

Range 

Length 

(Register) 

Data 

Structure 

40029 

0x1D 

Page Sequence 13 

1-18 

1-First page ; 18-Last page 

Integer 

40030 

0x1E 

Page Sequence 14 

1-18 

1-First page ; 18-Last page 

Integer 

40031 

0x1F 

Page Sequence 15 

1-18 

1-First page ; 18-Last page 

Integer 

40032 

0x20 

Page Sequence 16 

1-18 

1-First page ; 18-Last page 

Integer 

40033 

0x21 

Page Sequence 17 

1-18 

1-First page ; 18-Last page 

Integer 

40054 

0x22 

Page Sequence 18 

1-18 

1-First page ; 18-Last page 

Integer 

 

 

 

Value 

 

Meaning 

 

40034 

0x22 

Demand Interval Method 

0x0000 

Sliding 

Integer 

 

 

 

0x000 

Fixed 

 

 

40035 

0x23 

Demand Interval Duration 

Min Value : 1 

Max Value : 30 

Integer 

40036 

0x24 

Demand Interval Length (minutes) 

Min Value : 1 

Max Value : 30 

Integer 

40037 

0x25 

Reset MAX KW 

Reset MAX Active Power 

Integer 

40038 

0x26 

Reset MIN KW 

Reset MIN Active Power 

Integer 

40039 

0x27 

Reset MAX KVar 

Reset MAX Reactive Power 

Integer 

40040 

0x28 

Reset MIN KVar 

Reset MIN Reactive Power 

Integer 

40041 

0x29 

Reset Max KVA 

Reset MAX Apparent Power 

Integer 

Address 

Hex Address  Parameter 

30000 

0x00 

Voltage V1N 

30002 

0x02 

Voltage V2N 

30004 

0x04 

Voltage V3N 

30006 

0x06 

Average Voltage LN 

30008 

0x08 

Voltage V12 

30010 

0x0A 

Voltage V23 

30012 

0x0C 

Voltage V31 

30014 

0x0E 

Average Voltage LL 

30016 

0x10 

Current I1 

30018 

0x12 

Current I2 

30020 

0x14 

Current I3 

30022 

0x16 

Average Current 

30024 

0x18 

KW1 

30026 

0x1A 

KW2 

30028 

0x1C 

KW3 

30030 

0x1E 

KVA1 

30032 

0x20 

KVA2 

30034 

0x22 

KVA3 

30036 

0x24 

KVAr1 

30038 

0x26 

KVAr2 

30040 

0x28 

KVAr3 

30042 

0x2A 

Total KW 

30044 

0x2C 

Total KVA 

30046 

0x2E 

Total KVAr 

30048 

0x30 

PF1 

30050 

0x32 

PF2 

30052 

0x34 

PF3 

30054 

0x36 

Average PF 

30056 

0x38 

Frequency 

30058 

0x3A 

Import KWh 

30060 

0x3C 

Import KVAh 

30062 

0x3E 

Import KVArh 

Readable Parameters : [ Length (Register) : 2 : Data Structure : Float ] 

Address 

Hex Address  Parameter 

30064 

0x40 

KW MAX Active Power 

30066 

0x42 

KW MIN Active Power 

30068 

0x44 

KVAr MAX Reactive Power 

30070 

0x46 

KVAr MIN Reactive Power 

30072 

0x48 

KVA MAX Apparent Power 

30074 

0x4A 

Export KWh 

30076 

0x4C 

Export KVarh 

30132 

0x84 

Serial Number 

30134 

0x86 

Existing MAX Active Power 

30136 

0x88 

Existing MIN Active Power 

30138 

0x8A 

Existing MAX Reactive Power 

30140 

0x8C 

Existing MIN Reactive Power 

30142 

0x8E 

Existing MAX Apparent Power 

Содержание RI-D384-C

Страница 1: ...ty of the operating personnel as well as the instrument If the equipment is not used in the manner specified by the manufacturer it might impair the protection provided by the equipment CAUTION Read the instructions prior to installation and operation of the unit CAUTION Risk of electrical shock WIRING GUIDELINES WARNING 1 To prevent the risk of electric shock power supply to the equipment must be...

Страница 2: ...ack Light 0 7200S 0000 12 0 Demand Interval Method Sliding Fixed Sliding 13 0 Demand Interval Duration 1 30 15 14 0 Demand Interval Length 1 30min 1 15 0 Max auto Pages 1 to 18 18 16 0 Change Page Sequence No Yes No 16 1 Page Sequence 1 No Yes No 16 2 Page Sequence 2 No Yes No 16 3 Page Sequence 3 No Yes No 16 4 Page Sequence 4 No Yes No 16 5 Page Sequence 5 No Yes No 16 6 Page Sequence 6 No Yes N...

Страница 3: ... Integer 40028 0x1C Page Sequence 12 1 18 1 First page 18 Last page 1 Integer 0 1 Resolution 1 0 1 seconds 0 01 Resolution 1 0 01 KWh Address Hex Address Parameter Range Length Register Data Structure 40029 0x1D Page Sequence 13 1 18 1 First page 18 Last page 1 Integer 40030 0x1E Page Sequence 14 1 18 1 First page 18 Last page 1 Integer 40031 0x1F Page Sequence 15 1 18 1 First page 18 Last page 1 ...

Страница 4: ...rvices RI D384 C Page 4 of 4 DM V1 10 Rayleigh Instruments 13 04 16 Specifications subject to change as development is a continuous process RAYLEIGH INSTRUMENTS LIMITED Cutlers Road South Woodham Ferrers Chelmsford CM3 5WA UK ...

Отзывы: